1234 Main St.
Harleysville, PA 19438
11/14/2019 9:00AM

Sample agent
agent

Agent Name

Agency Name
2
Maintenance item
9
Recommendation
4
Safety hazard

1 - Inspection Details

In Attendance
Client
Occupancy
Furnished
Type of Building
Single Family
Weather Conditions
Clear, Recent Rain

2 - Roofing

IN NI NP O
2.1 Coverings X
2.2 Roof Drainage Systems X
2.3 Vent Flashings X
2.4 Flashings X
2.5 Chimney X
2.6 Skylights X
Inspection Method
UAV
Typical Life Expectancy
Flat Tab Shingles - typically last 15-20yrs
Approximate Roof Age
10-15yrs.
Coverings: Material
Asphalt
Roof Drainage Systems: Gutter Material
Aluminum
Flashings: Material
Aluminum
General Roof Maintenance

We recommend having the roof evaluated every couple of years by qualified roofing professional. As a homeowner, we recommend to monitor flashing areas for built-up debris and look damaged or missing shingles while doing your bi-annual inspection of the house.

Roof Drainage Systems: Test Underground Drains

Test underground drains to ensure water is directed away from the foundation.

Vent Flashings : Vent flashing (vent collar)
Roof

Vent collars generally last 7-10 years. It is best to replace them proactively to prevent damage to the structure.


5.1 The inspector shall: A. inspect: 1. roofing materials. 2. roof drainage systems. 3. flashing. 4. skylights, chimneys, and roof penetrations. B. describe: 1. roofing materials. 2. methods used to inspect the roofing. 5.2 The inspector is NOT required to inspect: A. antennas. B. interiors of vent systems, uses, and chimneys that are not readily accessible. C. other installed accessories.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations

3 - Exterior

IN NI NP O
3.1 Siding, Flashing & Trim X X
3.2 Exterior Doors X X
3.3 Decks, Balconies, Porches & Steps X
3.4 Eaves, Soffits & Fascia X
3.5 Vegetation, Grading, Drainage & Retaining Walls X X
3.6 Walkways, Patios & Driveways X X
3.7 Window Wells X
Inspection Method
Visual
Siding, Flashing & Trim: Siding Material
Vinyl
Exterior Doors: Exterior Entry Door
Fiberglass
Decks, Balconies, Porches & Steps: Decks, Balconies, Porches & Steps
Patio
Decks, Balconies, Porches & Steps: Material
Concrete
Walkways, Patios & Driveways: Driveway Material
Asphalt - Consider having driveway sealed on a regular basis.
Walkways, Patios & Driveways: Stamped concrete requires maintenance sealing. Consult stamped concrete professional to understand suggested maintenance schedule.
Window Wells: Window Well - Cover Missing

Consider adding a window well cover to help keep water out.

Bi-annual Inspection

We recommend clients to inspect their homes a minimum of twice a year, ideally spring and fall. Looking for areas that water could infiltrate the structure or items that have changed from the previous inspection. By doing this process on a regular basis you are more likely to catch minor issues before they become major issues.

Home Owners Association (HOA)

This property is part of an HOA. We suggest you obtain a copy of the association's bylaws as soon as possible to understand what is covered and required as an association. Ensure you read and understand HOA docs prior to the end of your contingency period.

Exterior Doors: Exposed Doors (no roof or covering over door)

Exposed doors are susceptible to water infiltration. Monitor the caulking around the area on a regular basis to help keep the water out. Adding a storm door (if it doesn't have one) is also good practice to create another layer of protection, keeping the water away from the door and reducing energy loss. 

Exterior Doors: Consider Adding Storm Door

Consider adding a storm door to create another layer of protection. This will deter the water from the door and reduce energy loss. 

Walkways, Patios & Driveways: Remember you are responsible for keeping people safe on your property so inspect walkways and sidewalks regularly. In the winter months keep walkways and sidewalks clear and slip resistant in compliance with local laws and regulations.
Walkways, Patios & Driveways: Driveway Sealer

Consider having the driveway sealed on a regular basis, this will help from the product breaking down. Caulking the cracks where it meets the building and sidewalk will help prevent the driveway from settling. 

