1234 Main St.
Salt Lake City UTAH 84116
05/26/2018 9:00AM

Sample agent
agent

Agent Name

Agency Name
65
Items Inspected
32
Recommendations
3
Safety hazard

1 - Inspection Details

In Attendance
Home inspector, Client
Occupancy
Vacant
Style
Ranch
Temperature (approximate)
51 Fahrenheit (F)
Type of Building
Single Family
Weather Conditions
Cloudy, Heavy Rain

2 - Roof

IN NI NP R
2.1 Coverings
2.2 Roof Drainage Systems
2.3 Flashings
2.4 Skylights, Chimneys & Other Roof Penetrations
Inspection Method
Roof
Roof Type/Style
Combination
Coverings: Material
Asphalt
Roof Drainage Systems: Gutter Material
Aluminum
Flashings: Material
Rubber

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspector’s opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
2.2.1 - Roof Drainage Systems

Debris

Debris has accumulated in the gutters. Recommend cleaning to facilitate water flow.

Here is a DIY resource for cleaning your gutters. 

Roof Roofing Professional
2.2.2 - Roof Drainage Systems

Downspouts Drain Near House

One or more downspout drains are too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least six feet from the foundation.

Here is a helpful DIY link and video on draining water flow away from your house.

Roof Roofing Professional
2.3.1 - Flashings

Missing

Flashings were missing at time of inspection. Flashings provide protection against moisture intrusion. Recommend a qualified roofing contractor evaluate and remedy kick out flashings around the chimney.

Roof Roofing Professional
2.4.1 - Skylights, Chimneys & Other Roof Penetrations

Chimney Cap Missing

No chimney cap was observed. This is important to protect from moisture intrusion and protect the chimney. Recommend a qualified roofer or chimney expert install.

Roof Roofing Professional

3 - Exterior

IN NI NP R
3.1 Siding, Flashing & Trim
3.2 Exterior Doors
3.3 Walkways, Patios & Driveways
3.4 Decks, Balconies, Porches & Steps
3.5 Eaves, Soffits & Fascia
3.6 Vegetation, Grading, Drainage & Retaining Walls
Inspection Method
Visual
Siding, Flashing & Trim: Siding Style
No siding
Siding, Flashing & Trim: Siding Material
Brick, Masonry
Exterior Doors: Exterior Entry Door
Hollow Core, Glass
Exterior Doors: Garage door
Walkways, Patios & Driveways: Driveway Material
Concrete
Decks, Balconies, Porches & Steps: Appurtenance
Covered Porch
Decks, Balconies, Porches & Steps: Material
Concrete
Eaves, Soffits & Fascia: Soffits and facia

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
3.2.1 - Exterior Doors

Unable to open and operate deadbolt

Contractor Qualified Professional
3.2.2 - Exterior Doors

Door knob is loose

Door knob is loose.

Contractor Qualified Professional
3.3.1 - Walkways, Patios & Driveways

Driveway Cracking - Minor

Minor cosmetic cracks observed, which may indicate movement in the soil. Recommend monitor and/or have concrete contractor patch/seal.

Gardening shovel tool shape Concrete Contractor

4 - Basement, Foundation, Crawlspace & Structure

IN NI NP R
4.1 Foundation
4.2 Basements & Crawlspaces
4.3 Floor Structure
4.4 Wall Structure
4.5 Ceiling Structure
Inspection Method
Visual
Foundation: Material
Concrete
Wall Structure: Drywall
Ceiling Structure: Gypsum Board
Floor Structure: Material
Wood Beams
Floor Structure: Sub-floor
Plywood
Floor Structure: Basement/Crawlspace Floor
Concrete

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations

5 - Heating

IN NI NP R
5.1 Equipment
5.2 Normal Operating Controls
5.3 Distribution Systems
5.4 Vents, Flues & Chimneys
5.5 Presence of Installed Heat Source in Each Room
Equipment: Brand
Trane
Equipment: Energy Source
Gas
Equipment: Heat Type
Heat Pump
Distribution Systems: Ductwork
Non-insulated
AFUE Rating
92

AFUE (Annual fuel utilization efficiency) is a metric used to measure furnace efficiency in converting fuel to energy. A higher AFUE rating means greater energy efficiency. 90% or higher meets the Department of Energy's Energy Star program standard.

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
5.1.1 - Equipment

Damaged flue pipe

Contractor Qualified Professional
5.1.2 - Equipment

Filter Dirty

The furnace filter is dirty and needs to be replaced every six months. 

Here is a DIY video on changing your furnace filter: 

 

Fire HVAC Professional
5.1.3 - Equipment

Needs Servicing/Cleaning

Furnace should be cleaned and serviced annually. Recommend a qualified HVAC contractor clean, service and certify furnace.

