1 - Inspection Details
In Attendance
Occupancy
Style
Temperature (approximate)
Type of Building
Weather Conditions
Excluded items:
The following items have been excluded from the inspection.
Left or right of home
Overview:
Overview
A home inspection is not a pass or fail type of inspection.It is a visual only evaluation of the conditions of the systems and accessible components of the home designed to identify areas of concern within specific systems or components defined by the State Standards of Practice and the InterNachi Standards of Practice, that are both observed and deemed material by the inspector at the exact date and time of inspection. Conditions can and will change after the inspection over time. Future conditions or component failure can not be foreseen or reported on. Components that are not readily accessible can not be inspected.Issues that are considered as cosmetic are not addressed in this report. (Holes, stains, scratches, unevenness, missing trim, paint and finish flaws or odors). It is not the intent of this report to make the house new again.Any and all recommendations for repair, replacement, evaluation, and maintenance issues found, should be evaluated by the appropriate trades contractors within the clients inspection contingency window or prior to closing, which is contract applicable, in order to obtain proper dollar amount estimates on the cost of said repairs and also because these evaluations could uncover more potential issues than able to be noted from a purely visual inspection of the property. This inspection will not reveal every concern or issue that exists, but only those material defects that were observable on the day of the inspection. This inspection is intended to assist in evaluation of the overall condition of the dwelling only. This inspection is not a prediction of future conditions and conditions with the property are subject to change the moment we leave the premises.
Information:
Categories
Listed below is a description of the Categories used throughout the report to help understand the severity of an item. Any items list in the below categories may be based on the inspectors opinion. These categories are not designed to be considered as an enforceable repair or responsibility of the current homeowner, but designed to inform the current client of the current condition of the property and structure. They may be used in negotiations between real estate professionals.
Maintenance/Monitor = The item, component, or system while perhaps is functioning as intended may be in need of minor repair, service, or maintenance; is showing wear or deterioration that could result in an adverse condition at some point in the future; or consideration should be made in upgrading the item, component, or system to enhance the function, efficiency, and/or safety. Items that fall into this category frequently be addressed by a homeowner or Licensed Handyman and are considered to be routine homeowner maintenance (DIY) or recommended upgrades.
Deficiencies = The item, component, or system while perhaps functioning as intended is in need of moderate repair, service, is showing signs of wear or deterioration that could result is an adverse condition at some point in the future; consideration should be made in upgrading the item, component, or system to enhance the function, efficiency and/or safety. Items falling into this category can frequently be addressed by a licensed handyman or qualified contractor of trade and are not considered routine maintenance or DIY items.
Safety & Immediate Attention = The item, component, or system poses a safety concern to occupants in or around the home. Some listed concerns may have been considered acceptable for the time of the structures construction, but pose a current risk.
The item, component or system is not functioning as intended, or needs further inspection by a qualified license contractor of trade; possible damage to the structure, item, or component may occur. Repairs may be possible to satisfactory condition with out repair.
Condo Inspection
This inspection was limited to the areas and items that were accessible to the inspector. Items owned or covered by an association are not included in this inspection. Any mention of those items is simply done as a courtesy.
2 - Roof
IN | NI | NP | D | ||
---|---|---|---|---|---|
2.1 | Coverings | X | |||
2.2 | Roof Drainage Systems | X | X | ||
2.3 | Flashings | X | |||
2.4 | Skylights, Chimneys & Other Roof Penetrations | X |
Inspection Method
Roof Type/Style
Coverings:
Material
Roof Drainage Systems:
Gutter Material
Flashings:
Material
Coverings:
Roof Photos



I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Debris
Debris has accumulated in the gutters. Recommend cleaning to facilitate water flow.
Here is a DIY resource for cleaning your gutters.
3 - Exterior
IN | NI | NP | D | ||
---|---|---|---|---|---|
3.1 | Foundation | X | |||
3.2 | Siding, Flashing & Trim | X | X | ||
3.3 | Walkways, Patios & Driveways | X | |||
3.4 | Decks, Balconies, Porches & Steps | X | |||
3.5 | Eaves, Soffits & Fascia | X | |||
3.6 | Vegetation, Grading, Drainage & Retaining Walls | X |
Inspection Method
Foundation:
Material
Siding, Flashing & Trim:
Siding Material
Siding, Flashing & Trim:
Siding Style
Walkways, Patios & Driveways:
Driveway / Walkway Material
Decks, Balconies, Porches & Steps:
Material
Decks, Balconies, Porches & Steps:
Appurtenance

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Previous Repair Observed
Previous brick/mortar repair observed at the brick lintel for the garage door.