We do not inspect these components as part of our inspection.
Hot tubs or associated equipment. Consult qualified hot tub professional to evaluate/understand proper and safe operation., Swimming pools or associated equipment. Have pool professional evaluate pool and surrounding area for function and safety. Pools should be fenced in and access gates should be kept locked.

4.1 The inspector shall: A. inspect: 1. wall coverings, flashing, and trim. 2. exterior doors. 3. attached and adjacent decks, balconies, stoops, steps, porches, and their associated railings. 4. eaves, soffits, and fascias where accessible from the ground level. 5. vegetation, grading, surface drainage, and retaining walls that are likely to adversely affect the building. 6. adjacent and entryway walkways, patios, and driveways. B. describe wall coverings. 4.2 The inspector is NOT required to inspect: A. screening, shutters, awnings, and similar seasonal accessories. B. fences, boundary walls, and similar structures. C. geological and soil conditions. D. recreational facilities. E. outbuildings other than garages and carports. F. seawalls, break-walls, and docks. G. erosion control and earth stabilization measures.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
3.1.1 - Siding, Flashing & Trim

Caulking and Painting

It's important that all exterior components are properly maintained and sealed. Wood and metal products should be painted to prevent material decomposition. Caulking around dissimilar materials and exterior penetrations will help prevent water infiltration to the structure. Monitoring these areas during your bi-annual inspection of the property is very important to keeping a healthy and safe home.

Wrench DIY
Credit
Comment
3.5.1 - Vegetation, Grading, Drainage & Retaining Walls

Negative Grading

Grading is sloping towards the home in some areas. This could lead to water intrusion and foundation issues. Recommend qualified landscaper or foundation contractor regrade so water flows away from home.

Here is a helpful article discussing negative grading. 

Credit
Comment
3.6.1 - Walkways, Patios & Driveways

Walkway - Trip Hazard

There is a section of the walkway that is raised or loose causing a trip hazard. Consult a qualified contractor to repair or replace.

Brick Masonry, Concrete, Brick & Stone
Credit
Comment
3.6.2 - Walkways, Patios & Driveways

Unsealed Gap at Building.

The connection between the walkway/hard surface and the building should be sealed with a compatible sealant to keep water out.

Contractor Qualified Professional

4 - Air Conditioning

IN NI NP O
4.1 Cooling Equipment X X
4.2 Distribution System X
Cooling Equipment: Approximate Manufacture Date of Compressor
15 years
Cooling Equipment: Typical Life Expectancy
12 - 15 years
Cooling Equipment: Type
Central Air Conditioner
Cooling Equipment: Failure Probability
Medium (15-20 years)
Cooling Equipment: Supply Temperature
57º
Cooling Equipment: Return Temperature
74º
Cooling Equipment: Approximate Cooling Capacity
2.5 ton
Cooling Equipment: Approximate Cooling Capacity
3 ton

9.1 The inspector shall: A. open readily openable access panels. B. inspect: 1. central and permanently installed cooling equipment. 2. distribution systems. C. describe: 1. energy source(s). 2. cooling systems. 9.2 The inspector is NOT required to: A. inspect electric air cleaning and sanitizing devices. B. determine cooling supply adequacy and distribution balance. C. inspect cooling units that are not permanently installed or that are installed in windows. D. inspect cooling systems using ground source, water source, solar, and renewable energy technologies.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
4.1.1 - Cooling Equipment

Air Flow Restricted Around Unit

Air flow to the air conditioner condenser was restricted. This may result in inefficient operation. Recommend cleaning dirt/debris from the unit and cutting vegetation away so that you can freely walk around the unit.

Credit
Comment
4.1.2 - Cooling Equipment

Unit not level

The A/C condensing unit is not level. This can cause accelerated deterioration of components. Recommend qualified HVAC contractor level the unit. 

