Viewing:

1234 Main St.
Oak park, Il 60531
12/15/2019 9:00AM

Sample agent
agent

Agent Name

Agency Name
50
Recommendation

1 - Inspection Details

In Attendance
Subject Property
Client
Occupancy
Subject Property
Vacant
Style
Subject Property
Manufactured
Temperature (approximate)
Exterior
75 Fahrenheit (F)
Type of Building
Subject Property
Restaurant
Weather Conditions
Exterior
Clear

2 - Roofing/Vents/Attic

IN NI NP D
2.1 Roof Coverings X X
2.2 Skylights, Chimneys & Roof Penetrations X X
2.3 Flashings X
2.4 Roof Drainage Systems X X
2.5 Roof Structure & Attic X
2.6 Attic Insulation X
2.7 Exhaust Systems X
2.8 Ventilation X X
Inspection Method
Roof
Walked roof, Drone
Roof Type/Style
Roof
Flat
Roof Coverings: Material
Roof
Membrane
Flashings: Material
Membrane, Tar
Roof Drainage Systems: Gutter Material
Aluminum
Roof Structure & Attic: Material
Inaccessible
Roof Structure & Attic: Type
Flat
Attic Insulation: Insulation Type
Unknown
Exhaust Systems: Exhaust Fans
Fan with Light
Ventilation: Ventilation Type
Roof/Attic
Turbines

5.1 The inspector shall: A. inspect: 1. roofing materials. 2. roof drainage systems. 3. flashing. 4. skylights, chimneys, and roof penetrations. B. describe: 1. roofing materials. 2. methods used to inspect the roofing. 5.2 The inspector is NOT required to inspect: A. antennas. B. interiors of vent systems, uses, and chimneys that are not readily accessible. C. other installed accessories. 


  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
2.1.1 - Roof Coverings

Discoloration
Roof

Roof discolored, which can be caused by moisture, rust or soot. Recommend a qualified roofing contractor evaluate and remedy with a roof cleaning or repair. 

Here is a helpful article on common roof stains. 

Roof Roofing Professional
$
Credit
Comment
2.1.2 - Roof Coverings

Ponding
Roof

Observed ponding in one or more areas of roof. Ponding can lead to accelerated erosion and deterioration. Recommend a qualified roofing contractor evaluate and repair. 

$
Credit
Comment
2.1.3 - Roof Coverings

Debris on roof

Metal and wood debris will lead to deterioration of roof all unused items on roof should be removed to prevent damage to membrane 

Contractor Qualified Professional
$
Credit
Comment
2.2.1 - Skylights, Chimneys & Roof Penetrations

Chimney Cap Missing or rusted

None or deteriorated chimney cap was observed. This is important to protect from moisture intrusion and protect the chimney. Recommend a qualified roofer or chimney expert install.

$
Credit
Comment
2.4.1 - Roof Drainage Systems

Debris

Debris has accumulated in the gutters. Recommend cleaning to facilitate water flow.

Here is a DIY resource for cleaning your gutters. 

Contractor Qualified Professional
$
Credit
Comment
2.4.2 - Roof Drainage Systems

Downspout extension Damaged

Downspout extension were damaged. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor evaluate and repair. 

$
Credit
Comment
2.4.3 - Roof Drainage Systems

Pooling water near foundation/downspout extensions needed
Exterior

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 6 feet from the foundation. 

Here is a helpful DIY link and video on draining water flow away from your house.  Recommend installing gutter extensions, extending 5' away from foundation. 

Tools Handyman/DIY
$
Credit
Comment
2.4.4 - Roof Drainage Systems

Downspout needs to be fastened to properly

Downspouts need to be fastened to property to ensure proper support during harsh weather 

Contractor Qualified Professional
$
Credit
Comment
2.8.1 - Ventilation

Whole House Fan Inoperable
Attic

Whole house fan was inoperable at time of inspection. Recommend a qualified whole house fan contractor evaluate and repair.

