1234 Main St.
Garland Texas 75043
11/13/2018 9:00AM

Sample agent
agent

Agent Name

Agency Name

1 - Information

Type of Building
Single Family
Occupancy
Furnished, Occupied
In Attendance
Buyer
Weather Conditions
Clear
Temp (approx)
Over 90
Front Faces
Northeast

M

SCOPE 22 TAC 535.227(a) (1) These standards of practice apply when a professional inspector or real estate inspector who is licensed under this chapter accepts employment to perform a real estate inspection for a prospective buyer or seller of real property. (2) These standards of practice define the minimum requirements for a real estate inspection conducted on a one to four family unit that is substantially completed. Substantially completed means the stage of construction when a new building, addition, improvement, or alteration to an existing building can be occupied or used for its intended purpose . (3) For the purposes of these standards of practice a real estate inspection : (A) is a limited visual survey and basic performance evaluation of the systems and components of a building using normal controls that provides information regarding the general condition of a residence at the time of inspection; (B) is not intended to be a comprehensive investigation or exploratory probe to determine the cause or effect of deficiencies noted by the inspector; and (C) does not require the use of: (i) specialized equipment, including but not limited to : (I) thermal imaging equipment; (II) moisture meters; (III) gas or carbon monoxide detection equipment; (IV) environmental testing equipment and devices; (V) elevation determination devices; or (VI) ladders capable of reaching surfaces over one story above ground surfaces; or (ii) specialized procedures, including but not limited to: (I) environmental testing; (II) elevation measurement; (III) calculations; or (IV) any method employing destructive testing that damages otherwise sound materials or finishes. (4) These standards of practice do not prohibit an inspector from providing a higher level of inspection performance than required by these standards of practice or from inspecting components and systems in addition to those listed under the standards of practice. DEFINITIONS 22 TAC 535.227(b) (1) Accessible -In the reasonable judgment of the inspector, capable of being approached, entered, or viewed without: (A) hazard to the inspector; (B) having to climb over obstacles, moving furnishings or large, heavy, or fragile objects; (C) using specialized equipment or procedures; (D) disassembling items other than covers or panels intended to be removed for inspection; (E) damaging property, permanent construction or building finish; or (F) using a ladder for portions of the inspection other than the roof or attic space. (2) Chapter 1102 - Texas Occupations Code, Chapter 1102. (3) Component - A part of a system. (4) Cosmetic - Related only to appearance or aesthetics, and not related to performance, operability, or water penetration. (5) Deficiency - In the reasonable judgment of the inspector, a condition that: (A) adversely and materially affects the performance of a system, or component; or (B) constitutes a hazard to life, limb, or property as specified by these standards of practice. (6) Deficient--Reported as having one or more deficiencies. (7) Inspect - To operate in normal ranges using ordinary controls at typical settings, look at and examine accessible systems or components and report observed deficiencies as specified by these standards of practice. (8) Performance - Achievement of an operation, function or configuration relative to accepted industry standard practices with consideration of age and normal wear and tear from ordinary use. (9) Report - To provide the inspector's opinions and findings on the standard inspection report form as required by 535.222 and 535.223 of this title. (10)Standards of practice - 535.227 - 535.233 of this title. GENERAL REQUIREMENTS 22 TAC 535.227(c) The inspector shall: (1) operate fixed or installed equipment and appliances listed herein in at least one mode with ordinary controls at typical settings; (2) visually inspect accessible systems or components from near proximity to the systems and components, and from the interior of the attic and crawl spaces; and (3) complete the standard inspection report form as required by 535.222 and 535.223 of this title. GENERAL LIMITATIONS 22 TAC 535.227(d) The inspector is not required to: (1) inspect: (A) items other than those listed within these standards of practice; (B) elevators; (C) detached buildings, decks, docks, fences, or waterfront structures or related equipment; (D) anything buried, hidden, latent, or concealed; (E) sub-surface drainage systems; (F) automated or programmable control systems, automatic shut-off, photoelectric sensors, timers, clocks, metering devices, signal lights, lightning arrestor system, remote controls, security or data distribution systems, solar panels or smart home automation components; or (G) concrete flatwork such as driveways, sidewalks, walkways, paving stones or patios; (2) report: (A) past repairs that appear to be effective and workmanlike except as specifically required by these standards; (B) cosmetic or aesthetic conditions; or (C) wear and tear from ordinary use; (3) determine: (A) the presence or absence of pests, termites, or other wood-destroying insects or organisms; (B) the presence, absence, or risk of: (i) asbestos; (ii) lead-based paint; (iii) mold, mildew; (iv) corrosive or contaminated drywall "Chinese Drywall"; or (v) any other environmental hazard, environmental pathogen, carcinogen, toxin, mycotoxin, pollutant, fungal presence or activity, or poison; (C) types of wood or preservative treatment and fastener compatibility; or (D) the cause or source of a condition; (E) the cause or effect of deficiencies; (F) any of the following issues concerning a system or component: (i) insurability or warrantability; (ii) suitability, adequacy, compatibility, capacity, reliability, marketability, or operating costs; (iii) recalls, counterfeit products, or product lawsuits; (iv) life expectancy or age; (v) energy efficiency, vapor barriers, or thermostatic performance; (vi) compliance with any code, listing, testing or protocol authority; (vii) utility sources; or (viii)manufacturer or regulatory requirements, except as specifically required by these standards; (4) anticipate future events or conditions, including but not limited to: (A) decay, deterioration, or damage that may occur after the inspection; (B) deficiencies from abuse, misuse or lack of use; (C) changes in performance of any component or system due to changes in use or occupancy; (D) the consequences of the inspection or its effects on current or future buyers and sellers; (E) common household accidents, personal injury, or death; (F) the presence of water penetrations; or (G) future performance of any item; (5) operate shut-off, safety, stop, pressure or pressure-regulating valves or items requiring the use of codes, keys, combinations, or similar devices; (6) designate conditions as safe; (7) recommend or provide engineering, architectural, appraisal, mitigation, physical surveying, realty, or other specialist services; (8) review historical records, installation instructions, repair plans, cost estimates, disclosure documents, or other reports; (9) verify sizing, efficiency, or adequacy of the ground surface drainage system; (10) verify sizing, efficiency, or adequacy of the gutter and downspout system; (11) operate recirculation or sump pumps; (12) remedy conditions preventing inspection of any item; (13) apply open flame or light a pilot to operate any appliance; (14) turn on decommissioned equipment, systems or utility services; or (15) provide repair cost estimates, recommendations, or re-inspection services. CONFLICTS 22 TAC 535.227(e) In the event of a conflict between the general provisions set out in this section, and specific provisions specified elsewhere in the standards of practice, specific provisions shall take precedence. DEPARTURE PROVISION 22 TAC 535.227(f) (1) An inspector may depart from the inspection of a component or system required by the standards of practice only if: (A) the inspector and client agree the item is not to be inspected; (B) the inspector is not qualified to inspect the item; (C) in the reasonable judgment of the inspector, the inspector determines that: (i) conditions exist that prevent inspection of an item; (ii) conditions or materials are hazardous to the health or safety of the inspector; or (iii) the actions of the inspector may cause damage to the property (D) the item is a common element of a multifamily development and is not in physical contact with the unit being inspected, such as the foundation under another building or a part of the foundation under another unit in the same building. (2) If an inspector departs from the inspection of a component or system required by the standards of practice, the inspector shall: (A) notify the client at the earliest practical opportunity that the component or system will not be inspected; and (B) make an appropriate notation on the inspection report form, stating the reason the component or system was not inspected. (3) If the inspector routinely departs from inspection of a component or system required by the standards of practice, and the inspector has reason to believe that the property being inspected includes that component or system, the earliest practical opportunity for the notice required by this subsection is the first contact the inspector makes with the prospective client.  ENFORCEMENT 22 TAC 535.227(g) Enforcement. Failure to comply with the standards of practice is grounds for disciplinary action as prescribed by Chapter 1102.