5 - Structural Components

IN NI NP O
5.1 Foundation, Basement & Crawlspaces X
5.2 Floor Structure X
5.3 Wall Structure X
5.4 Roof Structure & Attic X
5.5 Ceiling Structure X
Inspection Method
Visual
Foundation, Basement & Crawlspaces: Material
Concrete
Floor Structure: Basement/Crawlspace Floor
Concrete
Floor Structure: Material
Wood I-Joists, Wood Joists
Floor Structure: Sub-floor
OSB
Wall Structure: Material
Wood
Roof Structure & Attic: Material
Plywood
Ceiling Structure: Material
Wood
Roof Structure & Attic: Type
Truss

3. STRUCTURAL COMPONENTS 3.1 The inspector shall: A. inspect structural components including the foundation and framing. B. describe: 1. the methods used to inspect under floor crawlspaces and attics. 2. the foundation. 3. the floor structure. 4. the wall structure. 5. the ceiling structure. 6. the roof structure. 3.2 The inspector is NOT required to: A. provide engineering or architectural services or analysis. B. offer an opinion about the adequacy of structural systems and components. C. enter under floor crawlspace areas that have less than 24 inches of vertical clearance between components and the ground or that have an access opening smaller than 16 inches by 24 inches. D. traverse attic load-bearing components that are concealed by insulation or by other materials.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations

6 - Plumbing

IN NI NP O
6.1 Fixtures / Faucets X
6.2 Drain, Waste, & Vent Systems X X
6.3 Water Heater X
6.4 Vents, Flues, & Chimneys X
6.5 Sump Pumps / Sewage Ejectors X
6.6 Fuel Storage & Distribution Systems X
Material - Water Supply
Copper
Material - Distribution
CPVC
Source
Public
Main Fuel Shut-Off (Location)
Gas Meter
Drain, Waste, & Vent Systems: Material
PVC
Water Heater: Manufacturer
Bradford & White
Water Heater: Power Source
Gas
Water Heater: Tank Capacity
75 gal
Main Water Shut-Off Device (Location)
Basement
Water damage prevention

Consider placing a baking pan under your sink trap and store your cleaners in it. If the sink trap starts to leak hopefully you will notice it when pulling out your cleaners. Storing toilet paper around the trap area is also another good way to help identify a leak before it causes damage.



Consider Installing Water Alarms

Adding water alarms in areas where water damage is common is a cheap way to help prevent major damage.

Fixtures / Faucets: Frost free hose bib

Frost free hose bibs generally do not need to be shut off during freezing conditions. However, the hose must be disconnected to allow the faucet to drain properly or the system will not work. Adding a hose bib cover is good practice for added protection. 

Water Heater: Location
Basement
Sump Pumps / Sewage Ejectors: Water-Powered Back-up Sump Pump Installed

Consult homeowner for manual or contact the manufacturer of the water-powered back-up sump pump to understand the scheduled maintenance of the system.

We Do Not evaluate water conditioning systems

Consult qualified water testing/conditioning professional.

6.1 The inspector shall: A. inspect: 1. interior water supply and distribution systems including fixtures and faucets. 2. interior drain, waste, and vent systems including fixtures. 3. water heating equipment and hot water supply systems. 4. vent systems, flues, and chimneys. 5. fuel storage and fuel distribution systems. 6. sewage ejectors, sump pumps, and related piping. B. describe: 1. interior water supply, drain, waste, and vent piping materials. 2. water heating equipment including energy source(s). 3. location of main water and fuel shut-off valves. 6.2 The inspector is NOT required to: A. inspect: 1. clothes washing machine connections. 2. interiors of vent systems, flues, and chimneys that are not readily accessible. 3. wells, well pumps, and water storage related equipment. 4. water conditioning systems. 5. solar, geothermal, and other renewable energy water heating systems. 6. manual and automatic re-extinguishing and sprinkler systems and landscape irrigation systems. 7. septic and other sewage disposal systems. B. determine: 1. whether water supply and sewage disposal are public or private. 2. water quality. 3. the adequacy of combustion air components. C. measure water supply low and pressure, and well water quantity. D. fill shower pans and fixtures to test for leaks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
6.2.1 - Drain, Waste, & Vent Systems

Leak

There is a plumbing leak. Consult a qualified plumber to evaluate the cause of the leak and correct.

