1234 Main St.
Edmond, OK 73003
12/05/2019 9:00AM

Sample agent
agent

Agent Name

Agency Name

Thank you for choosing Home Run Inspections to perform your home inspection!

The inspection itself and the inspection report comply with the requirements of the Standards of Practice of Oklahoma as well as the International Association of Home Inspectors. These Standards of Practice define the scope of a home inspection.  Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report.  We have attached them to this report and linked them in your inspection agreement for your convenience.

This Inspection Report is based on a visual, non-invasive, snapshot-in-time inspection of readily accessible installed systems and components, for a fee, and designed to identify defects within specific systems and components defined by these Standards of Practice that are both observed and deemed material by the inspector.  While every effort is made to identify and report all current or potential issues, please understand that there are simply areas that are not visible or accessible such as within the wall structure or slab, hidden components of appliances, areas blocked by personal property/storage, etc.  

The general home inspection will not reveal every issue that exists or ever could exist, but only those material defects observed and deemed material on the date of the inspection.  Home inspectors cannot predict future conditions, and as such, we cannot be responsible for things that are concealed or occur after the inspection.  

A material defect is a specific issue with a system or component that may have a significant, adverse impact on the value of the property, that is not in normal working order, and/or that poses an unreasonable risk to people.  The fact that a system or component is near, at, or beyond the end of its normal, useful life is not, in itself, a material defect.

An inspector is considered to be a "Generalist" in that the job is to identify and report potential issues rather than diagnose the specific cause of repair items or the method or materials for repair.  For this reason, you will find that it is sometimes recommended to seek further evaluation by a qualified professional.  

The report includes Informational data on various components of the home, Limitations that affected the ability to inspect certain items/areas, and Recommendations for items that require immediate or future attention.

Recommendations are organized into three categories by level of severity: 

1) Upgrades and/or Minor Maintenance RecommendationsThese recommendations are more informational in nature and represent more of a future to-do list rather than something you might use as a negotiation or seller-repair item.  A Summary Report can be created should you choose to view a report without these minor items.

2) Moderate RecommendationsMost items typically fall into this category.  These recommendations may require a qualified contractor to evaluate further and repair or replace, but the cost is somewhat reasonable.  These recommendations may also include maintenance items that if left unattended will result in further damage and expenses. 

3) Significant and/or Safety Concerns - This category is composed of immediate safety concerns and/or items that could represent a significant expense to repair/replace.  

The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein .  The report is copyrighted and may not be used in whole or in part without our express written permission.

This is meant to be an Honest, Impartial, Third-Party assessment. I am more than happy to discuss anything in more detail.  

Please reach out if you have any questions or need further explanation on anything identified in this report.

1 - Inspection Details

General: Weather Conditions
Cloudy
General: In Attendance
Client, Client's Agent, Home Owner
General: Type of Building
Detached, Single Family
General: Occupancy
Occupied, Furnished
General: Utilities On
General Recommendations: Home Set-Up and Maintenance
General Recommendations: No Evidence of Termites Found
General: Home Faces:
West, Southwest
General: Temperature (Approximate)
37 Fahrenheit (F)

The outside temperature will impact various portions of the inspection. If its too cool, we will be unable to fully test the A/C. 

General: Relative Humidity (Interior)
37 %

Except in specialized facilities, the relative humidity in your building should be between 30% and 50%. Condensation on windows, wet stains on walls and ceilings, and musty smells are signs that relative humidity may be high.

General: Extra Photos
General: Items Not Included in the Inspection

Items Not Included Unless Requested and at an Additional Fee:  
Detached Structures
Sprinkler Systems with more than 6 zones
Pool/Spa/Fountains/Waterfalls
Well/Septic

Additional Items Not Covered in the Inspection Include (but not limited to):
Landscaping Drainage Systems
Landscaping Lighting
Fencing
Playground Equipment
Fire Pit
Security System
Televisions
Audio and Visual Equipment
Furniture
Personal Property
Water Softeners and Filtration Systems
Central Vacuum
Refrigerators/Freezers
Washer & Dryer
Intercom Systems
Shower Pan Testing
Carbon Monoxide Detectors
Cosmetic Issues
Decorative Items
Aesthetics or Quality of Finishes
Vermin including Wood-destroying Organisms
Underground Components
Environmental Issues including Asbestos, Mold, Lead

For a complete review of what is included or not included in a home inspection, review the Oklahoma Standards of Practice for Home Inspectors at this link.

The inspector recommends consulting qualified professionals regarding the condition and maintenance of any "not-included" items that are of concern.

Credit
Comment
1.2.1 - General Recommendations

Obtain Information

We recommend obtaining from the Owner (and Public Records) all available Information, User's Guides/Owner's Manuals, Receipts, Warranties, Permits, Insurance Claims, and Warranty Transferability & Fees regarding the Repairs, Upgrades, and Components of the Home & Lot.

Credit
Comment
1.2.2 - General Recommendations

Seller's Disclosures

The seller's disclosures might have information that you should consider along with the information in this inspection report. 

Credit
Comment
1.2.3 - General Recommendations

Home Warranty

We encourage our clients to consider purchasing a 1-Year home warranty.  These can be purchased at any time and may help cover the cost of an expensive repair or appliance replacement such as a water heater or air conditioner. These items are inspected by us, but our inspection is a snapshot in time and is not a warranty or guarantee; home systems can be working perfectly at our inspection and then fail shortly after moving into the home.  (We don't recommend nor offer 90 day home warranties because they are essentially worthless, they have many exclusions, and they are capped at $500 in total coverage; a good 1 year home warranty will cover much more but will still have its limitations and exclusions.)