2 - I. Structural Systems

IN NI NP D
2.1 A. Foundations X
2.2 B. Grading and Drainage X
2.3 C. Roof Covering Materials X
2.4 D. Roof Structure & Attic X
2.5 E. Walls (Interior and Exterior) X X
2.6 F. Ceilings and Floors X
2.7 G. Doors (Interior and Exterior) X
2.8 H. Windows X X
2.9 I. Stairways (Interior and Exterior) X
2.10 J. Fireplaces and Chimneys X X
2.11 K. Porches, Balconies, Decks, and Carports X
A. Foundations: Type of Foundation(s)
Slab on Grade
A. Foundations: Crawl space viewed from
No crawl space
A. Foundations: Comments
A. Foundations: Performance Opinion
B. Grading and Drainage: Comments
C. Roof Covering Materials: Types of Roof Covering
Composition
C. Roof Covering Materials: Viewed From
Drone
C. Roof Covering Materials: Water Penetrations
Not Present
C. Roof Covering Materials: Prior Repairs
Not Present
C. Roof Covering Materials: Comments
D. Roof Structure & Attic: Average Attic Floor Insulation Depth
11-13
D. Roof Structure & Attic: Water Penetrations
Not Present
D. Roof Structure & Attic: Comments
D. Roof Structure & Attic: Framing Type
Conventional Wood Frame
D. Roof Structure & Attic: Vertical Insulation Thickness
NA
D. Roof Structure & Attic: Insulation Type
Loose Fill
E. Walls (Interior and Exterior): Comments
E. Walls (Interior and Exterior): Material
Wood or Wood Type covering, Fiber Cement Board
F. Ceilings and Floors: Comments
F. Ceilings and Floors: Ceiling Type
Drywall
F. Ceilings and Floors: Floor Type
Tile, Carpet
G. Doors (Interior and Exterior): Comments
H. Windows: Comments
I. Stairways (Interior and Exterior): Comments
J. Fireplaces and Chimneys: Comments
K. Porches, Balconies, Decks, and Carports: Comments
D. Roof Structure & Attic: Viewed From
Decked space only, heavy storage.
Inspector Opinion

All of the information contained herein is the opinion of the inspector, on the day of the inspection.  Conditions may change.  

A. Foundations: Slab Foundation OK

Foundation Is Performing Adequately
In my opinion, the foundation appears to be providing adequate support for the structure at the time of this inspection. I did not observe any apparent evidence that would indicate the presence of adverse performance or significant deficiencies in the foundation. The interior and exterior stress indicators showed little affects of adverse performance and I perceived the foundation to contain no significant unlevelness after walking the 1st level floors.
The home was located in an area known to have expansive soil. Expansive soils are soils which increase to many times their original volume in response to increases in soil moisture content, creating forces which can easily damage home structural components such as foundations, floor slabs, flatwork and interior and exterior wall coverings.
While no major damage was visible at the time of the inspection which in the Inspector's experience could be directly attributed to expansive soils, future damage may be a possibility unless home construction has included a structural design which will accommodate soil movement. Identifying a particular foundation design or determining the likelihood of future problems relating to this condition exceed the scope of the General Home Inspection and would require the services of a qualified engineer ( structural or geotechnical).  

B. Grading and Drainage: Drainage

Proper grading and drainage are required to maintain proper foundation performance and prevent water penetration, which is a conducive condition for wood rot, wood destroying insect intrusion and possible mold growth.


B. Grading and Drainage: No Gutters

The home had no roof drainage system to channel roof drainage away from the foundation.  Excessive moisture levels in soil near the foundation can result in structural failure due to foundation movement or moisture intrusion with the potential to cause structural damage from decay. Moisture intrusion can also cause the development of unhealthy conditions in indoor air related to microbial growth such as mold fungi. The Inspector recommends installation of a roof drainage system to help protect the home structure and occupants.

D. Roof Structure & Attic: Code for Ventilation

Roof Ventiltion
R806.2 Minimum area. The total net free ventilating area shall not be less than 1/150 of the area of the space ventilated except that reduction of the total area to 1/300 is permitted, provided that at least 50 percent and not more than 80 percent of the required ventilating area is provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet (914 mm) above the eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents. As an alternative, the net free cross-ventilation area may be reduced to 1/300 when a vapor barrier having a transmission rate not exceeding 1 perm is installed on the warm-in-winter side of the ceiling.

R806.3Vent and insulation clearance. Where eave or cornice vents are installed, insulation shall not block the free flow of air. A minimum of a 1-inch (25 mm) space shall be provided between the insulation and the roof sheathing and at the location of the vent.

E. Walls (Interior and Exterior): Method

The inspection of interior and exterior walls focuses on structural performance and water penetration issues. The condition of surface finishes and cosmetic blemishes are not noted, except where they may contribute to or be symptomatic of other problems. Areas within finished walls and concealed flashing details (e.g. doors, windows, brick ledges, etc.) are not accessible and beyond the scope of the inspection. Home furnishings, artwork, stored goods, heavy foliage, etc. can obscure damage, water stains, previous repairs, etc., and preclude assessment of these conditions.

As a matter of general home maintenance, it is recommended that all deficiencies in the "exterior envelope" be sealed for energy efficiency and to help prevent water and moisture penetration into the structure. Examples would be caulking doors/windows, replacing worn weather-strip seals, and sealing wall penetrations or openings (around light fixtures, a/c lines etc.)

G. Doors (Interior and Exterior): Method of Inspection

The interior and exterior doors are inspected for proper function including latches and locking mechanisms. Garage doors are inspected for proper operation.

H. Windows: Method

Windows, where accessible, are inspected for proper function including latches and locking mechanisms. Broken panes, broken thermal seals, missing or damaged screens and caulking deficiencies are noted. Safety issues safety glass in required locations and egress issues in sleeping areas are noted.

I. Stairways (Interior and Exterior): Method

The inspection of the stairways is a visual observation of the required component's and focuses on handrails, spindles, railings, and guards etc. The inspector does not exhaustively measure every stairway component.

K. Porches, Balconies, Decks, and Carports: Method

Porches, decks, driveways and carport's are visually inspected for structural defects and safety related deficiencies (e.g. cracks, trip hazards, negative slope towards the structure, differential movement, etc.).

A. Foundations: Client Notice

This inspection is one of first impression and the inspector was not provided with any historical information pertaining to the structural integrity of the inspected real property. This is a limited cursory and visual survey of the accessible general conditions and circumstances present at the time of this inspection.  Opinions are based on general observations made without the use of specialized tools or procedures.  Therefore, the opinions expressed are one of apparent conditions and not of absolute fact and are only good for the date and time of this inspection.

Because some structural movement is tolerated in the DFW area, evaluation of foundation performance is, to a great extent, subjective. Our evaluation of this foundation is a visual review and represents the opinion of the inspector based on his personal experience with similar homes. The inspection does not predict or guarantee future performance. If actual measurements and an engineering evaluation are desired, a qualified engineer should be consulted.

The inspection of the foundation may show it to be providing adequate support for the structure or having movement typical to this region, at the time of the inspection. This does not guarantee the future life or failure of the foundation.  

The Inspector is not a structural engineer. This inspection is not an engineering report or evaluation and should not be considered one, either expressed or implied.  If any cause of concern is noted on this report, or if you want further evaluation, you should consider an evaluation by an engineer of your choice.

A. Foundations: Access Limitation

Foundation inspections are limited to observation of accessible interior and exterior structural components. 

No engineering studies or measurements are made.

 Factors preventing accurate assessment of structural conditions include but are not limited to paint, repairs, surfaces hidden by floor or wall coverings, furnishings, foliage, and masonry.

B. Grading and Drainage: Method

General lot drainage and slope is inspected by visual means only (no measuring devices are used-such means and devices are beyond the scope of our inspection). The findings are, to a great extent, subjective. Our evaluation of the slope of the grade and lot drainage is a visal review and represents the opinion of the inspector based on his personal experience with similar homes. The inspection does not predict or guarantee future performance. If actual measurements and a professional drainage evaluation are desired, a qualified engineer should be consulted.

Inspection of the homes grading and drainage is done by a visual observation of the site around the structure, including surface grade, rain gutters and down spouts, etc. Any visible conditions or symptoms that may indicate a situation that may adversely affect the foundation or indicate water penetration are noted. No soil, topographical or flood plain studies are performed.



C. Roof Covering Materials: Limitation

Roof inspections are limited to visual observations of the accessible surfaces. The roof is inspected from the roof level, only if in the opinion of the inspector it can be done safely and without damaging the roof. Certain types of damage and/or poor workmanship (e.g., improper fastening, manufacturer defects, improper installation etc) may not be apparent during the visual inspection. As such the inspector cannot guarantee that the roof will be free of leaks, nor can the inspector determine the remaining service life of the roof covering. If deficiencies are noted and/or you have concerns about life expectancy, insurability or potential for future problems, we Highly recommend consulting with a Qualified roofing Contractor prior to the expiration of any warranty or option period.  