Contractor Qualified Professional

7 - Heating

IN NI NP O
7.1 Heating Equipment X
7.2 Energy Source X
7.3 Distribution Systems X
7.4 Vents, Flues & Chimneys X
Heating Equipment: Approximate Manufacture Date
15 years
Heating Equipment: Failure Probability
Basement
Furnace (High Efficiency) - Medium 15-20yrs
Heating Equipment: Failure Probability
Furnace (Con./Mid. Efficiency) - Low 1-17yrs, Furnace (High Efficiency) - Medium 15-20yrs
Heating Equipment: Heat Distribution
Ducts and Registers
Heating Equipment: System Type
Furnace
Energy Source : Energy Source
Natural Gas
Distribution Systems: Ductwork
Insulated, Non-insulated
Energy Source : Main Gas Shut Off
AFUE Rating

AFUE (Annual fuel utilization efficiency) is a metric used to measure furnace efficiency in converting fuel to energy. A higher AFUE rating means greater energy efficiency. 90% or higher meets the Department of Energy's Energy Star program standard.

General Service

HVAC systems should be serviced annually to ensure proper operation and maximize life expectancy.

Heating Equipment: Brand
Basement
Comfortmaker
Heating Equipment: Brand
Attic
Comfortmaker
Heating Equipment: Approximate Capacity
75000 BTU/hr, 50000 BTU/hr
Heating Equipment: Air Filters

Keep air filters clean and install with airflow arrow pointing towards the furnace. Consider having your filters sent to when it's time to change. (depending on the filter type 30, 60 or 90 days)

8.1 The inspector shall: A. open readily openable access panels. B. inspect: 1. installed heating equipment. 2. vent systems, uses, and chimneys. 3. distribution systems. C. describe: 1. energy source(s). 2. heating systems. 8.2 The inspector is NOT required to: A. inspect: 1. interiors of vent systems, uses, and chimneys that are not readily accessible. 2. heat exchangers. 3. humidifiers and dehumidifiers. 4. electric air cleaning and sanitizing devices. 5. heating systems using ground-source, water-source, solar, and renewable energy technologies. 6. heat-recovery and similar whole-house mechanical ventilation systems. B. determine: 1. heat supply adequacy and distribution balance. 2. the adequacy of combustion air components.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations

8 - Electrical

IN NI NP O
8.1 Service Entrance Conductors X X
8.2 Grounding system X X
8.3 Main and Distribution Panels X X
8.4 Wire Installation X X
8.5 Junction Boxes, Switches and Fixtures X
8.6 Receptacles X
8.7 GFCI & AFCI X
8.8 Smoke Detectors X
8.9 Carbon Monoxide Detectors X
Branch Wire 15 and 20 AMP
Copper
Wiring Method
Romex
Grounding system: Grounding Rod/Rods
Copper
Grounding system: Bonding to the Gas Pipe
Copper
Main and Distribution Panels: Panel Capacity
200 AMP
Main and Distribution Panels: Panel Type
Circuit Breaker
Service Entrance Conductors: Electrical Service Conductors
Below Ground
Grounding system: Bonding to Water Pipe
Copper
Main and Distribution Panels: Panel Manufacturer
Cutler Hammer
Main and Distribution Panels: Panel Locations
Basement
Main and Distribution Panels: Panel Cover Warning

Do Not remove the panel cover that is fastened with mechanical fasteners. This would expose electrical connections that are extremely dangerous. 

GFCI & AFCI: AFCI breakers

Arc Fault Circuit Interrupter (AFCI) is designed to monitor the flow of electricity leaving the beaker and if the flow is inconsistent the breaker is designed to shut off. If appliances are turned on when plugging them in this can cause the breaker to trip. If you can understand why a breaker tripped off from an action you did, reset the breaker and change your habit. If it continues or you can not explain why, call a licensed electrician. 