Here is a resource on the importance of furnace maintenance.

Fire HVAC Professional
5.4.1 - Vents, Flues & Chimneys

Damnedest flu pipe

This pipe draws combustible air from the outside giving the appliance the needed oxygen to run correctly. In its current state, it has the potential to draw carbon monoxide into the room from other appliances such as the water heater. Recommend servicing by a qualified HVAC technician as soon as possible.

Contractor Qualified Professional

6 - Cooling

IN NI NP R
6.1 Cooling Equipment
6.2 Normal Operating Controls
6.3 Distribution System
6.4 Presence of Installed Cooling Source in Each Room
Cooling Equipment: Energy Source/Type
Electric
Cooling Equipment: Location
Exterior East
Distribution System: Configuration
Split
Cooling Equipment: Brand
Unknown

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65° Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations

7 - Plumbing

IN NI NP R
7.1 Main Water Shut-off Device
7.2 Drain, Waste, & Vent Systems
7.3 Water Supply, Distribution Systems & Fixtures
7.4 Hot Water Systems, Controls, Flues & Vents
7.5 Fuel Storage & Distribution Systems
7.6 Sump Pump
7.7 Bathroom
7.8 Kitchen sink
Filters
None
Water Source
Public
Drain, Waste, & Vent Systems: Drain Size
2"
Water Supply, Distribution Systems & Fixtures: Distribution Material
Copper
Water Supply, Distribution Systems & Fixtures: Water Supply Material
Copper
Hot Water Systems, Controls, Flues & Vents: Power Source/Type
Gas
Hot Water Systems, Controls, Flues & Vents: Location
Basement, Utility Room
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
Gas Meter
Sump Pump: Location
None present
Main Water Shut-off Device: Location
Basement
Drain, Waste, & Vent Systems: Material
ABS
Hot Water Systems, Controls, Flues & Vents: Manufacturer
Bradford & White

I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding.

Here is a nice maintenance guide from Lowe's to help.

Hot Water Systems, Controls, Flues & Vents: Capacity
50 gallons
Bathroom : Shower/bath tub
Bathroom : Sink
Bathroom : Toilet
Kitchen sink: Kitchen sink

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
7.4.1 - Hot Water Systems, Controls, Flues & Vents

No Drip Pan

No drip pan was present. Recommend installation by a qualified plumber.
Pipes Plumbing Contractor
7.4.2 - Hot Water Systems, Controls, Flues & Vents

No Expansion Tank

No expansion tank was present. Expansion tanks allow for the thermal expansion of water in the pipes. These are required in certain areas for new installs. Recommend a qualified plumber evaluate and install.
Pipes Plumbing Contractor
7.4.3 - Hot Water Systems, Controls, Flues & Vents

Gas line drip leg missing

Contractor Qualified Professional

8 - Electrical

IN NI NP R
8.1 Service Entrance Conductors
8.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device
8.3 Branch Wiring Circuits, Breakers & Fuses
8.4 Lighting Fixtures, Switches & Receptacles
8.5 GFCI & AFCI
8.6 Smoke Detectors
8.7 Carbon Monoxide Detectors
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Back
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
GTE Sylvania
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Branch Wiring Circuits, Breakers & Fuses: Branch Wire 15 and 20 AMP
Copper
Branch Wiring Circuits, Breakers & Fuses: Wiring Method
Romex
Service Entrance Conductors: Electrical Service Conductors
Below Ground
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Capacity
125 AMP
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Sub Panel Location
Basement
Lighting Fixtures, Switches & Receptacles: Electrical receptacles
GFCI & AFCI: GFCI

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors’ insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
8.2.1 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Knockouts Missing

"Knockouts" are missing on the electric panel. This poses a safety hazard and it is recommended that the opening in the panel caused by the missing knockout(s) be properly sealed by a licensed electrician.

Electric Electrical Contractor
8.2.2 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Missing Labels on Panel

At the time of inspection, panel was missing labeling. Recommend a qualified electrician or person identify and map out locations. 

Electric Electrical Contractor
8.4.1 - Lighting Fixtures, Switches & Receptacles

Bathroom fan is In operable

Contractor Qualified Professional
8.4.2 - Lighting Fixtures, Switches & Receptacles

Light switch is Running hot

Recommend replacement by a competent licensed electrician. 