C. Roof Covering Materials: Life Expectancy

Notice: Life expectancy of the roofing material is not covered by this property inspection report.  If any concerns exist about the roof covering life expectancy or potential for future problems, a roofing specialist should be consulted.  The Inspector cannot offer an opinion or warranty as to whether the roof has leaked in the past, leaks now, or may be subject to future leaks, either expressed or implied.  
The inspection of this roof may show it to be functioning as intended or in need of minor repairs. This inspection does not determine the insurability of the roof. You are strongly encouraged to have your Insurance Company physically inspect the roof, prior to the expiration of any time limitations such as option or warranty periods, to fully evaluate the insurability of the roof.

D. Roof Structure & Attic: Roof Structure Limitations

Inspection of the roof structure and attic is performed by a visual observation of areas and components which can be reasonably and safely accessed. Areas where insulation is covering joists and no visible pathway could be identified will not be traversed

E. Walls (Interior and Exterior): General Limitations

In accordance with industry standards, the inspection is limited to only those surfaces that are exposed and readily accessible. The Inspector does not move furniture, lift floor-covering materials, or remove or rearrange items within closets or on shelving. On your final walk through, or at some point after furniture and personal belongings have been removed, it is important that you inspect the interior portions of the residence that were concealed or otherwise inaccessible at the time of the inspection. Contact the Inspector immediately if any adverse conditions are observed that were not commented on in your inspection report.


In the event the residence was furnished at the time of the inspection and portions of the interior were hidden by the occupant's belongings. In accordance with industry standards, the inspection is limited to only those surfaces that are exposed and readily accessible. The Inspector does not move furniture, lift floor-covering materials, or remove or rearrange items within closets or on shelving. On your final walk through, or at some point after furniture and personal belongings have been removed, it is important that you inspect the interior portions of the residence that were concealed or otherwise inaccessible at the time of the inspection. Contact the Inspector immediately if any adverse conditions are observed that were not commented on in your inspection report.


E. Walls (Interior and Exterior): Heavy Foliage

The heavy foliage growing on, over or around the exterior walls of the structure should be trimmed back at least 18-inches.  The heavy foliage will limit the Inspectors visual observation of the exterior surfaces.  It is advised that any foliage over three feet tall be at least three feet from the foundation.

F. Ceilings and Floors: Ceiling and Floor Limitations

Inspection of ceilings and floors focuses on structural performance and water penetration issues. The condition of surface finishes and cosmetic blemishes are not noted, except where they may contribute to or be symptomatic of other problems. Areas concealed within finished spaces are not accessible and are beyond the scope of an inspection. Home furnishings, artwork, personal items, etc. can obscure damage, water stains, previous repairs, etc., and prevent assessment in these areas.

H. Windows: Seal Limitation

Signs of lost seals in the thermal pane windows may appear and disappear as temperature and humidity changes.  Some windows with lost seals may not be evident at the time of this inspection, some that are noted in the inspection may not be evident later.  Windows are checked in a non-exhaustive manner for obvious fogging.  When lost thermal pane window seals were noted, we recommend all windows be rechecked by a window specialist for further evaluation prior to the expiration of any time limitations such as option or warranty periods.

Our ability to visually detect failed thermal pane window sections in the early stages of seal failure is greatly influenced by outside lighting conditions, cleanliness of the windows, and the presence of screens.

NOTE: The absence of labeled safety glass does not necessarily mean the installed glass is not rated as safety glass. In accordance with the TREC standards we do look for identifying labels where required, but do not definitively test glass surfaces for proper certification when no obvious labels are visible.



J. Fireplaces and Chimneys: General

Examination of concealed or inaccessible portions of the chimney is beyond the scope of our inspection. We do not perform draft or smoke tests. If further review is desired, we recommend consulting with a qualified contractor.

J. Fireplaces and Chimneys: Gas Logs

There are gas logs installed in the firebox at the time of this inspection. I was unable to view the floor of the firebox at the time of this inspection.

FOUNDATIONS 22 TAC 535.228(a) (1) The inspector shall: (A) render a written opinion as to the performance of the foundation; and (B) report: (i) the type of foundations; (ii) the vantage point from which the crawl space was inspected; (C) report present and visible indications of adverse performance of the foundation, such as: (i) binding, out-of-square, or non-latching doors; (ii) framing or frieze board separations; (iii) sloping floors; (iv) window, wall, floor, or ceiling cracks or separations; and (v) rotating, buckling, cracking, or deflecting masonry cladding. (D) report as Deficient: (i) deteriorated materials; (ii) deficiencies in foundation components such as; beams, joists, bridging, blocking, piers, posts, pilings, columns, sills or subfloor; (iii) deficiencies in retaining walls related to foundation performance; (iv) exposed or damaged reinforcement; (v) crawl space ventilation that is not performing; and (vi) crawl space drainage that is not performing. (2) The inspector is not required to: (A) enter a crawl space or any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high; (B) provide an exhaustive list of indicators of possible adverse performance; or (C) inspect retaining walls not related to foundation performance.


GRADING AND DRAINAGE 22 TAC 535.228(b) (1) The inspector shall report as Deficient: (A) drainage around the foundation that is not performing; (B) deficiencies in grade levels around the foundation; and (C) deficiencies in installed gutter and downspout systems. (2) The inspector is not required to: (A) inspect flatwork or detention/retention ponds (except as related to slope and drainage); (B) determine area hydrology or the presence of underground water; or (C) determine the efficiency or performance of underground or surface drainage systems.


ROOF COVERING MATERIALS 22 TAC 535.228(c) (1) The inspector shall: (A) inspect the roof covering materials from the surface of the roof; (B) report: (i) type of roof coverings; (ii) vantage point from where the roof was inspected; (iii) evidence of water penetration; (iv) evidence of previous repairs to the roof covering material, flashing details, skylights and other roof penetrations; and (C) report as Deficient deficiencies in: (i) fasteners; (ii) adhesion; (iii) roof covering materials; (iv) flashing details; (v) skylights; and (vi) other roof penetrations. (2) The inspector is not required to: (A) inspect the roof from the roof level if, in the inspector's reasonable judgment, the inspector: (i) cannot safely reach or stay on the roof; or (ii) significant damage to the roof covering materials may result from walking on the roof; (B) determine: (i) the remaining life expectancy of the roof covering; or (ii) the number of layers of roof covering material; (C) identify latent hail damage; (D) exhaustively examine all fasteners and adhesion, or (E) provide an exhaustive list of locations of deficiencies and water penetrations.


ROOF STRUCTURES AND ATTICS 22 TAC 535.228(d) (1) The inspector shall: (A) report: (i) the vantage point from which the attic space was inspected; (ii) approximate average depth of attic insulation; (iii) evidence of water penetration; (B) report as Deficient: (i) attic space ventilation that is not performing; (ii) deflections or depressions in the roof surface as related to adverse performance of the framing and decking; (iii) missing insulation; (iv) deficiencies in (I) installed framing members and decking; (II) attic access ladders and access openings; and (III) attic ventilators. (2) The inspector is not required to: (A) enter attics or unfinished spaces where openings are less than 22 inches by 30 inches or headroom is less than 30 inches; (B) operate powered ventilators; or (C) provide an exhaustive list of locations of deficiencies and water penetrations.


INTERIOR WALLS, CEILINGS, FLOORS, AND DOORS 22 TAC 535.228(e) (1) The inspector shall: (A) report evidence of water penetration; (B) report as Deficient: (i) deficiencies in the condition and performance of doors and hardware; (ii) deficiencies related to structural performance or water penetration; and (iii) the absence of or deficiencies in fire separation between the garage and the living space and between the garage and its attic. (2) The inspector is not required to: (A) report cosmetic damage or the condition of floor, wall, or ceiling coverings; paints, stains, or other surface coatings; cabinets; or countertops, or (B) provide an exhaustive list of locations of deficiencies and water penetrations.