Smoke Detectors: We Do Not Test or Evaluate Smoke Detectors

We DO NOT test smoke detectors as a part of our service. However, you should replace all smoke detectors BEFORE you move in. If smoke detectors are not hard-wired we suggest using the type that is wirelessly tethered so if one goes off they all go off. Install smoke detectors according to directions provided by the manufacturer or contact your local fire department. Smoke detectors should be maintained according to manufactures directions. Smoke detectors typical expected life span is 10 years

Carbon Monoxide Detectors: We Do Not Test or Evaluate Carbon Monoxide Detectors

We DO NOT test carbon monoxide detectors. But we suggest they are in children's bedrooms and other manufacture suggested areas. Carbon monoxide detectors typical expected life span is 7 years. 

7.1 The inspector shall: A. inspect: 1. service drop. 2. service entrance conductors, cables, and raceways. 3. service equipment and main disconnects. 4. service grounding. 5. interior components of service panels and subpanels. 6. conductors. 7. overcurrent protection devices. 8. a representative number of installed lighting fixtures, switches, and receptacles. 9. ground fault circuit interrupters and arc fault circuit interrupters. B. describe: 1. amperage rating of the service. 2. location of main disconnect(s) and subpanels. 3. presence or absence of smoke alarms and carbon monoxide alarms. 4. the predominant branch circuit wiring method. 7.2 The inspector is NOT required to: A. inspect: 1. remote control devices. 2. or test smoke and carbon monoxide alarms, security systems, and other signaling and warning devices. 3. low voltage wiring systems and components. 4. ancillary wiring systems and components not a part of the primary electrical power distribution system. 5. solar, geothermal, wind, and other renewable energy systems. B. measure amperage, voltage, and impedance. C. determine the age and type of smoke alarms and carbon monoxide alarms.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
8.2.1 - Grounding system

CSST Gas Pipe Bonding Not Verified

Corrugated Stainless Steel Tubing (CSST) must be bonded to the grounding system prior to the use of the product in the house. We were unable to verify that it was bonded to the grounding system. Recommend a qualified plumber evaluate and correct.

Contractor Qualified Professional
Credit
Comment
8.3.1 - Main and Distribution Panels

Double Tap Breaker/Breakers
basement

There are breakers with more than one wire connected to them which is called "double tapping". Most electrical breakers are designed for only one wire connection. Consult a qualified electrician to evaluate the electric panel, correct the problems and ensure the panel is safe.

Contractor Qualified Professional

9 - Interiors

IN NI NP O
9.1 Ceilings X
9.2 Floors X
9.3 Walls X X
9.4 Garage Vehicle Door X
9.5 Garage Ceiling/Walls/Door to House X
9.6 Steps, Stairways & Railings X
9.7 Countertops & Cabinets X
9.8 Doors X X
9.9 Windows X X
Ceilings: Ceiling Material
Gypsum Board
Floors: Floor Coverings
Carpet, Hardwood, Tile, Vinyl
Walls: Wall Material
Gypsum Board
Garage Vehicle Door: Material
Metal
Garage Vehicle Door: Type
Automatic
Countertops & Cabinets: Cabinetry
Laminate, Wood
Countertops & Cabinets: Countertop Material
Granite
Windows: Window Manufacturer
Unknown
Windows: Window Type
Single-hung

10.1 The inspector shall inspect: A. walls, ceilings, and floors. B. steps, stairways, and railings. C. countertops and a representative number of installed cabinets. D. a representative number of doors and windows. E. garage vehicle doors and garage vehicle door operators. F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: A. paint, wallpaper, and other finish treatments. B. floor coverings. C. window treatments. D. coatings on and the hermetic seals between panes of window glass. E. central vacuum systems. F. recreational facilities. G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or confirm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
9.3.1 - Walls

Mold-like Substance
Basement

There are signs of a mold-like substance on the wall/s. It is unknown if this is a safety hazard without testing it first to understand what it is. Recommend a qualified mold inspector evaluate and understand proper clean-up procedures. 

Credit
Comment
9.8.1 - Doors

Door Doesn't Latch

Door doesn't latch properly. Recommend handyman repair latch and/or strike plate.