Credit
Comment
1.2.4 - General Recommendations

Read the Entire Report

The summary of recommended repairs might be everyone's first concern when reading an inspection report, but we strongly recommend that this report be read in its entirety, including looking through the informational sections, the "blue" recommendations, the limitations tab, and standards of practice tab.  We may have noted information, a "blue" recommendation, or a limitation that you would have a question about and want the opportunity to address before you make your home purchase.  The standards of practice provide information about the scope and limitations of a home inspection, what we inspect, and what we do not inspect.  Your inspection agreement also outlines the scope and limitations of an inspection i.e., what an inspection is and is not.  All of these documents will help you have a better understanding and realistic expectations about your inspection and the subject property.  

2 - Exterior

Exterior Doors: Exterior Entry Door- Rear
Storm Door, Combination, Metal Clad
Exterior Doors: Exterior Entry Door- Garage (Man Door)
Metal Clad
Fencing: Fencing Description
Wood
Sprinkler System: Wifi Controlled
Exterior Doors: Exterior Entry Door- Front
Wood
Window Exteriors: Lintels are Painted
Driveways: Driveway Material
Concrete
Patios: Patio Material
Concrete, Stamped Concrete
Decks, Balconies, Appurtenances: Appurtenances
Spa/Hot Tub, Pool, Deck
Eaves, Soffits & Fascia: Materials
Harboard/Plywood
Vegetation, Grading, Drainage & Retaining Walls: French Drains Present
Patio
Masonry Mail Box: Photo
Sprinkler System: Sprinkler System Brand
Rachio
Sprinkler System: Back Flow Preventer Location
Closet
Siding, Flashing & Trim: Siding Style
Masonry, Stucco, Stone
Siding, Flashing & Trim: Siding Material
Brick Veneer, Stucco, Stone Veneer, Wood
Inspection Method
Visual

Inspection of the exterior typically includes: exterior wall covering materials, window and door exteriors, adequate surface drainage, driveway and walkways, window wells, exterior electrical components, exterior plumbing components, potential tree problems, and retaining wall conditions that may affect the structure. 

Note: The General Inspection does not include inspection of detached structures, landscaping, landscape irrigation and drainage systems, fencing, ponds, fountains, decorative items, well & septic systems, or swimming pools/spas unless pre-arranged as ancillary inspections.

Comment on any nearby water courses is not within the scope of our inspection. The owner/occupant may have information regarding the volume of water during adverse weather and if there has been flooding or erosion in the past.

Environmental issues are outside the scope of an inspection.  This includes issues such as mold, lead-based paint, radon, asbestos, meth, rot, pests, and wood-destroying organisms. 

Walkways: Walkway Material
Concrete, Brick
Eaves, Soffits & Fascia: Eaves, Soffits and Fascia
The eaves are the edges of the roof which overhang the face of a wall and, normally, project beyond the side of a building. The eaves form an overhang to throw water clear of the walls.  The Soffit is the underside of the eave whereas the Fascia is the outward-facing vertical portion.
Vegetation, Grading, Drainage & Retaining Walls: Retaining Wall Material
Concrete, Concrete Pavers
Sprinkler System: Sprinkler System Zones Descriptions

Zone 1: Front Flower Bed, Front yard street side

Zone 2: Front Yard

Zone 3: North Front Side Yard

Zone 4: North Back Yard

Zone 5: Backyard Landscaping

Zone 6: South Side Backyard

Zone 7: Front Yard South of Driveway


Siding, Flashing & Trim: Weep Holes Added

Weep holes are necessary to provide ventilation and allow moisture to escape.

Inspection Limited/Prevented By:
Car &/or Storage in Garage, New Finishes/Paint/Trim, Vines/Shrubs/Trees Against the Wall, Exterior Storage

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

Credit
Comment
2.2.1 - Window Exteriors

Missing Screens
2 Patio, 1 South Backyard

The screen is missing at one or more windows. 

Credit
Comment
2.10.1 - Fencing

Damaged Gate Hinge
South

Credit
Comment
2.11.1 - Sprinkler System

Sprinkler Head Defect
Patio

Credit
Comment
2.12.1 - Siding, Flashing & Trim

Cracked Brick and/or Mortar
Garage, FrontPorch

Tuck Pointing recommended to prevent moisture intrusion. 

Credit
Comment
2.12.2 - Siding, Flashing & Trim

Expansion Joint Sealant Missing
North Backyard, South Backyard

Expansion joint sealant is missing.  

Credit
Comment
2.12.3 - Siding, Flashing & Trim

Damaged Siding
West Front Garage

The siding is damaged and should be repaired to prevent further damage and moisture intrusion.  

3 - Roof

Inspection Method
Ground, From Roof Edge, Pole with Camera
Roof Age Determined By
Property Condition Disclosure
Roof Age
2 Years
Coverings: Material
Asphalt, Architectural/Dimensional
Coverings: Number of Layers of Roof Covering
1
Underlayment: Underlayment Material
Mostly Hidden
Roof Drainage Systems: Guttering Coverage
Full Guttering

The inspector recommends having full guttering coverage. 