EXTERIOR WALLS, DOORS, AND WINDOWS 22 TAC 535.228(f) (1) The inspector shall: (A) report evidence of water penetration; (B) report as Deficient: (i) the absence of performing emergency escape and rescue openings in all sleeping rooms; (ii) a solid wood door less than 1-3/8 inches in thickness, a solid or honeycomb core steel door less than 1-3/8 inches thick, or a 20-minute fire-rated door between the residence and an attached garage; (iii) missing or damaged screens; (iv) deficiencies related to structural performance or water penetration; (v) deficiencies in: (I) weather stripping, gaskets or other air barrier materials; (II) claddings; (III) water resistant materials and coatings; (IV) flashing details and terminations; (V) the condition and performance of exterior doors, garage doors and hardware; and (VI) the condition and performance of windows and components. (2) The inspector is not required to: (A) report the condition of awnings, blinds, shutters, security devices, or other nonstructural systems; (B) determine the cosmetic condition of paints, stains, or other surface coatings; or (C) operate a lock if the key is not available. (D) provide an exhaustive list of locations of deficiencies and water penetrations.


EXTERIOR AND INTERIOR GLAZING 22 TAC 535.228(g) (1) The inspector shall report as Deficient: (A) insulated windows that are obviously fogged or display other evidence of broken seals; (B) deficiencies in glazing, weather stripping and glazing compound in windows and doors; and (C) the absence of safety glass in hazardous locations.(2) The inspector is not required to: (A) exhaustively inspect insulated windows for evidence of broken seals; (B) exhaustively inspect glazing for identifying labels; or (C) identify specific locations of damage.


INTERIOR AND EXTERIOR STAIRWAYS 22 TAC 535.228(h) (1) The inspector shall report as Deficient: (A) spacing between intermediate balusters, spindles, or rails for steps, stairways, guards, and railings that permit passage of an object greater than 4 inches in diameter, except that on the open side of the staircase treads, spheres less than 4-3/8 inches in diameter may pass through the guard rail balusters or spindles; and (B) deficiencies in steps, stairways, landings, guardrails, and handrails. (2) The inspector is not required to exhaustively measure every stairway component.


FIREPLACES AND CHIMNEYS 22 TAC 535.228(i) (1) The inspector shall report as Deficient: (A) built-up creosote in accessible areas of the firebox and flue; (B) the presence of combustible materials in near proximity to the firebox opening; (C) the absence of fireblocking at the attic penetration of the chimney flue, where accessible; and (D) deficiencies in the: (i) damper; (ii) lintel, hearth, hearth extension, and firebox; (iii) gas valve and location; (iv) circulating fan; (v) combustion air vents; and (vi) chimney structure, termination, coping, crown, caps, and spark arrestor. (2) The inspector is not required to: (A) verify the integrity of the flue; (B) perform a chimney smoke test; or (C) determine the adequacy of the draft.


PORCHES, BALCONIES, DECKS AND CARPORTS 22 TAC 535.228(j) (1) The inspector shall: (A) inspect: (i) attached balconies, carports, and porches; (ii) abutting porches, decks, and balconies that are used for ingress and egress; and (B) report as Deficient: (i) on decks 30 inches or higher above the adjacent grade, spacings between intermediate balusters, spindles, or rails that permit passage of an object greater than four inches in diameter; and (ii) deficiencies in accessible components. (2) The inspector is not required to: (A) exhaustively measure every porch, balcony, deck, or attached carport components; or (B) enter any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high.



  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
Credit
Comment
2.2.1 - B. Grading and Drainage

Ground Errosion
Right

Ground erosion was observed. Fill dirt is needed against the foundation perimeter wall where the soil line is to low to help support the foundation footer properly.

Yard scissors Landscaping Contractor
Credit
Comment
2.4.1 - D. Roof Structure & Attic

Poor Ventilation

The roof structure attic space does not appear to be adequately ventilated. It is recommended to increase the amount of lower and upper ventilation to help prevent heat buildup in the attic space area. This condition should be further evaluated and corrected as necessary.

Roof Roofing Professional
Credit
Comment
2.5.1 - E. Walls (Interior and Exterior)

Seal Trim/ Penetrations
Various Locations

The area between the exterior veneer and any wall penetration needs to be properly sealed. 

 It is recommended to use elastomeric caulking.

Tools Handyman/DIY
Credit
Comment
2.5.2 - E. Walls (Interior and Exterior)

Trim Damaged
Front , Left & Back

The wood veneer trim has some deterioration or damage.

Tools Handyman/DIY
Credit
Comment
2.6.1 - F. Ceilings and Floors

Subfloor Squeeks
Various Locations

The upstairs sub-floors (flooring) observed to squeak when walked over.

Flooring Flooring Contractor
Credit
Comment
2.8.1 - H. Windows

Window Glass Broken
Breakfast

Cracked and/or broken window glass was observed.

Window Window Repair and Installation Contractor
Credit
Comment
2.10.1 - J. Fireplaces and Chimneys

Damper Clamp

When artificial gas logs are installed in a firebox with a damper; the damper should be permanently blocked open with a damper clamp to prevent accidental spillage of carbon monoxide into the living space.

Fireplace Chimney Repair Contractor

3 - II. Electrical Systems

IN NI NP D
3.1 A. Service Entrance and Panels X X
3.2 B. Branch Circuits, Connected Devices, and Fixtures X
A. Service Entrance and Panels: Comments
A. Service Entrance and Panels: Electric Panel Rating
200
B. Branch Circuits, Connected Devices, and Fixtures: Type of Wiring
Copper
B. Branch Circuits, Connected Devices, and Fixtures: Comments
A. Service Entrance and Panels: Electric Panel location
Garage
Overview

A typical electrical system consists of two distinct components (1) The electric service entrance (e.g. underground or overhead). Underground the conductors are underground and are not visible for observation. Overhead service comes in from the utility pole to a service mast and down to the electrical meter. (2) Service Panel. The service panel determines the capacity of the electric power to the home. The circuits within the service panel distribute the power throughout the home.

General

Inspection of the electrical service system is limited to visible and accessible components of the entrance cables, meter box, service panel and the visible portions of the wiring. The majority of the electrical system is concealed behind walls and ceilings and conditions relating to these inaccessible areas can not be determined. Whenever possible, the dead front cover for the service panel will be removed to investigate the condition of the wiring and circuits. While some deficiencies in an electrical system may be apparent, not all conditions that can lead to an interruption of electrical service, or that may be hazardous, can be identified through a visual inspection. No assessment as to the adequacy of the service capacity relative to current or future consumption is performed.
Inspector is seldom able to locate/identify proper grounding and/or bonding. If buyer desires more information, further evaluation by a licensed electrician is advised.

A. Service Entrance and Panels: General

Not all electrical components are visible to the inspector. The inspector will report deficiencies that are visible at the time of the inspection.  If deficiencies are noted, or if there are any questions or concerns you are advised to have a licensed electrician fully evaluate the homes electrical system prior to the expiration of any warranty or option period.   

B. Branch Circuits, Connected Devices, and Fixtures: General

Electrical devices in a home typically use either 120 or 240 volt electricity. General purpose circuits (lighting, receptacles, fans, etc.) require 120 volts. The major appliances such as clothes dryers, kitchen ranges, electric water heaters, air conditioners, and electric heating units require 240 volts. Inspection of the electrical distribution system is limited to the visible and accessible components of the distribution wiring, receptacles, switches and other connected devices. The majority of the electrical distribution system is concealed behind walls and ceilings and their conditions are not known. The lack of GFCI, protection in presently required locations regardless of the homes age are noted, as required by the Texas Real Estate Commission. Low voltage and ancillary electrical systems such as landscape lighting, generators, etc. are not inspected. Inspection of the doorbells and chimes is limited to testing the operation of the chimes and the physical condition, function, and installation of the doorbell button. Inspection and testing of Intercom systems are not included in this inspection.

In furnished homes all switches and receptacles may not be accessible for inspection or testing.  Receptacles located in garage ceilings and exterior soffits are not individually tested.


B. Branch Circuits, Connected Devices, and Fixtures: Low voltage X inspected

Inspection of low-voltage or decorative lighting lies beyond the scope of the General Home Inspection.
You may wish to have the functionality of any such lighting demonstrated by the seller.