Credit
Comment
9.9.1 - Windows

Failed Thermal Seal
Foyer

Observed condensation between the window panes, which indicates a failed thermal seal. Recommend qualified window contractor to evaluate and repair or replace.

10 - Insulation and Ventilation

IN NI NP O
10.1 Attic Access X X
10.2 Attic Insulation X
10.3 Vapor Retarders X
10.4 Ventilation X
10.5 Exhaust Systems X X
Dryer Power Source
220 Electric
Dryer Vent
Metal, Metal (Flex)
Floor Insulation
None
Attic Insulation: R-value
unknown
Ventilation: Ventilation Type
Soffit & Ridge Vents
Exhaust Systems: Exhaust Fans
Fan with Light
Washing Machine Hoses

When installing your washer consider using the "burst resistant" type of hoses to help reduce the risk of water damage.

Attic Insulation: Insulation Type
Fiberglass
Exhaust Systems: Dryer Vent Cleaning

We can not see the inside of the dryer vent. We suggest you have it cleaned as soon as you move in. The dryer vent is often a cause of fire so regular cleaning is very important. If it is a long vent or it is not accessible, duct/vent cleaning companies typically clean dryers vents too.

11.1 The inspector shall: A. inspect: 1. insulation and vapor retarders in unfinished spaces. 2. ventilation of attics and foundation areas. 3. kitchen, bathroom, laundry, and similar exhaust systems. 4. clothes dryer exhaust systems. B. describe: 1. insulation and vapor retarders in unfinished spaces. 2. absence of insulation in unfinished spaces at conditioned surfaces. 11.2 The inspector is NOT required to disturb insulation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
10.1.1 - Attic Access

Attic Hatch Missing Insulation or Weather Stripping

To help improve energy efficiency consider adding insulation to the back of the hatch and weather stripping around the opening to help seal the hatch when closed.

Contractor Qualified Professional
Credit
Comment
10.5.1 - Exhaust Systems

Bathroom Vents Into Attic

Bathroom fan vents into the attic, which can cause moisture and mold. Recommend a qualified attic contractor property install exhaust fan to terminate to the exterior.

11 - Built-in Appliances

IN NI NP O
11.1 Dishwasher X
11.2 Range/Oven/Cooktop X
11.3 Garbage Disposal X
Dishwasher: Brand
GE
Range/Oven/Cooktop: Exhaust Hood Type
Vented
Range/Oven/Cooktop: Range/Oven Brand
Kitchenaid
Range/Oven/Cooktop: Range/Oven Energy Source
Electric
Dishwasher: Life Span

Dishwashers typically last 8-12yrs depending on the amount of use and care for the product. 

Not Tested As Part of Our Inspection

We do Not evaluate refrigerators, microwaves, washers, dryers, trash compactors and or any other appliance that is not part of the ASHI standards of practice as part of our service.

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations

12 - Fireplaces and Fuel-Burning Appliances

IN NI NP O
12.1 Fireplaces, Stoves & Inserts
12.2 Gas Fireplace X X
12.3 Chimney & Vent Systems X
Type
Gas, Blower
Gas Fireplace: Service Gas Fireplace

Service gas fireplace per manufactures recommendations.

12.1 The inspector shall: A. inspect: 1. fuel-burning replaces, stoves, and replace inserts. 2. fuel-burning accessories installed in replaces. 3. chimneys and vent systems. B. describe systems and components listed in 12.1.A.1 and .2. 12.2 The inspector is NOT required to: A. inspect: 1. interiors of vent systems, uses, and chimneys that are not readily accessible. 2. fire screens and doors. 3. seals and gaskets. 4. automatic fuel feed devices. 5. mantles and replace surrounds. 6. combustion air components and to determine their adequacy. 7. heat distribution assists (gravity fed and fan assisted). 8. fuel-burning replaces and appliances located outside the inspected structures. B. determine draft characteristics. C. move fireplace inserts and stoves or firebox contents.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
Credit
Comment
12.2.1 - Gas Fireplace

Inoperable

The gas fireplace was inoperable at inspection. Consult a qualified gas fireplace professional to evaluate and ensure safe operation.

Contractor Qualified Professional