Roof Drainage Systems: Gutter Material
Seamless Aluminum
Flashings: Material
Galvanized Metal
Roof Type/Style
Gable
Roof Drainage Systems: Guttering Drains Below Ground
Backyard
General Introduction

The roof inspection portion of the General Inspection will not be as comprehensive as an inspection performed by a qualified roofing contractor. Because of variations in installation requirements of the huge number of different roof-covering materials installed over the years, the General Inspection does not include confirmation of proper installation. Inspectors are trained to identify common deficiencies and to recognize conditions that require evaluation by a specialist. Inspection of the roof typically includes visual evaluation of the roof structure, roof-covering materials, flashing, and roof penetrations like chimneys, mounting hardware for roof-mounted equipment, attic ventilation devices, ducts for evaporative coolers, and combustion and plumbing vents. The roof inspection does not include leak-testing and will not certify or warranty the roof against future leakage. Other limitations may apply and will be included in the comments as necessary.

Coverings: Photos
Coverings: Asako Pole Camera Photos
Flashings: General Flashing Description

Flashing is a general term used to describe sheet metal fabricated into shapes and used to protect areas of the roof from moisture intrusion. Inspection typically includes inspection for condition and proper installation of flashing in the following locations: - roof penetrations such as vents, electrical masts, chimneys, mechanical equipment, patio cover attachment points, and around skylights; - junctions at which roofs meet walls; - roof edges; - areas at which roofs change slope; - areas at which roof-covering materials change; and - areas at which different roof planes meet (such as valleys).

Underlayment: Underlayment Disclaimer

The underlayment was hidden beneath the roof-covering material.  Some edges may have been visible.  It was not fully inspected, and the Inspector disclaims responsibility for evaluating its condition or confirming its presence. 

Skylights, Chimneys & Other Roof Penetrations: Flue Inspection Disclaimer

Accurate inspection of the chimney flue lies beyond the scope of the General Home Inspection. Although the Inspector may make comments on the condition of the portion of the flue readily visible from the roof, a full, accurate evaluation of the flue condition would require the services of a specialist. 

Skylights, Chimneys & Other Roof Penetrations: Antennae or Other Installed Accessories Not Inspected

The inspection of antennae or other installed accessories is beyond the scope of the inspection. 

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

Credit
Comment
3.3.1 - Roof Drainage Systems

Debris in Gutters
Southwest Front

Debris has accumulated in the gutters. Clean to facilitate water flow.

Credit
Comment
3.3.2 - Roof Drainage Systems

Downspouts Drain Near Foundation
Northwest Front

One or more downspouts drain too close to the home's foundation. Adjust downspout extensions to drain at least 4-6 feet from the foundation.

4 - Basement, Foundation, Crawlspace & Structure

Inspection Method
Visual, Attic Access
Foundation: Material
Concrete, Slab on Grade
Floor Structure: Material
Concrete, Slab
Floor Structure: Sub-floor
Inaccessible
Floor Structure: Basement/Crawlspace Floor
N/A
Wall Structure: Wood Frame - Brick Veneer
Wall Structure: Wood Frame - Board siding
Ceiling Structure: Sheetrock

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

5 - Garage

Size/Type
3-Car
Garage Door: Material
Metal, Insulated
Garage Door: Type
Sectional
Garage Door Opener: Number of Garage Vehicle Door Openers
2
Garage Door Opener: WiFi Capable
Garage Door Opener: Brand
Chamberlain, Lift Master
Garage Door Opener: Keypad Installed
Occupant Door (From garage to inside of home): Photo
Garage Introduction

Inspection of the garage typically includes examination of the following:

- general structure

- floor, wall and ceiling surfaces

- operation of all accessible conventional doors and door hardware

- overhead door condition and operation including manual and automatic safety component operation and switch placement

- proper electrical condition including Ground Fault Circuit Interrupter (GFCI) protection

- interior and exterior lighting

- stairs and stairways

- proper firewall separation from living space

- proper floor drainage

Garage Door: Overhead Door Introduction

Inspection of overhead garage doors typically includes examination for presence, serviceable condition and proper operation of the following components:

- door condition

- mounting brackets

- automatic opener

- automatic reverse

- photo sensor

- switch placement

- track & rollers

- manual disconnect

Storm Shelter: Storm Shelter Photo
Car/Storage
Credit
Comment
5.1.1 - Ceiling

Separation at Drywall Joint - Door Opener Related

Vibrations from the garage door opener often cause minor separation along nearby drywall joints. This is very common and primarily a cosmetic issue. 

Credit
Comment
5.7.1 - Storm Shelter

Register Storm Shelter

The inspector recommends registering the storm shelter with the local authorities. This will prompt the authorities to check the shelter in the event of an emergency search and rescue.

6 - Attic, Insulation & Ventilation

Exhaust Systems: Bathroom Exhaust Present
Fan with Light, Fan Only, Fan/Heat/Light
Roof Structure & Attic: Material
2" by 6" Rafters/Roof Joists, 24" Centers, OSB, Radiant Barrier Sheathing
Attic Ventilation: Ventilation Type
Passive/Non-Mechanical/Box/Louver/Turtle Vents, Soffit Vents
Attic Photos
Attic Insulation: Insulation Type
Fiberglass Blown

The inspector recommends attic insulation with an R-Value of at least the current IECC standards of R-38.

IECC Standards for Oklahoma 

Attic Insulation: R Value
35-40

R-VALUE BY TYPE

The resistance to heat moving through insulation is measured as "R-value", the higher the R-value, the greater the resistance to heat flow through the insulation.

The inspector recommends attic insulation with an R-Value of at least the current IECC standards of R-38.

IECC Standards for Oklahoma

Attic Insulation: OG&E Energy Audit

If your home is in the OG&E service area, click HERE for information about their Weatherization Program.  You may be eligible for a free energy inspection and free weatherization of your home. 