Electric Electrical Contractor

3 - Exterior

IN NI NP D
3.1 Exterior, Flashing & Trim X X
3.2 Eaves, Soffits & Fascia X
3.3 Vegetation, Grading, Drainage & Retaining Walls X X
3.4 Walkways, Patios & Driveways X X
Inspection Method
Subject Property
Visual, Infrared
Exterior, Flashing & Trim: Exterior Material
Exterior
Brick
Walkways, Patios & Driveways: Driveway Material
Exterior
Asphalt

4.1 The inspector shall: A. inspect: 1. wall coverings, flashing, and trim. 2. exterior doors. 3. attached and adjacent decks, balconies, stoops, steps, porches, and their associated railings. 4. eaves, soffits, and fascias where accessible from the ground level. 5. vegetation, grading, surface drainage, and retaining walls that are likely to adversely affect the building. 6. adjacent and entryway walkways, patios, and driveways. B. describe wall coverings. 4.2 The inspector is NOT required to inspect: A. screening, shutters, awnings, and similar seasonal accessories. B. fences, boundary walls, and similar structures. C. geological and soil conditions. D. recreational facilities. E. outbuildings other than garages and carports. F. seawalls, break-walls, and docks. G. erosion control and earth stabilization measures.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
3.1.1 - Exterior, Flashing & Trim

Cracking Concrete Foundation (Exterior) - Minor
Exterior

Major cracking was observed at one or more points on the exterior of foundation. This can be the result of poor original compaction of soil at the time of construction or excess moisture in the underlying soil. Recommend consulting with a structural engineer and/or soil expert.

House construction Structural Engineer
$
Credit
Comment
3.1.2 - Exterior, Flashing & Trim

Loose mortar or bricks (Tuckpointing)
Exterior

Tuck-pointing needed to prevent water intrusion. Contact professional mason to further evaluate and correct.

Contractor Qualified Professional
$
Credit
Comment
3.3.1 - Vegetation, Grading, Drainage & Retaining Walls

Planting near foundation
Exterior

Inspector recommends avoid planting shrubs, trees and plants 12 inches or closer to foundation to prevent possible damage to foundation. 

Wrench DIY
$
Credit
Comment
3.4.1 - Walkways, Patios & Driveways

Walkway Cracking - Major
Exterior

Major cracks observed. Recommend driveway contractor evaluate and replace.
Brick Masonry Contractor
$
Credit
Comment
3.4.2 - Walkways, Patios & Driveways

Driveway Trip Hazard
Exterior

Trip hazards observed. Patch or repair recommended.
Brick Masonry Contractor

4 - Plumbing

IN NI NP D
4.1 Water Heater X X
4.2 Pressure Test X
4.3 Fixtures / Faucets X X
4.4 Drain, Waste, & Vent Systems X X
4.5 Gas Lines X
Filters
None
Main Water Shut-Off Device (Location)
Main Level
Material - Distribution
Galvanized
Material - Water Supply
Galvanized
Source
Public
Public
Water Heater: Location
Main Floor
Water Heater: Power Source
Mechanical Room
Gas
Drain, Waste, & Vent Systems: Drain Size
2"
Drain, Waste, & Vent Systems: Material
Lead
Main Fuel Shut-Off (Location)
Main Level
Water Heater: Capacity
Mechanical Room
10 Gallons

 

Water Heater: Manufacturer
Mechanical Room
Unknown

Water heaters should be flushed annually to prevent sediment buildup and maintain efficiency.  