B. Branch Circuits, Connected Devices, and Fixtures: Smoke Detectors

Smoke Detectors
Today's standards require smoke detectors in each bedroom and outside each separate sleeping area on every level of the structure. Smoke detectors should be located on the ceilings at least 18" away from the wall. (Smoke tends to mushroom upward, turning outward toward the center of the ceiling. To Fire Fighters this is known as the mushroom effect, which leaves a dead airspace 18" from a ceiling to a wall corner). Test all alarms weekly or monthly per manufacturers recommendations.  Failure to test, repair defective or install absent alarms, detectors and other safety equipment immediately can result in serious injury or death. Initiate and practice plans of escape and protection for all occupants in case any emergency arises.
 Smoke detectors are tested using the manufacturer supplied test button only. This inspection does not include testing smoke detectors with actual smoke.

B. Branch Circuits, Connected Devices, and Fixtures: Carbon Monoxide Alarms

Carbon Monoxide Alarms
Smoke is heated and rises, thus smoke detectors are placed on the ceiling.  Carbon Monoxide, on the other hand, mixes with our air, and stays closer to the ground.  For this reason it is advised that CO detectors should be mounted at Knee Height (nose level for the average person sleeping).  The Center for Disease Control (CDC) recommends replacing CO alarms every 5 years.   Carbon Monoxide Alarms are tested with the manufacturer test button only. 

B. Branch Circuits, Connected Devices, and Fixtures: Unable to determine switch operation

I was unable to determine the operation end of one or more of the switches.

SERVICE ENTRANCE AND PANELS 22 TAC 535.229 (a) (1) The inspector shall report as Deficient: (A) a drop, weatherhead or mast that is not securely fastened to the building; (B) the absence of or deficiencies in the grounding electrode system; (C) missing or damaged dead fronts or covers plates; (D) conductors not protected from the edges of electrical cabinets, gutters, or cutout boxes; (E) electrical cabinets and panel boards not appropriate for their location; such as a clothes closet, bathrooms or where they are exposed to physical damage; (F) electrical cabinets and panel boards that are not accessible or do not have a minimum of 36-inches of clearance in front of them; (G) deficiencies in: (i) electrical cabinets, gutters, cutout boxes, and panel boards; (ii) the insulation of the service entrance conductors, drip loop, separation of conductors at weatherheads, and clearances; (iii) the compatibility of overcurrent devices and conductors; (iv) the overcurrent device and circuit for labeled and listed 240 volt appliances; (v) bonding and grounding; (vi) conductors; (vii) the operation of installed ground-fault or arc-fault circuit interrupter devices; and (H) the absence of: (i) trip ties on 240 volt overcurrent devices or multi-wire branch circuit; (ii) appropriate connections; (iii) anti-oxidants on aluminum conductor terminations; (iv) a main disconnecting means. (2) The inspector is not required to: (A) determine present or future sufficiency of service capacity amperage, voltage, or the capacity of the electrical system; (B) test arc-fault circuit interrupter devices when the property is occupied or damage to personal property may result, in the inspector's reasonable judgment; (C) conduct voltage drop calculations; (D) determine the accuracy of overcurrent device labeling; (E) remove covers where hazardous as judged by the inspector; (F) verify the effectiveness of overcurrent devices; or (G) operate overcurrent devices.


BRANCH CIRCUITS, CONNECTED DEVICES, AND FIXTURES 22 TAC 535.229 (b) (1) The inspector shall: (A) manually test the installed and accessible smoke and carbon monoxide alarms; (B) report the type of branch circuit conductors; (C) report as Deficient: (i) the absence of ground-fault circuit interrupter protection in all: (I) bathroom receptacles; (II) garage receptacles; (III) outdoor receptacles; (IV) crawl space receptacles; (V) unfinished basement receptacles; (VI) kitchen countertop receptacles; and (VII)receptacles that are located within six feet of the outside edge of a sink; (ii) the failure of operation of ground-fault circuit interrupter protection devices; (iii) missing or damaged receptacle, switch or junction box covers; (iv) the absence of: (I) equipment disconnects; (II) appropriate connections, such as copper/aluminum approved devices, if branch circuit aluminum conductors are discovered in the main or sub-panel based on a random sampling of accessible receptacles and switches; (v) appliances and metal pipes that are not bonded or grounded; (vi) deficiencies in: (I) receptacles; (II) switches; (III) wiring, wiring terminations, junction boxes, devices, and fixtures, including improper location; (IV) doorbell and chime components; (V) smoke and carbon monoxide alarms; (vii) improper use of extension cords; (viii) deficiencies in or absences of conduit, where applicable; and \ (ix) the absence of smoke alarms: (I) in each sleeping room; (II) outside each separate sleeping area

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
Credit
Comment
3.1.1 - A. Service Entrance and Panels

Double Tap Neutral / Ground

There are double tapped neutral and or ground wires on the bus bar.  This may be an as-built condition but Per TREC standards of practice we are required to report this condition as a deficiency.

Electric Electrical Contractor
Credit
Comment
3.1.2 - A. Service Entrance and Panels

Not Labeled Properly

The breakers (overcurrent devices) in the electrical panel are not properly labeled.

Electric Electrical Contractor
Credit
Comment
3.1.3 - A. Service Entrance and Panels

No Anti-Oxidant Aluminum

There was no anti-oxidant gel observed on the exposed aluminum conductor terminations.

Electric Electrical Contractor
Credit
Comment
3.2.1 - B. Branch Circuits, Connected Devices, and Fixtures

CO improper placement

The home contained a carbon monoxide detector located near heating or cooling equipment. This is not a good location. Proper placement of a carbon monoxide detector is important. If you are installing only one carbon monoxide detector, the Consumer Product Safety Commission (CPSC) recommends it be located near sleeping areas where it can wake you if you are asleep. Additional detectors on every level and in every bedroom of a home will provide extra protection. Homeowners should remember not to install carbon monoxide detectors directly above or beside fuel-burning appliances, as appliances may emit a small amount of carbon monoxide upon start-up. A detector should not be placed within fifteen feet of heating or cooking appliances or in or near very humid areas such as bathrooms.

Tools Handyman/DIY

4 - III. Heating, Ventilation & Air Conditioning Systems

IN NI NP D
4.1 A. Heating Equipment X
4.2 B. Cooling Equipment X
4.3 C. Duct System, Chases, and Vents X
A. Heating Equipment: Type of System
Forced Air
A. Heating Equipment: Energy Source
Natural Gas
A. Heating Equipment: Comments
A. Heating Equipment: Furnace unit
Main house unit, Arcoaire
B. Cooling Equipment: Type of System
Central
B. Cooling Equipment: Comments
C. Duct System, Chases, and Vents: Comments
B. Cooling Equipment: AC Unit Information
Main House unit, 2016, 4 Ton, Max 40 amp breaker, Arcoaire, Filter located at unit in attic, Media Filter, 410, Temp differential 21
HVAC Inspection

The inspector will identify the type of HVAC system present and what source(s) of energy is used.  The HVAC system will be operated and checked for proper operation. The location of the HVAC system and clearances as required will also be identified. The flue pipe (if present) will be inspected for condition and proper clearances as required. Gas lines are checked for leaks at the connections and correct installation methods.

Note: When D (D = Deficient) is checked, that indicates that the HVAC system does not appear to be performing as intended. The observations made to support the rendering of this opinion are listed in this report.  This list should not be considered an all inclusive list of deficiencies.  You are advised to have a fully qualified and licensed HVAC service provider perform a  full evaluation of  this HVAC system equipment and repair any and all deficiencies that are found prior to the expiration of any warranty or option period .  

A. Heating Equipment: Too Hot

The operation of the heating system was not checked due to the outside ambient temperature being above 90 Degrees. If any concerns exist about the future operation of the heating equipment, then it is recommended that a Qualified HVAC Technician further inspect and give an evaluation on the operation of the equipment and any further concerns that may exist with this equipment.
At the time, a limited visual inspection will be performed and if any defects are found they will be listed in this section.

B. Cooling Equipment: Overview

During the hot summer months, the condenser (outdoor cooling equipment) unit, in conjunction with the evaporator/air handler (indoor unit), extracts heat from the house and transfers it to the outside.  The cooling equipment is inspected for correct installation of the indoor and outdoor units and clearances as required. A Delta-T (temperature differential of supply and return air) is measured and noted.

Temperature differential readings are a fundamental standard for testing the proper operation of the cooling system. The normal acceptable range is considered approximately between 15 to 23 degrees F. total difference between the return air and supply air. Unusual conditions such as excessive humidity, low outdoor temperatures, and restricted airflow may indicate abnormal operation even through the equipment is functioning basically as designed and occasionally may indicate normal operation in spite of an equipment malfunction.