Attic Ventilation: Attic Ventilation Disclaimer

Attic ventilation disclaimer

The Inspector disclaims confirmation of adequate attic ventilation year-round performance, but will comment on the apparent adequacy of the system as experienced by the inspector on the day of the inspection. Attic ventilation is not an exact science and a standard ventilation approach that works well in one type of climate zone may not work well in another. The performance of a standard attic ventilation design system can vary even with different site locations and conditions or weather conditions within a single climate zone.

The typical approach is to thermally isolate the attic space from the living space by installing some type of thermal insulation on the attic floor. Heat that is radiated into the attic from sunlight shining on the roof is then removed using devices that allow natural air movement to carry hot air to the exterior. This reduces summer cooling costs and increases comfort levels, and can help prevent roof problems that can develop during the winter such as the forming of ice dams along the roof eves.

Natural air movement is introduced by providing air intake vents low in the attic space and exhaust vents high in the attic space.  Thermal buoyancy (the tendency of hot air to rise) causes cool air to flow into the attic to replace hot air flowing out the exhaust vents. Conditions that block ventilation devices, or systems and devices that are poorly designed or installed can reduce the system performance.

Stored Items in Attic

Pull Down Attic Ladder not present.

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

7 - Heating

Upstairs Equipment: Location
Attic
Upstairs Equipment: Energy Source
Natural Gas
Upstairs Equipment: Brand
Carrier
Upstairs Equipment: Heat Type
Gas Forced Air
Upstairs Equipment: Approximate Capacity/BTU
44k
Upstairs Equipment: Efficiency
Mid
Upstairs Equipment: HVAC Filter Location
Upstairs
Upstairs Equipment: HVAC Filter Size
14 x 30
Upstairs Equipment: Thermostat Type
Digital Non-Programmable
Upstairs Equipment: Temperature Differential
30 Indicates Good Performance
Downstairs Equipment: Energy Source
Natural Gas
Downstairs Equipment: Brand
Carrier
Downstairs Equipment: Heat Type
Gas Forced Air
Downstairs Equipment: Approximate Capacity/BTU
110k
Downstairs Equipment: Efficiency
Mid
Downstairs Equipment: HVAC Filter Location
Hallway
Downstairs Equipment: HVAC Filter Size
14 x 30
Downstairs Equipment: Thermostat Type
Digital Programmable, WiFi
Downstairs Equipment: Temperature Differential
35 Indicates Good Performance
Distribution Systems: Ductwork
Insulated, Sealed Duct
Vents, Flues & Chimneys: Chimney & Chimney Liner Material
B Vent, Direct Vent, Metal
Decorative Fireplaces/Gas Logs/Non-Wood Burning: Fuel & Style
Natural Gas, Vented, Direct Vent, Factory Built, Gas logs, Decorative
Upstairs Equipment: Data Plate Photo(s)
Upstairs Equipment: Thermostat Brand
Lux
Downstairs Equipment: Location
Attic
Downstairs Equipment: Data Plate Photo(s)
Downstairs Equipment: Thermostat Brand
Apple Nest
Decorative Fireplaces/Gas Logs/Non-Wood Burning: Gas-Burning Fireplace Photo
Decorative Fireplaces/Gas Logs/Non-Wood Burning: Combustion Source
Exterior
Disclaimer

Inspection of heating systems is limited to basic evaluation based on visual examination and operation using normal controls. Report comments are limited to identification of common requirements and deficiencies. Observed indications that further evaluation is needed will result in referral to a qualified heating, ventilating, and air-conditioning (HVAC) contractor.

Inspection of heating systems typically includes:

- system operation: confirmation of adequate response to the thermostat

- proper location

- proper system configuration

- component condition

- exterior cabinet condition

- fuel supply configuration and condition

- combustion exhaust venting

- air distribution components

- proper condensation discharge

- temperature/pressure relief valve and discharge pipe: presence, condition, and configuration

Upstairs Equipment: Equipment Inspection

Inspection of the furnace typically includes examination/operation of the following:

- cabinet exterior

- fuel supply and shut-off (not tested)

- electrical shut-off

- adequate combustion air

- proper ignition

- burn chamber conditions (when visible)

- exhaust venting

- air filter and blower

- plenum and ducts

- response to the thermostat

- return air system

- condensate drain components (where applicable)

Upstairs Equipment: Age
8

Typical Life Expectancy:

Conventional/Mid Efficiency:  18-25 Years

High Efficiency:  10-15 Years

Downstairs Equipment: Equipment Inspection

Inspection of the furnace typically includes examination/operation of the following:

- cabinet exterior

- fuel supply and shut-off (not tested)

- electrical shut-off

- adequate combustion air

- proper ignition

- burn chamber conditions (when visible)

- exhaust venting

- air filter and blower

- plenum and ducts

- response to the thermostat

- return air system

- condensate drain components (where applicable)

Downstairs Equipment: Age
8

Typical Life Expectancy:

Conventional/Mid Efficiency:  18-25 Years

High Efficiency:  10-15 Years

Heat Exchanger

Only a small portion is visible. 

Wood-Burning Fireplace, Insert, or Stove not present.

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

Credit
Comment
7.1.1 - Upstairs Equipment

No Sediment Trap in Gas Line
Attic

No sediment trap or drip leg was installed at the furnace. Sediment traps and drip legs are installed to keep particulates and moisture out of the gas valve. Particulates or moisture in the gas valve can interfere with burner operation. The inspector recommends repair by a licensed HVAC professional.  

Credit
Comment
7.2.1 - Downstairs Equipment

No Sediment Trap in Gas Line

No sediment trap or drip leg was installed at the furnace. Sediment traps and drip legs are installed to keep particulates and moisture out of the gas valve. Particulates or moisture in the gas valve can interfere with burner operation. The inspector recommends repair by a licensed HVAC professional.  