Here is a DIY link to help

Water Heater: Limited Access/No Info Label
Mechanical Room

6.1 The inspector shall: A. inspect: 1. interior water supply and distribution systems including fixtures and faucets. 2. interior drain, waste, and vent systems including fixtures. 3. water heating equipment and hot water supply systems. 4. vent systems, flues, and chimneys. 5. fuel storage and fuel distribution systems. 6. sewage ejectors, sump pumps, and related piping. B. describe: 1. interior water supply, drain, waste, and vent piping materials. 2. water heating equipment including energy source(s). 3. location of main water and fuel shut-off valves. 6.2 The inspector is NOT required to: A. inspect: 1. clothes washing machine connections. 2. interiors of vent systems, flues, and chimneys that are not readily accessible. 3. wells, well pumps, and water storage related equipment. 4. water conditioning systems. 5. solar, geothermal, and other renewable energy water heating systems. 6. manual and automatic re-extinguishing and sprinkler systems and landscape irrigation systems. 7. septic and other sewage disposal systems. B. determine: 1. whether water supply and sewage disposal are public or private. 2. water quality. 3. the adequacy of combustion air components. C. measure water supply low and pressure, and well water quantity. D. fill shower pans and fixtures to test for leaks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
4.1.1 - Water Heater

Temperature reading
Kitchens

Hot water temperature target is 120 degrees to prevent bacteria growth and scalding. A simple adjustment at the hot water tank thermostat. 

Tools Handyman/DIY
$
Credit
Comment
4.1.2 - Water Heater

Improper Installation
Mechanical Room

Tpr pipe should be 6' from ground. None installed. 

Contractor Qualified Professional
$
Credit
Comment
4.1.3 - Water Heater

No floor drain present

Pipes Plumbing Contractor
$
Credit
Comment
4.2.1 - Pressure Test

Good Pressure
Throughout

Plumbing pressure tested and as a result the pressure was good throughout. 

$
Credit
Comment
4.3.1 - Fixtures / Faucets

Plumbing penetrations
Kitchen/Bath/Laundry

All plumbing penetrations should be sealed to prevent water intrusion and mold growth should a leak occur. 

Tools Handyman/DIY
$
Credit
Comment
4.3.2 - Fixtures / Faucets

Corrosion
Kitchen/Bath/Laundry

Corrosion present at plumbing pipes. Buyer to monitor. Corrosion can lead to leaks. 

Pipes Plumbing Contractor
$
Credit
Comment
4.3.3 - Fixtures / Faucets

Loose toilets
Bathroom(s)

Loose toilets are safety and sanitary hazards that can cause leaks if not corrected.

Pipes Plumbing Contractor
$
Credit
Comment
4.3.4 - Fixtures / Faucets

Leak(s) present
Kitchen/Bath/Laundry

Existing leak under bathroom tub at time of inspection. 

Contractor Qualified Professional
$
Credit
Comment
4.3.5 - Fixtures / Faucets

Loose fixtures
Kitchen/Bath/Laundry

Loose fixtures present throughout. Should be corrected or replace before more damage of fixtures or leaks occur. 

Pipes Plumbing Contractor
$
Credit
Comment
4.4.1 - Drain, Waste, & Vent Systems

Poor/Slow/Clogged Drainage
Kitchen/Bath/Laundry

Poor/slow drainage was observed at time of inspection. Recommend a qualified plumber evaluate and repair. 

Pipes Plumbing Contractor
$
Credit
Comment
4.4.2 - Drain, Waste, & Vent Systems

Uncapped plumbing

Uncapped plumbing is unsanitary and can cause vermin intrusion, should be removed or capped. 

Pipes Plumbing Contractor

5 - Structural Components

IN NI NP D
5.1 Foundation, Basement & Crawlspaces X X
Inspection Method
Crawl Space
Visual, Infrared
Foundation, Basement & Crawlspaces: Material
Concrete, Slab on Grade
Crawl Space Access Bolted shut
Crawl Space
Foundation, Basement & Crawlspaces: Unable To Fully Inspect due to Waterproofing covering or clutter
Basement or Crawlspace

Thermal imaging camera was used and no indication of water intrusion present at time of inspection. 