4 - Garage
IN | NI | NP | D | ||
---|---|---|---|---|---|
4.1 | General | X | |||
4.2 | Ceiling | X | |||
4.3 | Floor | X | |||
4.4 | Walls & Firewalls | X | X | ||
4.5 | Garage Door | X | |||
4.6 | Garage Door Opener | X | |||
4.7 | GFCI | X | |||
4.8 | Occupant Door (From garage to inside of home) | X | |||
4.9 | Lighting | X |
Garage Door:
Material
Garage Door:
Type
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency




Minor Cracking
Minor cracking was observed in the walls. Recommend monitoring for further movement.

5 - Exterior Doors and Windows
IN | NI | NP | D | ||
---|---|---|---|---|---|
5.1 | Exterior Doors | X | X | ||
5.2 | Windows | X |
Exterior Doors:
Exterior Entry Door
Exterior Doors:
Exterior Rear Door
Windows:
Window Manufacturer
Windows:
Window Type
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Screen Door Track
Screen door track is loose. Recommend repair by licensed professional.

6 - Electrical
IN | NI | NP | D | ||
---|---|---|---|---|---|
6.1 | Service Entrance Conductors | X | |||
6.2 | Main & Subpanels, Service & Grounding, Main Overcurrent Device | X | |||
6.3 | Branch Wiring Circuits, Breakers & Fuses | X |
Service Entrance Conductors:
Electrical Service Conductors
Main & Subpanels, Service & Grounding, Main Overcurrent Device:
Main Panel Location
Main & Subpanels, Service & Grounding, Main Overcurrent Device:
Panel Capacity
Main & Subpanels, Service & Grounding, Main Overcurrent Device:
Panel Manufacturer
Main & Subpanels, Service & Grounding, Main Overcurrent Device:
Panel Type
Main & Subpanels, Service & Grounding, Main Overcurrent Device:
Sub Panel Location
Branch Wiring Circuits, Breakers & Fuses:
Branch Wire 15 and 20 AMP
Branch Wiring Circuits, Breakers & Fuses:
Wiring Method
I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
7 - Heating & Cooling
IN | NI | NP | D | ||
---|---|---|---|---|---|
7.1 | General | X | |||
7.2 | HVAC Heat Pump Equipment | X | |||
7.3 | Normal Operating Controls | X | |||
7.4 | Distribution System | X | |||
7.5 | Heating & Cooling Source | X |
HVAC Heat Pump Equipment:
Air Handler / Evaporator Brand
HVAC Heat Pump Equipment:
Condenser Unit Brand
HVAC Heat Pump Equipment:
Energy Source/Type
Distribution System:
Configuration
Heating & Cooling Source:
Heating/Cooling Source
Normal Operating Controls:
Thermostat Brand

General:
HVAC Split System - Heat Pump
This home employs a HVAC Heat Pump to both cool and heat the home. It's a split system that utilizes an outdoor condenser (or heat pump) unit and inside air handler/evaporator unit.
A heat pump is a heat transporter constantly moving warm air from one place to another, to where it's needed or not needed, depending on the season. Even in air that seems too cold, heat energy is present. When it's cold outside a heat pump extracts this outside heat and transfers it inside. When it's warm outside, it reverses directions and acts like an air conditioner, removing heat from your home.

HVAC Heat Pump Equipment:
Estimated Air Handler / Evaporator Age
Air Handler/ Evaporator built in 2003. Unit is late service life of a standard industry recognized 12-15 years lifespan.

HVAC Heat Pump Equipment:
Air Handler / Evaporator Coil Photos


HVAC Heat Pump Equipment:
Estimated Condenser Age
Condensor unit was built in 2006. Unit is early service life of a standard industry recognized 12-15 years lifespan.

HVAC Heat Pump Equipment:
Condenser Photos


- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency


Insulation Missing or Damaged

8 - Kitchen
IN | NI | NP | D | ||
---|---|---|---|---|---|
8.1 | Dishwasher | X | |||
8.2 | Refrigerator | X | |||
8.3 | Range/Oven/Cooktop | X | |||
8.4 | Garbage Disposal | X | |||
8.5 | Ceilings | X | |||
8.6 | Walls | X | X | ||
8.7 | Floors | X | |||
8.8 | Doors | X | |||
8.9 | Windows | X | X | ||
8.10 | Lighting Fixtures, Switches & Receptacles | X | |||
8.11 | GFCI & AFCI | X | |||
8.12 | Countertops & Cabinets | X | |||
8.13 | Water Supply, Distribution Systems & Fixtures | X |
Dishwasher:
Brand
Refrigerator:
Brand
Range/Oven/Cooktop:
Exhaust Hood Type
Range/Oven/Cooktop:
Range/Oven Energy Source
Range/Oven/Cooktop:
Anti-Tip
Ceilings:
Ceiling Material
Walls:
Wall Material
Floors:
Floor Coverings
Countertops & Cabinets:
Cabinetry
Countertops & Cabinets:
Countertop Material
Water Supply, Distribution Systems & Fixtures:
Distribution Material
Water Supply, Distribution Systems & Fixtures:
Water Supply Material
Range/Oven/Cooktop:
Range/Oven Brand