Credit
Comment
7.3.1 - Distribution Systems

Grills Closed
Various

Some of the ceiling grills/registers were shut.

8 - Cooling

Downstairs Equipment: Brand
Carrier
Downstairs Equipment: Energy Source/Type
Electric Central AC
Downstairs Equipment: Age
8

Typical Life Expectancy: 12-15 Years

Downstairs Equipment: Cooling Capacity/Tonage
5 Tons
Downstairs Equipment: Refrigerant Type
R-410A
Downstairs Equipment: Condensate Overflow Switch
None
Downstairs Equipment: Temperature Differential
Ambient Temperatures Too Cold to Test
Upstairs Equipment: Brand
Carrier
Upstairs Equipment: Energy Source/Type
Electric Central AC
Upstairs Equipment: Age
8

Typical Life Expectancy: 12-15 Years

Upstairs Equipment: Cooling Capacity/Tonage
2 Tons
Upstairs Equipment: Refrigerant Type
R-410A
Upstairs Equipment: Condensate Overflow Switch
None
Upstairs Equipment: Temperature Differential
Ambient Temperatures Too Cold to Test
Distribution System: Configuration
Ducts & Registers, Central, Split
Downstairs Equipment: Location
South Backyard
Downstairs Equipment: Data Plate Photo(s)
Upstairs Equipment: Location
West Backyard
Upstairs Equipment: Data Plate Photo(s)
Disclaimer

Inspection of cooling systems typically includes visual examination of readily observable components for adequate condition, and system testing for proper operation using normal controls. Cooling system inspection will not be as comprehensive as that performed by a qualified heating, ventilating, and air-conditioning (HVAC) system contractor. Report comments are limited to identification of common requirements and deficiencies. Observed indications that further evaluation is needed will result in referral to a qualified HVAC contractor.

Downstairs Equipment: Split System

The air conditioning system was a split system in which the cabinet housing the compressor, cooling fan and condensing coils was located physically apart from the evaporator coils. As is typical with split systems, the compressor/condenser cabinet was located at the exterior so that the heat collected inside the structure could be released to the outside air. Evaporator coils designed to collect heat from the interior were located inside a duct at the furnace and were not directly visible.

Upstairs Equipment: Split System

The air conditioning system was a split system in which the cabinet housing the compressor, cooling fan and condensing coils was located physically apart from the evaporator coils. As is typical with split systems, the compressor/condenser cabinet was located at the exterior so that the heat collected inside the structure could be released to the outside air. Evaporator coils designed to collect heat from the interior were located inside a duct at the furnace and were not directly visible.

Downstairs Equipment: Low Temperature

The air conditioning equipment was not tested due to low outdoor temperature. Air conditioning equipment should not be operated when outdoor temperatures are below 65 degrees within the past or future 24 hours.

Upstairs Equipment: Low Temperature

The air conditioning equipment was not tested due to low outdoor temperature. Air conditioning equipment should not be operated when outdoor temperatures are below 65 degrees within the past or future 24 hours.

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65 Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

Credit
Comment
8.1.1 - Downstairs Equipment

Evaluate A/C When Temps Warm

Air conditioning equipment should not be operated when outdoor temperatures are below 65 degrees within the past or future 24 hours.  The inspector recommends having the air conditioning system evaluated by a licensed HVAC professional when the temperatures are warm enough to do so. Some licensed HVAC technicians have special equipment for testing A/C systems during cold weather.

Credit
Comment
8.1.2 - Downstairs Equipment

No Overflow Switch
Furnace

Credit
Comment
8.2.1 - Upstairs Equipment

Evaluate A/C When Temps Warm

Air conditioning equipment should not be operated when outdoor temperatures are below 65 degrees within the past or future 24 hours.  The inspector recommends having the air conditioning system evaluated by a licensed HVAC professional when the temperatures are warm enough to do so. Some licensed HVAC technicians have special equipment for testing A/C systems during cold weather.

Credit
Comment
8.2.2 - Upstairs Equipment

No Overflow Switch
Attic

Credit
Comment
8.2.3 - Upstairs Equipment

Insulation Missing or Damaged

Refrigerant line insulation is missing and/or damaged.  Missing or damaged insulation on refrigerant lines can cause energy loss and condensation.

Credit
Comment
8.2.4 - Upstairs Equipment

Thermostat Wire Damaged

9 - Electrical

Service Entrance Conductors: Electrical Service Conductors
Below Ground, 220 Volts
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
Eaton
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Service Size
200 Amps
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Disconnect/Service Box Rating
200 Amps
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Sub Panel Location
Pool
Branch Wiring, Circuits, Breakers & Fuses: Branch Wire Material
Copper
Branch Wiring, Circuits, Breakers & Fuses: Wiring Method
Romex
GFCI & AFCI: GFCI Location
Bathrooms, Garage, Exterior, Kitchen, Jetted Tub, Bedrooms
GFCI & AFCI: GFCI Reset Location
At the Receptacle
Smoke Detectors: Location of Smoke Detectors
Hallways and Bedrooms, Upstairs
Carbon Monoxide Detectors: Location of Carbon Monoxide Detector
Unknown
Service Entrance Conductors: Location
South
Structured Wiring/Smart Panel
Hallway Closet
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Garage
GFCI & AFCI: AFCI Protection Installed

Arc-fault circuit interrupter (AFCI) protection was installed to protect electrical circuits in bedrooms. An arc fault circuit interrupter (AFCI) is a circuit protection device designed to protect against fires caused by arcing faults in electrical wiring.