3. STRUCTURAL COMPONENTS 3.1 The inspector shall: A. inspect structural components including the foundation and framing. B. describe: 1. the methods used to inspect under floor crawlspaces and attics. 2. the foundation. 3. the floor structure. 4. the wall structure. 5. the ceiling structure. 6. the roof structure. 3.2 The inspector is NOT required to: A. provide engineering or architectural services or analysis. B. offer an opinion about the adequacy of structural systems and components. C. enter under floor crawlspace areas that have less than 24 inches of vertical clearance between components and the ground or that have an access opening smaller than 16 inches by 24 inches. D. traverse attic load-bearing components that are concealed by insulation or by other materials.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency

6 - Electrical

IN NI NP D
6.1 Service Entrance Conductors X
6.2 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels X X
6.3 Branch Circuit Conductors, Overcurrent Devices and Compatibility of Their Amperage & Voltage X
6.4 Connected Devices and Fixtures X
6.5 Smoke & Carbon Monoxide Detectors X
6.6 Outlets, Junction Boxes, Switches & Exposed Wires X X
Branch Wire 15 and 20 AMP
Copper
Wiring Method
Conduit
Service Entrance Conductors: Electrical Service Conductors
Exterior
400 volts, Overhead
Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels: Panel Capacity
Mechanical Room
440 AMP
Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels: Panel Locations
Main Level
Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels: Panel Manufacturer
Mechanical Room
Unknown
Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels: Panel Type
Mechanical Room
Circuit Breaker
Smoke & Carbon Monoxide Detectors: Change batteries every year
Throughout

Take care of your smoke alarms according to the manufacturer's instructions. Replace the batteries at least once every year. Replace the entire smoke alarm every 10 years.

Smoke & Carbon Monoxide Detectors: Change detectors every 10 years
Throughout

Smoke & carbon alarms need to be replaced 10 years from their date of manufacture, according to FEMA.

7.1 The inspector shall: A. inspect: 1. service drop. 2. service entrance conductors, cables, and raceways. 3. service equipment and main disconnects. 4. service grounding. 5. interior components of service panels and subpanels. 6. conductors. 7. overcurrent protection devices. 8. a representative number of installed lighting fixtures, switches, and receptacles. 9. ground fault circuit interrupters and arc fault circuit interrupters. B. describe: 1. amperage rating of the service. 2. location of main disconnect(s) and subpanels. 3. presence or absence of smoke alarms and carbon monoxide alarms. 4. the predominant branch circuit wiring method. 7.2 The inspector is NOT required to: A. inspect: 1. remote control devices. 2. or test smoke and carbon monoxide alarms, security systems, and other signaling and warning devices. 3. low voltage wiring systems and components. 4. ancillary wiring systems and components not a part of the primary electrical power distribution system. 5. solar, geothermal, wind, and other renewable energy systems. B. measure amperage, voltage, and impedance. C. determine the age and type of smoke alarms and carbon monoxide alarms.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
6.2.1 - Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels

Not Labeled
Mechanical Room

Electrical panel does not have labels. Recommend a qualified electrician test and properly label all switches. 

Electric Electrical Contractor
$
Credit
Comment
6.2.2 - Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels

Panel Damaged
Mechanical Room

Electrical panel is damaged. Knock outs and door missing. Recommend a qualified electrician evaluate and repair. 

Electric Electrical Contractor
$
Credit
Comment
6.2.3 - Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels

Electrical panel needs clearance
Mechanical Room

Electrical panel needs 3 feet of clearance at all times for services 

Electric Electrical Contractor
$
Credit
Comment
6.4.1 - Connected Devices and Fixtures

Light Inoperable
Throughout

One or more lights are not operating. New light bulb possibly needed.
Electric Electrical Contractor
$
Credit
Comment
6.4.2 - Connected Devices and Fixtures

Exhaust Fans in Bathroom
Bathroom(s)

Dirty and loose, should be cleaned periodically to maintain effectiveness. 