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Minor Corner Cracks
Minor cracks at the corners of doors and windows in walls. Appeared to be the result of long-term settling. Some settling is not unusual in a home of this age and these cracks are not a structural concern.
9 - Master Bedroom
IN | NI | NP | D | ||
---|---|---|---|---|---|
9.1 | General | X | |||
9.2 | Doors | X | |||
9.3 | Windows | X | X | ||
9.4 | Floors | X | |||
9.5 | Walls | X | X | ||
9.6 | Ceilings | X | |||
9.7 | Lighting Fixtures, Switches & Receptacles | X | |||
9.8 | GFCI & AFCI | X | |||
9.9 | Smoke Detectors | X | |||
9.10 | Carbon Monoxide Detectors | X |
Floors:
Floor Coverings
Walls:
Wall Material
Ceilings:
Ceiling Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Window Tight/Loud
Upper sash is tight to lower and makes a loud scratching sound. Recommend repair by licensed professional


Minor Corner Cracks
Minor cracks at the corners of doors and windows in walls. Appeared to be the result of long-term settling. Some settling is not unusual in a home of this age and these cracks are not a structural concern.
10 - Bedroom 2
IN | NI | NP | D | ||
---|---|---|---|---|---|
10.1 | General | X | |||
10.2 | Doors | X | |||
10.3 | Windows | X | |||
10.4 | Floors | X | |||
10.5 | Walls | X | |||
10.6 | Ceilings | X | |||
10.7 | Lighting Fixtures, Switches & Receptacles | X | |||
10.8 | GFCI & AFCI | X | |||
10.9 | Smoke Detectors | X | |||
10.10 | Carbon Monoxide Detectors | X |
Floors:
Floor Coverings
Walls:
Wall Material
Ceilings:
Ceiling Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
11 - Loft Area
IN | NI | NP | D | ||
---|---|---|---|---|---|
11.1 | General | X | |||
11.2 | Doors | X | |||
11.3 | Windows | X | |||
11.4 | Floors | X | X | ||
11.5 | Walls | X | |||
11.6 | Ceilings | X | X | ||
11.7 | Lighting Fixtures, Switches & Receptacles | X | |||
11.8 | GFCI & AFCI | X | |||
11.9 | Smoke Detectors | X | |||
11.10 | Carbon Monoxide Detectors | X |
Floors:
Floor Coverings
Walls:
Wall Material
Ceilings:
Ceiling Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Possible Electrical Box In Floor
Possible electrical box in the floor. Recommend inquiring with current owners as to the nature of this equipment.


Nail Pop
Nail pop observed in the ceiling. Recommend repair by licensed professional.

12 - Bedroom 3
IN | NI | NP | D | ||
---|---|---|---|---|---|
12.1 | General | X | |||
12.2 | Doors | X | X | ||
12.3 | Windows | X | |||
12.4 | Floors | X | |||
12.5 | Walls | X | X | ||
12.6 | Ceilings | X | |||
12.7 | Lighting Fixtures, Switches & Receptacles | X | |||
12.8 | GFCI & AFCI | X | |||
12.9 | Smoke Detectors | X | |||
12.10 | Carbon Monoxide Detectors | X |
Floors:
Floor Coverings
Walls:
Wall Material
Ceilings:
Ceiling Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
Door Doesn't Latch

Wall Cracking
Minor cracking observed in the walls. Recommend repair by licensed professional.

13 - Master Bathroom
IN | NI | NP | D | ||
---|---|---|---|---|---|
13.1 | General | X | |||
13.2 | Doors | X | X | ||
13.3 | Toilet | X | |||
13.4 | Vanity and Vanity Top / Sink | X | |||
13.5 | Shower | X | X | ||
13.6 | Windows | X | |||
13.7 | Floors | X | |||
13.8 | GFCI & AFCI | X | |||
13.9 | Water Supply, Distribution Systems & Fixtures | X | |||
13.10 | Ceilings | X | |||
13.11 | Walls | X | |||
13.12 | Lighting Fixtures, Switches & Receptacles | X | |||
13.13 | Tub | X |
Vanity and Vanity Top / Sink:
Vanity
Vanity and Vanity Top / Sink:
Vanity Top / Sink
Floors:
Floor Coverings
Water Supply, Distribution Systems & Fixtures:
Distribution Material
Water Supply, Distribution Systems & Fixtures:
Water Supply Material
Ceilings:
Ceiling Material
Walls:
Wall Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
Door Doesn't Latch

Shower Equipment Leaks
The shower head leaks at the connection. Recommend repair by licensed professional.