Smoke Detectors: Hard-Wired Smoke Detectors

The home had smoke detectors that were interconnected through the home branch wiring. This means that when one detector is activated, all will be activated, and none will ever need batteries. Each detector should be checked occasionally to make sure it has power. If a detector has power, the indicator light will be illuminated.

Sensor Controlled Lighting
Branch Wiring, Circuits, Breakers & Fuses: Branch Circuit Limitation

Branch circuit wiring consists of wiring distributing electricity to devices such as switches, receptacles, and appliances. Most conductors are hidden behind floor, wall and ceiling coverings and cannot be evaluated by the inspector. The Inspector does not remove cover plates and inspection of branch wiring is limited to proper response to testing of switches and a representative number of electrical receptacles.

Lighting Fixtures, Switches & Receptacles: Disclaimer- Switches

Switches are sometimes connected to fixtures that require specialized conditions, such as darkness or movement, to respond. Sometimes they are connected to electrical receptacles (and sometimes only the top or bottom half of an receptacle). Often, outlets are inaccessible due to furniture or other obstructions. This being said, functionality of all switches in the structure may not be confirmed by the inspector.

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

Credit
Comment
9.2.1 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Loose Breaker

Credit
Comment
9.4.1 - Lighting Fixtures, Switches & Receptacles

Damaged Light Fixture
Kitchen Pantry

A light fixture showed visible damage.

Credit
Comment
9.4.2 - Lighting Fixtures, Switches & Receptacles

Light Inoperable
Backyard, Garage Man Door

Light fixture did not respond to the switch.  The bulb may need to be replaced or there may be a problem with the switch, wiring or light fixture.  

Credit
Comment
9.4.3 - Lighting Fixtures, Switches & Receptacles

Cover Plate(s) Missing
Master Bedroom Closet

At the time of the inspection, one or more electrical cover plates were missing. This condition left energized electrical components exposed to touch.  This is a shock/electrocution hazard. 

Credit
Comment
9.4.4 - Lighting Fixtures, Switches & Receptacles

Loose Receptacle
Office

An electrical receptacle was improperly secured and moved when a plug was inserted. Receptacles should be securely installed to prevent fire, shock and/or electrocution hazard.

Credit
Comment
9.6.1 - Smoke Detectors

Smoke Detectors

The inspector recommends having smoke detectors in the following locations: (1) In all sleeping rooms, (2) Hallways outside of sleeping areas in immediate vicinity of the sleeping rooms. (3) On each level of the dwelling unit including basements. (4) If separated by a door, we also recommend having smoke detectors in the dining room, furnace room, utility room, and hallways not protected by the required Smoke Alarms. The installation of Smoke Alarms in kitchens, unfinished attics, or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation. We recommend installing smoke detectors according to the manufacturers instructions as well as regularly testing and monitoring smoke detectors as their batteries need to be replaced and/or the smoke detectors expire and should be replaced periodically per the manufacturer's instructions.

Credit
Comment
9.7.1 - Carbon Monoxide Detectors

Carbon Monoxide Detectors

The inspector recommends carbon monoxide detectors are installed in the structure and maintained according to manufacturer's instructions.

10 - Plumbing

General: Water Source
Public
Sewage & Drain, Waste, & Vent (DWV) Systems: Sewage System Type
Public
Sewage & Drain, Waste, & Vent (DWV) Systems: Material
PVC
Sewage & Drain, Waste, & Vent (DWV) Systems: Drain Size
3”
Fixtures, Water Supply, & Distribution Systems: Water Supply Material
Not Visible
Fixtures, Water Supply, & Distribution Systems: Distribution Material
Plastic, Pex
Fixtures, Water Supply, & Distribution Systems: Water Flow and Pressure
Average 60-80 psi
Fixtures, Water Supply, & Distribution Systems: Water Filter
None
Fuel Storage & Distribution Systems: CSST Gas Distribution Piping
None
Hot Water Systems, Controls, Flues & Vents: Power Source
Gas
Hot Water Systems, Controls, Flues & Vents: Type
Tankless
Hot Water Systems, Controls, Flues & Vents: Age
8 Near End of Life Expectancy

Typical Life Expectancy:

Conventional:  8 to 12 Years

Tankless:  20 Years

Hot Water Systems, Controls, Flues & Vents: Water Heater Functional at the time of the Inspection
Hot Water Systems, Controls, Flues & Vents: Capacity (Gallons)
Tankless
Main Water Shut-off Device: Location
West Southwest
Streetside
Main Water Shut-off Device: Interior Water Shut Off
Southwest Front Bedroom Closet
Fixtures, Water Supply, & Distribution Systems: Water Pressure Regulator
Southwest Front Bedroom Closet
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
South Front Yard
Gas Meter
Fuel Storage & Distribution Systems: Plumbed for Gas at the Patio
Hot Water Systems, Controls, Flues & Vents: Location
Attic
Hot Water Systems, Controls, Flues & Vents: Data Plate Photo(s)
General: General

Inspection of the plumbing system typically includes visual examination of:

- water supply pipes

- drain, waste and vent (DWV) system

- water heater (type, condition and operation)

- sewage disposal system (designation as public or private)

- gas system

- sump pump (confirmation of installation/operation)

Sewage & Drain, Waste, & Vent (DWV) Systems: Plumbing Clean-Out Location
Front Yard
West Exterior, Under Kitchen Sink
Sewage & Drain, Waste, & Vent (DWV) Systems: Main Line Video-Scan

The inspector attempts to evaluate drain pipes by running water in every drain that has an active fixture while observing its draw and watching for blockages or slow drains. This is not a conclusive test, and only a camera/video-scan of the main line would confirm its actual condition. 