Tools Handyman/DIY
$
Credit
Comment
6.6.1 - Outlets, Junction Boxes, Switches & Exposed Wires

Cover Plates Damaged
Throughout

One or more receptacles have a damaged cover plate. Recommend replacement.
Tools Handyman/DIY
$
Credit
Comment
6.6.2 - Outlets, Junction Boxes, Switches & Exposed Wires

Cover Plates Missing
Throughout

One or more receptacles are missing a cover plate. This causes short and shock risk. Recommend installation of plates.
Tools Handyman/DIY
$
Credit
Comment
6.6.3 - Outlets, Junction Boxes, Switches & Exposed Wires

Reverse Polarity, Grounding & GFCI

Electrical receptacles (or outlets) have both a hot and a neutral pole. Reverse polarity happens when the neutral wire gets connected to the incorrect side of the outlet. Reverse polarity creates a potential shock hazard. This effect is amplified in the presence of moisture and/or water. Because of this, outlets that are located near plumbing fixtures or moisture, such as those in bathrooms, kitchens, the outside of the building and garages, are required to be GFCI (Ground Fault Circuit Interrupter) outlets or breakers.

GFCI outlets initiate an instant break in the electrical current whenever they register a surge in voltage. This prevents sparks that could lead to fires or the risk electrocution.


 Polarity and Grounding of Receptacles

Electric Electrical Contractor
$
Credit
Comment
6.6.4 - Outlets, Junction Boxes, Switches & Exposed Wires

Loose outlets
Throughout

Whether due to cracks in the outlet face or simply wear and tear, outlets that don't securely hold the prongs on electrical cord plugs are another common problem. What this means is that the electrical contacts within the outlet have lost their tension and are failing to grip the plug prongs as they are supposed to. If the plug slips out partway, it can be quite dangerous, since the energized metal prongs are exposed.

Electric Electrical Contractor
$
Credit
Comment
6.6.5 - Outlets, Junction Boxes, Switches & Exposed Wires

Junction box needs to be fastened

To ensure no damage can be done to conduit fasten junction boxes to wall

Contractor Qualified Professional

7 - Heating

IN NI NP D
7.1 Heating Equipment X X
7.2 Distribution Systems X
Heating Equipment: Brand
Mechanical Room
Rheem, Cutler hammer
Heating Equipment: Energy Source
Mechanical Room
Gas
Heating Equipment: Filter Type
Mechanical Room
None
Heating Equipment: Heat Type
Mechanical Room
Forced Air
Distribution Systems: Ductwork
Non-insulated

8.1 The inspector shall: A. open readily openable access panels. B. inspect: 1. installed heating equipment. 2. vent systems, uses, and chimneys. 3. distribution systems. C. describe: 1. energy source(s). 2. heating systems. 8.2 The inspector is NOT required to: A. inspect: 1. interiors of vent systems, uses, and chimneys that are not readily accessible. 2. heat exchangers. 3. humidifiers and dehumidifiers. 4. electric air cleaning and sanitizing devices. 5. heating systems using ground-source, water-source, solar, and renewable energy technologies. 6. heat-recovery and similar whole-house mechanical ventilation systems. B. determine: 1. heat supply adequacy and distribution balance. 2. the adequacy of combustion air components.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
7.1.1 - Heating Equipment

Corrosion
Mechanical Room

Furnace was corroded in one or more areas. This could be the result of improper venting, which the source would need to be identified. Recommend a HVAC contractor evaluate and repair.

Th Heating and Cooling Contractor
$
Credit
Comment
7.1.2 - Heating Equipment

Needs Servicing/Cleaning
Mechanical Room

Furnace should  be cleaned and serviced annually. Recommend a qualified HVAC contractor clean, service and certify boiler.

Th Heating and Cooling Contractor

8 - Air Conditioning

IN NI NP D
8.1 Cooling Equipment X X
8.2 Distribution System X
Type
Subject Property
Air Conditioner
Cooling Equipment: Brand
Cutler hammer, Rheem
Cooling Equipment: Energy Source/Type
Electric
Cooling Equipment: Location
Roof
Distribution System: Configuration
Central

9.1 The inspector shall: A. open readily openable access panels. B. inspect: 1. central and permanently installed cooling equipment. 2. distribution systems. C. describe: 1. energy source(s). 2. cooling systems. 9.2 The inspector is NOT required to: A. inspect electric air cleaning and sanitizing devices. B. determine cooling supply adequacy and distribution balance. C. inspect cooling units that are not permanently installed or that are installed in windows. D. inspect cooling systems using ground source, water source, solar, and renewable energy technologies.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
8.1.1 - Cooling Equipment

Unusually noisy

Compressor started and operated but unit was unusually noisy. Recommend licensed HVAC contractor evaluate.