Contractor Qualified Professional
8.4.3 - Lighting Fixtures, Switches & Receptacles

No power to receptacles

Contractor Qualified Professional
8.4.4 - Lighting Fixtures, Switches & Receptacles

Cover Plates Damaged

One or more receptacles have a damaged cover plate. Recommend replacement.
Electric Electrical Contractor
8.4.5 - Lighting Fixtures, Switches & Receptacles

Cover Plates Missing

One or more receptacles are missing a cover plate. This causes short and shock risk. Recommend installation of plates.
Electric Electrical Contractor
8.4.6 - Lighting Fixtures, Switches & Receptacles

Light Inoperable

One or more lights are not operating. New light bulb possibly needed.
Electric Electrical Contractor
8.4.7 - Lighting Fixtures, Switches & Receptacles

Cover plate missing screws

Contractor Qualified Professional
8.4.8 - Lighting Fixtures, Switches & Receptacles

Receptacle damaged

This receptacle is slightly broken as discussed. 

Contractor Qualified Professional
8.6.1 - Smoke Detectors

Missing smoke detector

Contractor Qualified Professional

9 - Attic, Insulation & Ventilation

IN NI NP R
9.1 Attic Insulation
9.2 Vapor Retarders (Crawlspace or Basement)
9.3 Ventilation
9.4 Exhaust Systems
Flooring Insulation
None
Attic Insulation: R-value
38

The attic is well insulated and has good ventilation.

Ventilation: Ventilation Type
Soffit Vents, Gable Vents, Ridge Vents
Exhaust Systems: Exhaust Fans
Fan Only
Dryer Power Source
220 Electric
Dryer Vent
Metal

Basement laundry room 


 Dryer vent is a little bit long Restricting airflow recommend of shortening or straightening the corrugated vent from the dryer.

Attic Insulation: Insulation Type
Blown

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations

10 - Doors, Windows & Interior

IN NI NP R
10.1 Doors
10.2 Windows
10.3 Floors
10.4 Walls
10.5 Ceilings
10.6 Steps, Stairways & Railings
10.7 Countertops & Cabinets
Doors: Closet doors
Doors: Garage door
Doors: Interior doors
Windows: Window Type
Double-hung, Sliders
Windows: Window Manufacturer
Unknown
Floors: Floor Coverings
Tile, Carpet
Walls: Wall Material
Drywall
Ceilings: Ceiling Material
Gypsum Board
Steps, Stairways & Railings: Stairwell and steps
Countertops & Cabinets: Countertop Material
Granite, Marble
Countertops & Cabinets: Cabinetry
Wood

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
10.1.1 - Doors

Closet doors Out of alignment

Out of alignment resulting in doors rubbing on one another.

Contractor Qualified Professional
10.1.2 - Doors

Door Doesn't Latch

Door doesn't latch properly. Recommend handyman repair latch and/or strike plate.
Wrenches Handyman
10.2.1 - Windows

Needs to be caulked

Needs to be caulked. Recommend that windows are sealed and caulked to prevent moisture intrusion. 

Contractor Qualified Professional
10.3.1 - Floors

Carpet Stains

Carpet had areas of staining or discoloration. Recommend a thorough steam clean by a qualified carpet cleaning company. 

Mop Cleaning Service
10.4.1 - Walls

Poor Patching

Sub-standard drywall patching observed at time of inspection. Recommend re-patching. 

Putty knife Drywall Contractor
10.4.2 - Walls

Cracks holes and damage

Cracks, holes and damage found in various parts of the drywall throughout the home. Recommend a competent drywall contractor to make repairs as needed.

Contractor Qualified Professional
10.5.1 - Ceilings

Minor Damage

Minor damage or deterioration to the ceiling was visible at the time of the inspection.

Contractor Qualified Professional
10.5.2 - Ceilings

Stain(s) on Ceiling

There is a stain on ceiling/wall that requires repair and paint.  Source of staining should be determined.

Contractor Qualified Professional
10.5.3 - Ceilings

Minor Cracking

Cracks in the ceiling were visible at time of inspection. 

Contractor Qualified Professional

11 - Built-in Appliances

IN NI NP R
11.1 Dishwasher
11.2 Refrigerator
11.3 Range/Oven/Cooktop
11.4 Garbage Disposal
Range/Oven/Cooktop: Range/Oven Brand
Jenn-Air, GE
Range/Oven/Cooktop: Exhaust Hood Type
None
Dishwasher: Brand
Whirlpool
Refrigerator: Brand
GE
Range/Oven/Cooktop: Range/Oven Energy Source
Gas, Electric
Range/Oven/Cooktop: Microwave oven
Garbage Disposal: Garbage disposal

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • R = Recommendations
11.3.1 - Range/Oven/Cooktop

Oven Not Heating Up

Gas oven wasn't heating up at time of inspection. Recommend a qualified appliance contractor evaluate and repair. 

Here is a DIY troubleshooting tip

Contractor Qualified Professional