Note: When D (D = Deficient) is checked, that indicates that the HVAC system does not appear to be performing as intended. The observations made to support the rendering of this opinion are listed in this report.  This list should not be considered an all inclusive list of deficiencies.  You are advised to have a fully qualified and licensed HVAC service provider perform a  full evaluation of  this HVAC system equipment and repair any and all deficiencies that are found prior to the expiration of any warranty or option period .  


Inspection Method

This inspection is a visual observation of components present at the time of the inspection. We do not dismantle components. Current day heat exchangers are sealed units and are not visible for inspection. Heat Pumps are not operated when outdoor temperatures are above 60 degrees due to damage that may occur to the heat pump system

B. Cooling Equipment: Visual observation

A visual observation of all accessible components are inspected. The cooling system will be checked for correct operation. A measurement of the Delta-T checked at the return and supply air vents only will be measured. The cooling equipment will not be operated when the outdoor temperatures fall below 60 degrees due to damage that may occur to the cooling equipment during operation.


C. Duct System, Chases, and Vents: General

Some of the duct work is in areas of the attic that are not readily accessible.  Not all of the duct work is visible.  Some duct work, by design, is hidden in the walls and ceilings.  Only visible ductwork is inspected.

HEATING EQUIPMENT 22 TAC 535.230(a) (1) General requirements. (A) The inspector shall report: (i) the type of heating systems; (ii) the energy sources; (B) The inspector shall report as Deficient: (i) inoperative units; (ii) deficiencies in the thermostats; (iii) inappropriate location; (iv) the lack of protection from physical damage; (v) burners, burner ignition devices or heating elements, switches, and thermostats that are not a minimum of 18 inches above the lowest garage floor elevation, unless the unit is listed for garage floor installation; (vi) the absence of an opening that would allow access to equipment for inspection, service, repair or replacement without removing permanent construction or building finish; (vii) when applicable; a floored passageway and service platform that would allow access for equipment inspection, service, repair or replacement; (viii) deficiencies in mounting and performance of window and wall units; (2) Requirements for electric heating units, the inspector shall report deficiencies in: (A) performance of heat pumps; (B) performance of heating elements; and (C) condition of conductors; and (3) Requirements for gas heating units, the inspector shall report as Deficient: (A) gas leaks; (B) flame impingement, uplifting flame, improper flame color, or excessive scale buildup; (C) the absence of a gas shut-off valve within six feet of the appliance; (D) the absence of a gas appliance connector or one that exceeds six feet in length; (E) gas appliance connectors that are concealed within or extended through walls, floors, partitions, ceilings or appliance housings; and (F) deficiencies in: (i) combustion, and dilution air; (ii) gas shut-off valves; (iii) access to a gas shutoff valves that prohibits full operation; (iv) gas appliance connector materials; and (v) the vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances; and COOLING EQUIPMENT 22 TAC 535.230(b) (1) Requirements for cooling units other than evaporative cooler. (A) The inspector shall report the type of systems; (B) The inspector shall report as Deficient: (i) inoperative units; (ii) inadequate cooling as demonstrated by its performance; (iii) the absence of an opening that would allow access to equipment for inspection, service, repair or replacement without removing permanent construction or building finish; (iv) when applicable; a floored passageway and service platform that would allow access for equipment inspection, service, repair or replacement; (v) noticeable vibration of blowers or fans; (vi) water in the auxiliary/secondary drain pan; (vii) a primary drain pipe that discharges in a sewer vent; (viii)missing or deficient refrigerant pipe insulation; (ix) dirty coils, where accessible; (x) condensing units lacking adequate clearances or air circulation or that has deficiencies in the fins, location, levelness, or elevation above grade surfaces; (xi) deficiencies in: (I) the condensate drain and auxiliary/ secondary pan and drain system; (II) mounting and performance of window or wall units; and (III) thermostats. (2) Requirements for evaporative coolers. (A) The inspector shall report: (i) type of systems; (ii) the type of water supply line; (B) The inspector shall report as Deficient: (i) inoperative units; (ii) inadequate access and clearances; (iii) deficiencies in performance or mounting; (iv) missing or damaged components; (v) the presence of active water leaks; and (vi) the absence of backflow prevention. DUCT SYSTEMS, CHASES, AND VENTS 22 TAC 535.230(c) (1) The inspector shall report as Deficient: (A) damaged duct systems or improper material; (B) damaged or missing duct insulation; (C) the absence of air flow at accessible supply registers; (D) the presence of gas piping and sewer vents concealed in ducts, plenums and chases; (E) ducts or plenums in contact with earth; and (2) The inspector shall report as Deficient deficiencies in: (A) filters; (B) grills or registers; and (C) the location of return air openings. GENERAL LIMITATIONS 22 TAC 535.230(d) For heating, ventilation, and air conditioning systems inspected under this section, the inspector is not required to perform the following actions: (1) program digital thermostats or controls; (2) inspect: (A) for pressure of the system refrigerant, type of refrigerant, or refrigerant leaks; (B) winterized or decommissioned equipment; or (C) duct fans, humidifiers, dehumidifiers, air purifiers, motorized dampers, electronic air filters, multi-stage controllers, sequencers, heat reclaimers, wood burning stoves, boilers, oil-fired units, supplemental heating appliances, de-icing provisions, or reversing valves; (3) operate: (A) setback features on thermostats or controls; (B) cooling equipment when the outdoor temperature is less than 60 degrees Fahrenheit; (C) radiant heaters, steam heat systems, or unvented gas-fired heating appliances; or (D) heat pumps, in the heat pump mode, when the outdoor temperature is above 70 degrees; (4) verify: (A) compatibility of components; (B) tonnage match of indoor coils and outside coils or condensing units; (C) the accuracy of thermostats; or (D) the integrity of the heat exchanger; or (5) determine: (A) sizing, efficiency, or adequacy of the system; (B) balanced air flow of the conditioned air to the various parts of the building; or (C) types of materials contained in insulation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency

5 - IV. Plumbing Systems

IN NI NP D
5.1 A. Plumbing Supply, Distribution Systems, and Fixtures X X
5.2 B. Drains, Wastes, & Vents X X
5.3 C. Water Heating Equipment X
5.4 D. Hydro-Massage Therapy Equipment X X
Location of Main Water Supply Valve
Front of structure
Location of Water Meter
Within 3 ft of front curb
Comments
A. Plumbing Supply, Distribution Systems, and Fixtures: Comments
B. Drains, Wastes, & Vents: Comments
C. Water Heating Equipment: Comments
D. Hydro-Massage Therapy Equipment: Comments
Static Water Pressure
50-60
C. Water Heating Equipment: Water Heater
Energy Type: Gas, Capacity: 50 Gallon, Craftmaster
C. Water Heating Equipment: general

Water Heaters should be flushed every year or as recommended by the manufacturer to remove sediments that collect at the bottom of the tank. This can be accomplished by attaching a garden hose to the drain valve at the bottom of the heater, directing the discharge water to a safe location and turning the valve on. Caution should be observed as the water coming out will be very hot. The flush is complete when the water comes out clear.


The T & P Valve (Temperature & Pressure Release Valve) should be tested annually for reasons of safety. Follow the manufacturers instructions for testing procedures.


We highly recommend the use of a water alarm at the water heater.  This alarm will sound at the presence of any water leaks and could help prevent major water intrusion events due to failure of the water heater.  These units are available online or at major home improvement centers for about $10 each.

General

Laundry connection faucets and drains are visually inspected only. The faucets are not operated due to the damage that may occur during testing. The refrigerator water supply line and valve are not inspected.  If the inspector finds the water supply valve shutoff to any appliance, no attempt is made to turn the supply on.  

B. Drains, Wastes, & Vents: General

Clean-outs are located around the outside of the structure.  Waste lines appeared to be in satisfactory condition the time of inspection. None of the waste lines were not fully visible at the time of the inspection. The inspector is unable to determine the condition of underground drain lines. At the time of inspection, the water is run at multiple fixtures for an extended period of time. This is generally considered a "functional flow" test. This test cannot simulate the waste flow characteristic of full occupancy. There may be partial blockage of the sanitary drain lines from debris, broken pipes or tree roots that cannot be detected at the time of the inspection. This type of inspection requires specialized equipment (Fiber Optic Cameras).