14 - Bathroom 2
IN | NI | NP | D | ||
---|---|---|---|---|---|
14.1 | General | X | |||
14.2 | Doors | X | |||
14.3 | Toilet | X | |||
14.4 | Shower | X | |||
14.5 | Windows | X | |||
14.6 | Floors | X | |||
14.7 | GFCI & AFCI | X | |||
14.8 | Vanity and Vanity Top / Sink | X | |||
14.9 | Water Supply, Distribution Systems & Fixtures | X | |||
14.10 | Ceilings | X | X | ||
14.11 | Walls | X | |||
14.12 | Lighting Fixtures, Switches & Receptacles | X | |||
14.13 | Tub | X |
Floors:
Floor Coverings
Vanity and Vanity Top / Sink:
Vanity
Vanity and Vanity Top / Sink:
Vanity Top / Sink
Water Supply, Distribution Systems & Fixtures:
Distribution Material
Water Supply, Distribution Systems & Fixtures:
Water Supply Material
Ceilings:
Ceiling Material
Walls:
Wall Material
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Nail Pops
Nail pops are when the nails used in the construction process are pushed out by the expansion contraction of the framing members. Thus is completely normal and are usually addressed by the builder during the first year.

15 - Half Bath 1
IN | NI | NP | D | ||
---|---|---|---|---|---|
15.1 | Toilet | X | |||
15.2 | GFCI & AFCI | X | |||
15.3 | Vanity and Vanity Top / Sink | X | |||
15.4 | Water Supply, Distribution Systems & Fixtures | X | |||
15.5 | Lighting Fixtures, Switches & Receptacles | X | |||
15.6 | Windows | X | |||
15.7 | Doors | X | |||
15.8 | Ceilings | X | |||
15.9 | Walls | X | |||
15.10 | Floors | X |
Vanity and Vanity Top / Sink:
Vanity
Vanity and Vanity Top / Sink:
Vanity Top / Sink
Water Supply, Distribution Systems & Fixtures:
Distribution Material
Water Supply, Distribution Systems & Fixtures:
Water Supply Material
Ceilings:
Ceiling Material
Walls:
Wall Material
Floors:
Floor Coverings
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
16 - Attic
IN | NI | NP | D | ||
---|---|---|---|---|---|
16.1 | General | X | |||
16.2 | Attic Hatch | X | X | ||
16.3 | Electrical | X | |||
16.4 | Insulation | X | |||
16.5 | Ventilation | X |
General:
Ceiling Structure
General:
Inspection Method
General:
Insulation Depth
General:
Insulation Material
General:
Roof Structure
Ventilation:
Ventilation Type
I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency

Door not Latch
Door does not latch. Recommend repair by licensed professional.

17 - Living Room
IN | NI | NP | D | ||
---|---|---|---|---|---|
17.1 | General | X | |||
17.2 | Doors | X | |||
17.3 | Windows | X | |||
17.4 | Floors | X | |||
17.5 | Walls | X | |||
17.6 | Ceilings | X | X | ||
17.7 | Lighting Fixtures, Switches & Receptacles | X | |||
17.8 | GFCI & AFCI | X |
Floors:
Floor Coverings
Walls:
Wall Material
Ceilings:
Ceiling Material

- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency


Minor Cracking
Stair Area
Minor cracking was observed in the ceiling area.
Recommend repair by licensed professional.

18 - Plumbing
IN | NI | NP | D | ||
---|---|---|---|---|---|
18.1 | Main Water Shut-off Device | X | |||
18.2 | Drain, Waste, & Vent Systems | X | |||
18.3 | Water Supply, Distribution Systems & Fixtures | X | |||
18.4 | Exhaust Systems | X | |||
18.5 | Hot Water Systems, Controls, Flues & Vents | X | |||
18.6 | Fuel Storage & Distribution Systems | X |
Water Source
Drain, Waste, & Vent Systems:
Material
Water Supply, Distribution Systems & Fixtures:
Distribution Material
Water Supply, Distribution Systems & Fixtures:
Water Supply Material
Exhaust Systems:
Exhaust Fans
Hot Water Systems, Controls, Flues & Vents:
Capacity
Hot Water Systems, Controls, Flues & Vents:
Location
Hot Water Systems, Controls, Flues & Vents:
Power Source/Type
Hot Water Systems, Controls, Flues & Vents:
Age
Hot Water Systems, Controls, Flues & Vents:
Warranty Coverage
Main Water Shut-off Device:
Location

Hot Water Systems, Controls, Flues & Vents:
Manufacturer
I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding.
I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency
19 - Misc. Interior
IN | NI | NP | D | ||
---|---|---|---|---|---|
19.1 | Smoke Detectors | X | |||
19.2 | Steps, Stairways & Railings | X |
I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.
- IN = Inspected
- NI = Not Inspected
- NP = Not Present
- D = Deficiency