Blockages can  occur, usually relative in severity to the age of the system, and will range from minor clogs in the branch lines, or at the traps beneath sinks, tubs and showers to major blockages in the main line. The minor clogs are easily cleared, either by chemical means or by removing and cleaning out the traps. 

If tree roots grow into the main drain that connects the structure to the public sewer, repairs could become expensive and might include replacing the entire main line. 

An option is to have the main waste line camera/video-scanned. 

You can also obtain an insurance policy that covers blockages and damage to the main line; however, most policies only cover plumbing repairs within the structure or the cost of rooter service, which are usually relatively inexpensive.  


Fixtures, Water Supply, & Distribution Systems: Jetted Tub and GFCI Protection
Present/GFCI Protected
Hot Water Systems, Controls, Flues & Vents: Brand
Navien

Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. 

Here is a nice maintenance guide from Lowe's to help. 

Hot Water Systems, Controls, Flues & Vents: Tankless, Gas

Hot water for the home was supplied by a gas-fired tankless water heater. Tankless water heaters do not store water in a tank like conventional water heaters. When a hot water fixture is opened in the home, water flows into the water heater where it is heated by gas burners before flowing to the open hot water fixture. Tankless water heaters save energy by avoiding the stand-by losses associated with conventional water heaters which must constantly maintain water in a tank at a minimum temperature. Due to calcium build-up on components, tankless water heaters typically require service annually. Failure to service the water heater in a timely manner typically results in a reduced hot water flow rate. The Inspector recommends inspection by a qualified contractor.

General: Water Softener
Garage

The water softener is beyond the scope of the home inspection. 

Main Water Shut-off Device: Washing Machine Operating at the Inspection
Sewage & Drain, Waste, & Vent (DWV) Systems: Most DWV Pipes Not Visible

Most drain, waste and vent pipes were not visible due to wall, ceiling and floor coverings.

Fixtures, Water Supply, & Distribution Systems: Most Not Visible

Most water distribution pipes were not visible due to wall, floor and ceiling coverings. The Inspector disclaims responsibility for inspection of pipes not directly visible.

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

Credit
Comment
10.3.1 - Sewage & Drain, Waste, & Vent (DWV) Systems

Slow Drain
East Hallway Bathroom Bathtub

Slow/poor drainage observed. 

Credit
Comment
10.5.1 - Fuel Storage & Distribution Systems

Unable to Verify Bonding to Ground at Yellow CSST Piping
Attic

We were unable to verify that the yellow CSST gas supply piping is properly bonded to ground. The inspector recommends verification by a licensed electrician that the piping is properly bonded and grounded as required by the manufacturers installation instuctions. Additional information may be found at www.CSSTSafety.com and http://cib.ok.gov/grounding-yellow-csst.




Credit
Comment
10.6.1 - Hot Water Systems, Controls, Flues & Vents

Sediment Trap or Drip Leg Missing

The sediment trap or drip leg was missing at the water heater. Sediment traps and drip legs are installed to keep particulates and moisture out of the gas valve. Particulates or moisture in the gas valve can interfere with water heater burner operation. The Inspector recommends installation of a sediment trap/drip leg by a licensed plumber.

11 - Doors, Windows & Interior

Odors: Odors
None
Windows: Window Type
Single-hung, Thermal, Vinyl Clad
Floors: Floor Coverings
Carpet, Engineered Wood
Ceilings: Ceiling Material
Drywall
Walls: Wall Material
Drywall
Countertops & Cabinets: Countertop Material
Granite
Countertops & Cabinets: Cabinetry Material
Wood
Laundry Facilities: Dryer Vent Material
Unknown
Laundry Facilities: Dryer Exhaust
Vented to Exterior
Laundry Facilities: Dryer Power Source
220 Electric, Gas
Laundry Facilities: Laundry Hook-Up Photo
Storage in cabinets and closets
Windows: Windows Not Inspected
2nd Floor

One or more windows were not inspected because of storage, furnishings, or other limitations to access to the windows.

Laundry Facilities: Hook-Ups Inaccessible

The hookups for the washer and dryer were inaccessible and not inspected due to the presence of the appliances at the time of the inspection. They appeared to be properly installed and in working order.

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

Credit
Comment
11.2.1 - Doors

No Door Stops
Various Throughout

Doors had no stops installed. The inspector recommends that door stops be installed throughout the home to protect the walls.

Credit
Comment
11.2.2 - Doors

Door Missing
Northeast Bedroom Closet, entry door

Credit
Comment
11.3.1 - Windows

Emergency Exit Ladder for Upstairs Bedrooms

The inspector recommends adding a two-story safety exit ladder for emergency egress. 

Credit
Comment
11.3.2 - Windows

Emergency Egress Missing

There is no means of emergency egress in one or more sleeping areas of the home.  Residential sleeping rooms are required to have at least one operable window or exterior door approved for emergency exit in case of a fire. The egress windows are also required in basements with habitable space.

The minimum net clear opening height must be 24 inches and the minimum net clear opening width must be 20 inches.  The minimum net clear opening should be at least 5.7 sq. ft. (5.0 sq. ft. for ground floor).  An egress window must also have a sill height no more than 44 inches above the finished interior floor.

The egress window must be operable from the inside to a full clear opening without the use of a key, tool, or special knowledge.  The window or door should be operable by the average person or child.  