B. Drains, Wastes, & Vents: Tub and washer

Tub overflow drains are not inspected or tested. Showers were run for an extended period of time. The clothes washer drain line was not inspected or tested at the time of the inspection.

C. Water Heating Equipment: Not accessible

What are heater was an accessible due to heavy storage. 

PLUMBING SYSTEMS 22 TAC 535.231(a) (1)The inspector shall: (A) report: (i) location of water meter; (ii) location of homeowners main water supply shutoff valve; and (iii) static water pressure; (B) report as Deficient: (i) the presence of active leaks; (ii) water pressure in excess of 80 PSI; (iii) the lack of a pressure reducing valve when the water pressure exceeds 80 PSI; (iv) the lack of an expansion tank at the water heater(s) when a pressure reducing valve is in place at the water supply line/system, unless the pressure reducing valve automatically allows for thermal expansion; (v) the absence of: (I) fixture shut-off valves; (II) dielectric unions, when applicable; (III) back-flow devices, anti-siphon devices, or air gaps at the flow end of fixtures; and (vi) deficiencies in: (I) water supply pipes and waste pipes; (II) the installation and termination of the vent system; (III) the performance of fixtures and faucets not connected to an appliance; (IV) water supply, as determined by viewing functional flow in two fixtures operated simultaneously; (V) fixture drain performance; (VI) orientation of hot and cold faucets; (VII) installed mechanical drain stops; (VIII) commodes, fixtures, showers, tubs, and enclosures; and (IX) the condition of the gas distribution system. (2) The inspector is not required to: (A) operate any main, branch, or shut-off valves; (B) operate or inspect sump pumps or waste ejector pumps; (C) verify the performance of: (i) the bathtub overflow; (ii) clothes washing machine drains or hose bibbs; or (iii) floor drains; (D) inspect: (i) any system that has been winterized, shut down or otherwise secured; (ii) circulating pumps, free-standing appliances, solar water heating systems, waterconditioning equipment, filter systems, water mains, private water supply systems, water wells, pressure tanks, sprinkler systems, swimming pools, or fire sprinkler systems; (iii) inaccessible gas supply system components for leaks; (iv) for sewer clean-outs; or (v) for the presence or performance of private sewage disposal systems; or (E) determine: (i) quality, potability, or volume of the water supply; or (ii) effectiveness of backflow or antisiphon devices. WATER HEATERS 22 TAC 535.231(b) (1) General requirements. (A) The inspector shall: (i) report: (I) the energy source; (II) the capacity of the units; (ii) report as Deficient: (I) inoperative units; (II) leaking or corroded fittings or tanks; (III) damaged or missing components; (IV) the absence of a cold water shutoff valve; (V) if applicable, the absence of a pan or a pan drain system that does not terminate over a waste receptor or to the exterior of the building above the ground surface; (VI) inappropriate locations; (VII) the lack of protection from physical damage; (VIII) burners, burner ignition devices or heating elements, switches, or thermostats that are not a minimum of 18 inches above the lowest garage floor elevation, unless the unit is listed for garage floor installation; (IX) the absence of an opening that would allow access to equipment for inspection, service, repair or replacement without removing permanent construction or building finish; (X) when applicable; a floored passageway and service platform that would allow access for equipment inspection, service, repair or replacement; (XI) the absence of or deficiencies in the temperature and pressure relief valve and discharge piping; (XII) a temperature and pressure relief valve that failed to operate, when tested manually; (B) The inspector is not required to: (i) verify the effectiveness of the temperature and pressure relief valve, discharge piping, or pan drain pipes; (ii) operate the temperature and pressure relief valve if the operation of the valve may, in the inspector's reasonable judgment, cause damage to persons or property; or (iii) determine the efficiency or adequacy of the unit. (2) Requirements for electric units, the inspector shall report deficiencies in: (A) performance of heating elements; and (B) condition of conductors; and (3) Requirements for gas units, the inspector shall report as Deficient: (A) gas leaks; (B) flame impingement, uplifting flame, improper flame color, or excessive scale build-up; (C) the absence of a gas shut-off valve within six feet of the appliance; (D) the absence of a gas appliance connector or one that exceeds six feet in length; (E) gas appliance connectors that are concealed within or extended through walls, floors, partitions, ceilings or appliance housings; (F) deficiencies in: (i) combustion and dilution air; (ii) gas shut-off valves; (iii) access to a gas shutoff valves that prohibit full operation; (iv) gas appliance connector materials; and (v) vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances. HYDRO-MASSAGE THERAPY EQUIPMENT 22 TAC 535.231(c) (1) The inspector shall report as Deficient: (A) inoperative units; (B) the presence of active leaks; (C) deficiencies in components and performance; (D) missing and damaged components; (E) the absence of an opening that would allow access to equipment for inspection, service, repair or replacement without removing permanent construction or building finish; and (F) the absence or failure of operation of ground-fault circuit interrupter protection devices; and (2) The inspector is not required to determine the adequacy of self-draining features of circulation systems.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
Credit
Comment
5.1.1 - A. Plumbing Supply, Distribution Systems, and Fixtures

Seal tub spout
2nd Floor Hall Bathroom

Tub spout should be sealed to avoid water intrusion in the wall.

Tools Handyman/DIY
Credit
Comment
5.1.2 - A. Plumbing Supply, Distribution Systems, and Fixtures

Surface damage
2nd Floor Hall Bathroom

The bathtub surface has some damage.

Mag glass Monitor
Credit
Comment
5.1.3 - A. Plumbing Supply, Distribution Systems, and Fixtures

Commode loose
Master Bathroom

The commode is loose at the floor mount.

Pipes Plumbing Contractor
Credit
Comment
5.1.4 - A. Plumbing Supply, Distribution Systems, and Fixtures

Vacuum breaker damaged

The hose bibb vacuum breaker was observed to be damaged

Pipes Plumbing Contractor
Credit
Comment
5.2.1 - B. Drains, Wastes, & Vents

Slow drain = Sink
Master Bathroom

The sink was observed to drain slowly, suggesting that an obstruction may exist.

Pipes Plumbing Contractor
Credit
Comment
5.2.2 - B. Drains, Wastes, & Vents

Laundry drain

Laundry drain is wrapped. This indicates previous issues. Recommend that you request disclosure. 

Contractor Qualified Professional
Credit
Comment
5.3.1 - C. Water Heating Equipment

No sediment trap

There is no sediment trap / drip leg present.  Per the TREC SOP I am required to note this as a deficiency. 

Pipes Plumbing Contractor
Credit
Comment
5.3.2 - C. Water Heating Equipment

Flue not mounted properly top

The draft hood is not properly mounted on the water heater. This configuration will emit Carbon Monoxide into the heater compartment, which is a known safety hazard

Pipes Plumbing Contractor
Credit
Comment
5.3.3 - C. Water Heating Equipment

mechanical attach flue

The water flue should be mechanically attached to the draft hood with a minimum of three sheet metal screws. Improperly attached flue can come loose and emit carbon monoxide.

Pipes Plumbing Contractor
Credit
Comment
5.3.4 - C. Water Heating Equipment

No pan

There is no pan installed under the water heater.   This may be an as-built condition but Per TREC standards of practice we are required to report this condition as a deficiency.

Pipes Plumbing Contractor

6 - V. Appliances

IN NI NP D
6.1 A. Dishwashers X
6.2 B. Food Waste Disposers X
6.3 C. Range Hood and Exhaust Systems X
6.4 D. Ranges, Cooktops, and Ovens X
6.5 E. Microwave Ovens X
6.6 F. Mechanical Exhaust Vents and Bathroom Heaters X
6.7 G. Garage Door Operators X
6.8 H. Dryer Exhaust Systems X
A. Dishwashers: Comments
B. Food Waste Disposers: Comments
C. Range Hood and Exhaust Systems: Comments
C. Range Hood and Exhaust Systems: Exhaust Hood Type
Re-circulate, Updraft
D. Ranges, Cooktops, and Ovens: Comments
E. Microwave Ovens: Comments
F. Mechanical Exhaust Vents and Bathroom Heaters: Comments
G. Garage Door Operators: Comments
H. Dryer Exhaust Systems: Comments
A. Dishwashers: Brand
Kitchenaid
D. Ranges, Cooktops, and Ovens: Range, Cook Top, Oven
Range, Whirlpool
E. Microwave Ovens: Brand
Whirlpool
A. Dishwashers: Normal

The dishwasher is operated in the NORMAL mode.