9 - Interiors

IN NI NP D
9.1 Walls
9.2 Ceilings X X
9.3 Floors X X
9.4 Steps, Stairways & Railings X X
9.5 Countertops & Cabinets X
9.6 Doors X X
9.7 Windows X
9.8 Exterior Doors X X
Walls: Wall Material
Plaster
Ceilings: Ceiling Material
Suspended Ceiling Panels
Floors: Floor Coverings
Tile
Countertops & Cabinets: Cabinetry
None
Countertops & Cabinets: Countertop Material
Granite
Doors: Type
Solid
Windows: Window Manufacturer
Unknown
Windows: Window Type
Single Pane
Exterior Doors: Type
Metal, Steel

10.1 The inspector shall inspect: A. walls, ceilings, and floors. B. steps, stairways, and railings. C. countertops and a representative number of installed cabinets. D. a representative number of doors and windows. E. garage vehicle doors and garage vehicle door operators. F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: A. paint, wallpaper, and other finish treatments. B. floor coverings. C. window treatments. D. coatings on and the hermetic seals between panes of window glass. E. central vacuum systems. F. recreational facilities. G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or confirm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
9.1.1 - Walls

Poor Patching

Sub-standard drywall patching observed at time of inspection. Recommend re-patching. 

$
Credit
Comment
9.2.1 - Ceilings

Existing leak in ceiling
Kitchen

Existing leak noted in ceiling is caused by roof leak.  

Contractor Qualified Professional
$
Credit
Comment
9.2.2 - Ceilings

Missing panels

Contractor Qualified Professional
$
Credit
Comment
9.3.1 - Floors

Moderate Wear

Floors in the home exhibited moderate surface wear along major paths of travel. Recommend a qualified flooring contractor evaluate for possible re-finish. 

$
Credit
Comment
9.3.2 - Floors

Tiles Missing or broken

One or more floor tiles were missing. Recommend installing/replacing missing tiles. 

Contractor Qualified Professional
$
Credit
Comment
9.3.3 - Floors

Floors not leveled
Dining area

Cracked tiles and floors not leveled. Trip hazard if not corrected. 

Contractor Qualified Professional
$
Credit
Comment
9.3.4 - Floors

Drain tiles creating trip hazard

Contractor Qualified Professional
$
Credit
Comment
9.4.1 - Steps, Stairways & Railings

Loose Balusters

Handrail balusters were loose. This could pose a safety hazard. Recommend a qualified handyman evaluate and fasten. 

Hammer Carpentry Contractor
$
Credit
Comment
9.6.1 - Doors

Missing or loose knobs

Contractor Qualified Professional
$
Credit
Comment
9.6.2 - Doors

Loose or high threshold

Loose or high threshold are trip hazards 

Contractor Qualified Professional
$
Credit
Comment
9.8.1 - Exterior Doors

Weather stripping missing
back door

Weather strip needed to keep cool or warm air in and also vermin out.  

Contractor Qualified Professional

10 - Built-in Appliances

IN NI NP D
10.1 Refrigerator X
10.2 Range/Oven/Cooktop X
Range/Oven/Cooktop: Exhaust Hood Type
Kitchen
Vented
Range/Oven/Cooktop: Kitchen exhaust brand
Kitchen
Unknown

Incorrect sealant. Incorrect material.

Range/Oven/Cooktop: Range/Oven Energy Source
Kitchen
Gas, Imperial
Refrigerator: Brand
Kitchen
True, Atosa

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
10.1.1 - Refrigerator

Leaks noted

Contractor Qualified Professional