12 - Built-in Appliances

General Appliance Operation

Note: Appliances are operated at the discretion of the Inspector

Door Bell: Camera Doorbell
Dishwasher: Functional at the time of the Inspection
Cooktop: Cooktop Type
Gas
Cooktop: Cooktop Energy Source
Gas
Wall Oven: Wall Oven Energy Source
Electric
Wall Oven: Wall Oven Type
Single
Refrigerator: Functional at the time of the Inspection
Built-in Microwave: Microwave Brand
GE
Built-in Microwave: Functional at the time if the Inspection
Dishwasher: Brand
Cafe, GE
Cooktop: Cooktop Brand
GE
Wall Oven: Wall Oven Brand
GE
Range Hood/Exhaust System: Brand
Ancona
Range Hood/Exhaust System: Type
Vented to the Exterior
Refrigerator: Refrigerator Brand
GE
Built-in Microwave: Microwave Type
Door
Garbage Disposal: Brand
In-Sink-erator
Dishwasher: High Loop Present


The dishwasher had a high loop installed in the drain line at the time of the inspection. The high loop is designed to prevent wastewater from contaminating the dishwasher. This is a proper condition.

Range: Limited Inspection

The General Inspection testing of ovens does not include testing of all oven features, but is limited to confirmation of bake and broil features. You should ask the seller about the functionality of any other features.

Wall Oven: Limited Inspection

The General Home Inspection testing of ovens does not include testing of all oven features, but is limited to confirmation of bake and broil features. You should ask the seller about the functionality of any other features.

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.

13 - Swimming Pools and Spas

General: Type of Pool/Spa:
Inground Pool and Spa
Pool Area Coping, Tile and Decking:: Water Temperature
46
Pool Area Coping, Tile and Decking:: Water Level Adequate
Pool Area Coping, Tile and Decking:: Coping Type:
Stone, Tile
Pool Area Coping, Tile and Decking:: Decking Type:
Stamped Concrete
Vessel Surface:: Interior Finish Material:
Concrete
Pool Electrical:: Electric Controls:
Local Subpanel, Phone App
Pool Electrical:: GFCI Protection
N/A
Pool Electrical:: Wiring Type:
Liquid TIght Conduit
Filtering/Cleaning Type:: Filtering Components:
Skimmer, Pool Sweep
Filtering/Cleaning Type:: Filtration Type:
Cartridge
Filtering/Cleaning Type:: Skimmer Noted:
Filtering/Cleaning Type:: Water Treatment:
Not Clear/Unknown
Pool Plumbing:: Pipes:
PVC
Pool Plumbing:: Fill Valve Type:
Auto-fill valve with float
Pumps:: Appears to be Operational

Pool Pump, Fountain/Waterfall Pump

Pumps:: Appears to be Grounded
Heating:: Age of Heater (Approx) and Photo:
1 New

New System

Heating:: Heater Operational at the Time of the Inspection
Spa Controls:: Control(s):
Spa Side Control, Remote Control

We recommend verifying equipment with seller.

Pool Electrical:: Equipment Bonding:
Pump(s)
Filtering/Cleaning Type:: Filter Brand
Jandy
Filtering/Cleaning Type:: Filter Type
Cartridge
Pumps:: Pump Types:
Circulation, Variable Speed
Heating:: Photo
Accessories: Cleaning Tools
General: Pool and Spa Safety Information:

Pool and Spa Safety Information:

For up to date pool safety recommendations go to the following:

Pool Safely

and

Red Cross Pool Safety

and

Pool Safety Guidelines

and

Barrier Guidelines


Limitations:: Limited Visual Pool Inspection

The objective of our limited visual pool inspection is to determine if the pool and related equipment may benefit from a more thorough inspection by a qualified pool specialist. The scope of our inspection includes a limited visual inspection of the pool electrical system, primary circulation system, pool barrier system, the pool interior surface and surrounding deck. We do not dismantle components such as filters, pumps and heaters. We do not test water chemistry. We do not test or operate pool heaters, cleaning systems, control valves, chemical injectors or similar components.

Limitations:: Pool/Spa View
Safety Devices:: Pool Barrier Requirements

Basic pool barrier requirements include the following:  

* Fence at least 48 inches tall with no horizontal bars or other components that would allow a child to climb the fence

* Self-closing and self-latching gates with latches at least 54 inches above grade


* Self-closing and self-latching doors for all doors from living areas that provide access to the pool with locks at least 54 inches above the floor


* Locks at least 54 inches above the floor on all windows from living areas that provide access to the pool. Heights are usually measured on the side of the barrier away from the pool.

* Pool cover may substitute for other barriers if the cover is motorized and approved by local authorities.

Safety Devices:: Pool Barriers:
Pool Area Fenced Off

All pool fencing should be a minimum of 60 inches with the latch a minimum of 54 inches off the grade. Gates should be self-closing and self-latching and open away from the pool/spa area.

Drains:: Drain Type(s):
Anti-vortex Drain Covers
Pool Electrical:: Circuit Breaker Location(s):
Equipment Area
Control Valves:: Valve Type(s):
Standard Manual Valves, Automatic Valves with Actuator, Phone App Controlled
Heating:: Heating Type:
Natural Gas Heater
Filtering/Cleaning Type:: Filters Not Visible

Filters are typically not visible at the time of the inspection.  They are a regular maintenance item that the owner should be prepared to replace and or clean regularly.

Credit
Comment
13.3.1 - Safety Devices:

Door alarms are not installed.

All doors that lead to the pool area should be protected with door alarms unless separate pool fencing is installed.
Credit
Comment
13.3.2 - Safety Devices:

Perimeter gates do not comply with barrier requirement.

The perimeter gates that provide access to the pool/spa area should be self-closing and self-latching and open away from the pool area.