C. Range Hood and Exhaust Systems: performance

Vents are operated with the switch.  Actual performance level is not evaluated.

G. Garage Door Operators: Close pressure

The close pressure sensor was not tested due to the high probability of damage occurring during this test process.  

GENERAL PROVISIONS 22 TAC 535.232(a) The inspector is not required to: (1) operate or determine the condition of other auxiliary components of inspected items; (2) test for microwave oven radiation leaks; (3) inspect self-cleaning functions; (4) disassemble appliances; (5) determine the adequacy of venting systems; or (6) determine proper routing and lengths of duct systems. DISHWASHERS 22 TAC 535.232(b) The inspector shall report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; (3) rusted, missing or damaged components; (4) the presence of active water leaks; and (5) the absence of backflow prevention. FOOD WASTE DISPOSERS 22 TAC 535.232(c) The inspector shall report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; (3) missing or damaged components; and (4) the presence of active water leaks. RANGE HOODS AND EXHAUST SYSTEMS 22 TAC 535.232(d) The inspector shall report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; (3) missing or damaged components; (4) ducts that do not terminate outside the building, if the unit is not of a re-circulating type or configuration; and (5) improper duct material.  ELECTRIC OR GAS RANGES, COOKTOPS, AND OVENS 22 TAC 535.232(e) The inspector shall report as Deficient: (1) inoperative units; (2) missing or damaged components; (3) combustible material within thirty inches above the cook top burners; (4) absence of an anti-tip device, if applicable; (5) gas leaks; (6) the absence of a gas shutoff valve within six feet of the appliance; (7) the absence of a gas appliance connector or one that exceeds six feet in length; (8) gas appliance connectors that are concealed within or extended through walls, floors, partitions, ceilings or appliance housings; (9) deficiencies in: (A) thermostat accuracy (within 25 degrees at a setting of 350 F); (B) mounting and performance; (C) gas shut-off valves; (D) access to a gas shutoff valves that prohibits full operation; and (E) gas appliance connector materials. MICROWAVE OVENS 22 TAC 535.232(f) The inspector shall inspect built-in units and report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; and (3) missing or damaged components. MECHANICAL EXHAUST SYSTEMS AND BATHROOM HEATERS 22 TAC 535.232(g) The inspector shall report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; (3) missing or damaged components; (4) ducts that do not terminate outside the building; and (5) a gas heater that is not vented to the exterior of the building unless the unit is listed as an unvented type.  GARAGE DOOR OPERATORS 22 TAC 535.232(h) The inspector shall report as Deficient: (1) inoperative units; (2) deficiencies in performance or mounting; (3) missing or damaged components; (4) installed photoelectric sensors located more than six inches above the garage floor; and (5) door locks or side ropes that have not been removed or disabled.  DRYER EXHAUST SYSTEMS 22 TAC 535.232(i) The inspector shall report as Deficient: (1) missing or damaged components; (2) the absence of a dryer exhaust system when provisions are present for a dryer; (3) ducts that do not terminate to the outside of the building; (4) screened terminations; and (5) ducts that are not made of metal with a smooth interior finish.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency

7 - VI. Optional Systems

IN NI NP D
7.1 A. Landscape Irrigation (Sprinkler) Systems X
A. Landscape Irrigation (Sprinkler) Systems: Operated

Made to Last Inspections does not inspect sprinkler systems.  
We are happy to "Operate" the system to the best of our ability, and will make comments in this section regarding our observations.

For a full evaluation of the sprinkler system and associated components we recommend that you contact a Licensed Irrigation Technician.

A. Landscape Irrigation (Sprinkler) Systems: Needs Tune Up

The sprinkler system should be "tuned up".  Currently several of the heads are spraying the house, windows, and concrete flatwork.

LIMITATIONS 22 TAC 535.233(a) An inspector is not required to inspect the components or systems described under this section.  SCOPE 22 TAC 535.233(b) If an inspector agrees to inspect a component or system described under this section, the general provisions under 535.227 and the provisions and requirements of this section applicable to that system or component apply. LANDSCAPE IRRIGATION (SPRINKLER) SYSTEMS 22 TAC 535.233(c) (1) The inspector shall: (A) manually operate all zones or stations on the system through the controller; (B) report as Deficient: (i) the absence of a rain or moisture sensor, (ii) inoperative zone valves; (iii) surface water leaks; (iv) the absence of a backflow prevention device; (v) the absence of shut-off valves between the water meter and backflow device; (vi) deficiencies in the performance and mounting of the controller; (vii) missing or damaged components; and (viii)deficiencies in the performance of the water emission devices; such as, sprayer heads, rotary sprinkler heads, bubblers or drip lines. (2) The inspector is not required to inspect: (A) for effective coverage of the irrigation system; (B) the automatic function of the controller; (C) the effectiveness of the sensors; such as, rain, moisture, wind, flow or freeze sensors; or (D) sizing and effectiveness of backflow prevention device. SWIMMING POOLS, SPAS, HOT TUBS, AND EQUIPMENT 22 TAC 535.233(d) (1) The inspector shall: (A) report the type of construction; (B) report as Deficient: (i) the presence of a single blockable main drain (potential entrapment hazard); (ii) a pump motor, blower, or other electrical equipment that lacks bonding; (iii) the absence of or deficiencies in safety barriers; (iv) water leaks in above-ground pipes and equipment; (v) the absence or failure in performance of ground-fault circuit interrupter protection devices; and (vi) deficiencies in: (I) surfaces; (II) tiles, coping, and decks; (III) slides, steps, diving boards, handrails, and other equipment; (IV) drains, skimmers, and valves; (V) filters, gauges, pumps, motors, controls, and sweeps; (VI) lighting fixtures; and (VII) the pool heater that these standards of practice require to be reported for the heating system. (2) The inspector is not required to: (A) disassemble filters or dismantle or otherwise open any components or lines; (B) operate valves; (C) uncover or excavate any lines or concealed components of the system; (D) fill the pool, spa, or hot tub with water; (E) inspect any system that has been winterized, shut down, or otherwise secured; (F) determine the presence of sub-surface water tables; (G) determine the effectiveness of entrapment covers; (H) determine the presence of pool shell or sub-surface leaks; or (I) inspect ancillary equipment such as computer controls, covers, chlorinators or other chemical dispensers, or water ionization devices or conditioners other than required by this section.  OUTBUILDINGS 22 TAC 535.233(e) (1) The inspector shall report as Deficient the absence or failure in performance of ground-fault circuit interrupter protection devices in gradelevel portions of unfinished accessory buildings used for storage or work areas, boathouses, and boat hoists; and (2) The inspector shall report as Deficient deficiencies in the structural, electrical, plumbing, heating, ventilation, and cooling systems that these standards of practice require to be reported for the principal building. PRIVATE WATER WELLS 22 TAC 535.233(f) (1) The inspector shall: (A) operate at least two fixtures simultaneously; (B) recommend or arrange to have performed coliform testing; (C) report: (i) the type of pump and storage equipment; (ii) the proximity of any known septic system; (D) report as Deficient deficiencies in: (i) water pressure and flow and performance of pressure switches; (ii) the condition of accessible equipment and components; and (iii) the well head, including improper site drainage and clearances. (2) The inspector is not required to: (A) open, uncover, or remove the pump, heads, screens, lines, or other components of the system; (B) determine the reliability of the water supply or source; or (C) locate or verify underground water leaks. PRIVATE SEWAGE DISPOSAL (SEPTIC) SYSTEMS. 22 TAC 535.233(g) (1) The inspector shall: (A) report: (i) the type of system; (ii) the location of the drain or distribution field; (iii) the proximity of any known water wells, underground cisterns, water supply lines, bodies of water, sharp slopes or breaks, easement lines, property lines, soil absorption systems, swimming pools, or sprinkler systems; (B) report as Deficient: (i) visual or olfactory evidence of effluent seepage or flow at the surface of the ground; (ii) inoperative aerators or dosing pumps; and (iii) deficiencies in: (I) accessible components; (II) functional flow; (III) site drainage and clearances around or adjacent to the system; and (IV) the aerobic discharge system. (2) The inspector is not required to: (A) excavate or uncover the system or its components; (B) determine the size, adequacy, or efficiency of the system; or (C) determine the type of construction used.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency