1234 Main St.
OCEANSIDE, CALIFORNIA 92057
12/05/2019 9:00AM

Sample agent
agent

Agent Name

Agency Name
1
Maintenance item
17
Recommendation
2
Safety hazard

Thank you for choosing Triton Home Inspections.  I really appreciate your business and want to ensure that you get the most out of my inspection and this inspection report.  A lot of time and care have been taken to prepare this document for you.  Please read the entire inspection report and call us immediately with any questions.  

****Verbal statements or opinions expressed at the time of the inspection are not to be relied upon.  Only the statements written in this report are the official opinions of your inspector Ken Stoermer.****

Very Important Next Steps:  

Step 1:  Read the entire inspection report!
Step 2:  Call your inspector immediately at 760/533-6605, if you have any questions, concerns, or need changes made to the inspection report.

Step 3:  Make a list of all Discovery Items marked Consideration Items, Attention Items, and Safety Concerns identified in this report as needing repair or further evaluation.  

Step 4:  Contact licensed contractors, specialist, and/or qualified professionals and have the Systems marked Consideration Items, Attention Items, and Safety Concerns further evaluated or repaired BEFORE THE END OF YOUR CONTINGENCY PERIOD.


PLEASE BE ADVISED:

This inspection report is the exclusive and sole property of Triton Home Inspections and the Clients who's name appears in the Inspection Details section of the report labeled Client.  

Unauthorized reproduction and/or distribution of this report is strictly prohibited.
Subsequent buyers, real estate agents and/or sellers assume full responsibility for giving this inspection report to anyone who does not have a signed contract or written agreement with Triton Home Inspections.  Due to the natural aging process of the materials used in constructing a home, and the normal wear and tear on the mechanical items in the home, THIS REPORT CAN ONLY REFLECT OBSERVATIONS MADE ON THE DAY OF THE INSPECTION. Subsequent buyers should have a new inspection performed to protect their interests.

Triton Home Inspections inspect properties in accordance with the Standards of Practice and Code of Ethics of the International Association of Certified Home Inspectors and our inspection agreement which are listed on our website at the following link: Inspection Agreement. Items that are excluded (not inspected) are indicated in the contract and/or disclaimed in the aforementioned Standards of Practice. The observations and opinions expressed within the report take precedence over any verbal comments. It should be understood that the inspector is only on-site for a few hours and will not comment on insignificant deficiencies, but rather, confine the observations to truly significant defects or deficiencies that significantly affect the value, desirability, habitability or safety of the structure.  The Client should consider all defects identified in this inspection report as significant.

The inspection shall be limited to those specific systems, structures and components that are present and accessible. Components and systems shall be operated with normal user controls, and not forced or modified to work. Those components or systems that are found not to work at time of inspection will be reported, and those items should be inspected and repaired or replaced by a qualified specialist in that field. You must obtain estimates for any items noted in the report that require further evaluation or repair. The inspector cannot know what expense would be considered significant by client, as everyone's budget is different. It is therefore client's responsibility to obtain quotations prior to the end of the contingency period. . This is very important, as once you pass the contingency period, or purchase the house, repairs become your sole responsibility. If you have questions about the significance of a repair item, call a licensed professional immediately.

The recommendations that the inspector makes in this report for specialist evaluations should be completed within the contingency period by licensed professionals, who may well identify additional defects or recommend some upgrades or replacements that could affect your evaluation of the property. We caution you to be wary of anyone who has a vested interest, and particularly those who attempt to alarm you or denigrate others.

***** VERY IMPORTANT*****

We feel that everything in this inspection report is significant.  Especially the Discovery items marked  Observation Items, Attention Items and Safety Concern.  We cannot assume liability for an item, system, or component the client did not feel was significant at time of inspection, but later feels is.  For this reason, we are informing you that when as little as one Component is called out as Observation Items, Attention Items, or Safety Concern in any System of this home inspection report, you must have that entire system further evaluated by a licensed specialist in that field before the end of your contingency period.  These licensed specialist may identify additional components within that system that need to be repaired/replaced or recommend some upgrades that could affect your evaluation of the property.  

Definitions that may help you understand the above statement better:

System = a set of components working together as parts of a mechanism or an interconnecting network.  Examples of a system would be; the Roofing system, the Plumbing system, the Electrical system.

Component = a part or an element of a system. Examples of components would be; a shingle in a Roofing system, a faucet in a Plumbing system, a circuit breaker in an Electrical system.


SCOPE OF WORK

You have contracted me, Ken Stoermer at Triton Home Inspections, to perform a general home inspection.  I performed this inspection in accordance with Standards of Practice and Code of Ethics established by the International Association of Certified Home Inspectors (Inter-NACHI). A copy of these standards and ethics can be obtained by visiting Standards of Practice and the Code of Ethics.  It is distinct from a specialist inspection, which can be costly, take several days to complete, involve the use of specialized instruments, the dismantling of equipment, video-scanning, destructive testing, and laboratory analysis. By contrast, the general home inspection is completed on-site, at a fraction of the cost and within an hour. Consequently, this general home inspection and its report will not be as comprehensive as that generated by specialists and it is not intended to be. 

The purpose of this inspection is to identify systems that should be further evaluated by licensed contractors who through their evaluations may identify additional components, material defects or adverse conditions that could result in injury or lead to costs that would significantly affect your evaluation of the property.  I strongly urge you to follow my further evaluation recommendations as stated in the inspection report prior to the end of your contingency period to prevent unexpected issues from arising after the close of escrow.

I evaluate conditions, systems, or components, and report on their condition, which does not mean that they are ideal but that they are either functional or met a reasonable standard at a given point in time. I do take into consideration when a house was built and allow for the predictable deterioration that would occur through time, such as the cracks that appear in concrete and in the plaster around windows and doors, scuffed walls or woodwork, worn or squeaky floors, stiff or stuck windows, and cabinetry that does not function as it did when new. Therefore, we tend to ignore insignificant and predictable defects, and do not annotate them, and particularly those that would be apparent to the average person or to someone without any construction experience. I am not authorized, or have the expertise, to test for environmental contaminants, or comment on termite, dry rot, fungus or mold, but may alert you to its presence. Similarly, I do not test the quality of the air within a residence. However, clean air is essential to good health, and I recommend air sampling and the cleaning of supply ducts as a wise investment in environmental hygiene. Therefore, you should schedule any such specialized inspections with the appropriate specialist before the close of escrow.

A home and its systems and its components are complicated, and because of this and the limitations of an on-site report, I only offer unlimited consultation and encourage you to ask questions.  I encourage candid and forthright communication between all parties, because I believe that it is the only way to avoid stressful disputes and costly litigation. Remember, I only summarized the report on-site and it is essential that you read all of it, and that any recommendations that are made for service or evaluation by specialists should be completed and documented well before the close of escrow, because additional defects could be revealed by specialists, or some upgrades recommended that could affect your evaluation of the property, and my service does not include any form of warranty or guarantee.

Definitions of Comments:

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. That professional should inspect the entire system or component, as problems at one area could indicate problems at other areas of the system. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and it appeared to be functioning as intended.
Not Inspected (NI) = I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended.
Not Present (NP) = This item, component or unit is not in this home or building.
Discovery (D) = One of the following conditions exist: Observation Items, Attention Item, or Safety Concern.


Observation Items = May include one or more of the following conditions:
1.  Items that may not be affecting the function or usability of a system or component.  However, if not corrected, it may at some point in the future.

2.  Items that may required repair due to age and/or normal wear and tear. 

3.  The items should be monitored; repair or replacement should be considered.

Attention Items = May include any one or more of the following conditions:  
1.  The item is not functioning as intended.  

2.  The item and its entire system need to be further evaluated by a licensed contractor in that field (Plumbing = Plumber, Electrical = Electrician, etc.).  The item and/or other items within the system (not identified in this report) may need to be repaired or replaced. 

3.  Areas, systems or components that were not accessible by our company.

Safety Concern = May include the following condition:
1.  Items or systems in which the current state poses a potential safety hazard to the occupants or structure (in the inspectors opinion).  This item should be immediately further evaluated and repaired by a qualified technician/contractor to ensure safety.

Note: Damage or additional items in need of repair may exist that are not identified in this inspection report and/or are beyond the scope of this home inspection, may be discovered by the licensed contractor.  This is why I strongly recommend that you seek further inspections and evaluations BEFORE THE END OF YOUR CONTINGENCY PERIOD.  I cannot and will not be responsible for your failure to follow our recommendations listed in this inspection report.    

A home inspection and its report are only describing the condition of the systems and components of this house on the day of inspection.  This home inspection is not a home warranty or guarantee of any kind.  Systems and components of this home may and probably will fail anytime after the inspection.  

I HIGHLY recommend that you purchase and maintain a comprehensive home warranty, including coverage for your home, swimming pool, roofing, heating and air conditioning, plumbing, and electrical systems and renew it each year you own this house.

Mold:

If you or a family member has health problems, or you are concerned about mold, it is YOUR responsibility to get an air quality or mold inspection completed, regardless of the findings in this report.  Triton Home Inspections is not a mold inspection company and is not qualified/licensed to inspect for nor identify mold.

Environmental Hazards:

My company is not licensed or trained to inspect for or test for environmental hazards.  If you or anyone occupying or visiting this property are concerned about environmental hazards like; lead, radon, mold, PCBs, mildew, urea- formaldehyde, asbestos, sulfur, contaminated drywall, Chinese drywall, or other toxins in the building, ground, water or air, you need to contact a licensed environmental hygienist to have them visit the property and test for these issues.    

Pest:

My company is not licensed or trained to inspect for pest to include but not limited to: rodents, insects, wood destroying organisms or the damage caused by these animals/organisms. 

Pictures:

Any pictures included in this report are not meant to represent every defect that has been found. There may be Observation, Attention and Safety Concern items that do not have a picture included. We suggest reading the entire report to find all of the defects that have been reported on. Pictures, if included, represent only the key finding associated with that picture. If you have any questions on the key findings, please contact the inspector for clarification.  

Please Note:  Triton Home Inspections hereby certifies that we have no interest present or prospective in the property, buyer, seller, lender or any other party involved in this transaction.

1 - Inspection Details

In Attendance
Client, Client's Agent
Occupancy
Vacant
Type of Building
Single Family
Weather Conditions
Clear

2 - Exterior

IN NI NP D
2.1 Siding, Flashing & Trim X X
2.2 Exterior Doors X
2.3 Walkways, Patios & Driveways X X
2.4 Decks, Balconies, Porches & Steps X
2.5 Eaves, Soffits & Fascia X
2.6 Vegetation, Grading, Drainage & Retaining Walls X
Inspection Method
Attic Access
Siding, Flashing & Trim: Siding Material
Stucco
Walkways, Patios & Driveways: Driveway Material
Concrete

The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
2.1.1 - Siding, Flashing & Trim

Holes and/or gaps

One or more holes or gaps were found in siding or trim. Vermin, insects or water may enter the structure. Recommend that a qualified person repair as necessary.

Contractor Qualified Professional
Credit
Comment
2.3.1 - Walkways, Patios & Driveways

Driveway Draining Towards Home

The driveway has a negative slope and drains towards the structure and garage. Recommend a driveway contractor evaluate and repair.

Credit
Comment
2.3.2 - Walkways, Patios & Driveways

Handrails missing

Handrails at one or more flights of stairs were missing. This is a potential fall hazard. Handrails should be installed at stairs with four or more risers or where stairs are greater than 30 inches high. Recommend that a qualified contractor install handrails where missing and per standard building practices.

Contractor Qualified Professional

3 - Roof

IN NI NP D
3.1 Coverings X X
3.2 Roof Drainage Systems X X
3.3 Flashings X
3.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Roof
Roof Type/Style
Gable
Coverings: Material
Asphalt
Roof Drainage Systems: Gutter Material
Aluminum

 The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
3.2.1 - Roof Drainage Systems

Debris

Debris has accumulated in the gutters. Recommend cleaning to facilitate water flow.

Here is a DIY resource for cleaning your gutters. 

Credit
Comment
3.2.2 - Roof Drainage Systems

Downspouts Missing

Home was missing downspouts in one or more areas. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor install downspout extensions that drain at least 6 feet from the foundation. 

Credit
Comment
3.2.3 - Roof Drainage Systems

Gutter Damaged

Gutters were damaged. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor evaluate and repair. 

4 - Electrical

IN NI NP D
4.1 Service Entrance Conductors X
4.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X X
4.3 Branch Wiring Circuits, Breakers & Fuses X
4.4 Lighting Fixtures, Switches & Receptacles X X
4.5 GFCI & AFCI X
4.6 Smoke Detectors X
4.7 Carbon Monoxide Detectors X
Service Entrance Conductors: Electrical Service Conductors
Below Ground
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Right
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Capacity
100 AMP
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
Federal Pacific
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Anti Oxidant Paste

One or more multi-strand aluminum wires in panel(s) # lacked anti-oxidant paste at their connections with other equipment (e.g. circuit breakers, lugs, bus bars). Oxidation can occur without it and result in reduced conductivity and overheating. This is a potential fire hazard. Recommend that a qualified electrician apply anti-oxidant paste per standard building practices.

The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items or child-protective caps are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician.

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
4.2.1 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Pacific Stab-Lok Panel

Panel is manufactured by the Federal Pacific Electric company and used "Stab-Lok" circuit breakers. There is significant evidence that both double and single pole versions of these circuit breakers fail by not tripping when they are supposed to. However, in 2011 the Consumer Products Safety Commission (CPSC) closed an investigation into this product because they did not have enough data to establish that the circuit breakers pose a serious risk of injury to consumers. Regardless, and due to other evidence of safety issues, recommend that a qualified electrician carefully evaluate all Federal Pacific panels and make repairs as necessary. Consider replacing Federal Pacific panels with modern panels that offer more flexibility for new, safer protective technologies like ground fault circuit interrupters (GFCls) and arc fault circuit interrupters (AFCls).

Electric Electrical Contractor
Credit
Comment
4.4.1 - Lighting Fixtures, Switches & Receptacles

Switches Installed Improperly
Right hand side bedroom 2nd Floor

One or more switches are installed improperly. Recommend licensed electrician repair or replace.
Credit
Comment
4.4.2 - Lighting Fixtures, Switches & Receptacles

Loose outlet

One or more loose outlet was noted at the time of the inspection. Recommend further evaluation by a licensed electrical contractor before the end of your contingency period to determine repairs possible at this time.

Electric Electrical Contractor
Credit
Comment
4.4.3 - Lighting Fixtures, Switches & Receptacles

Ungrounded GFCI
Bathrooms and the back exterior

One or more ground fault circuit interrupter (GFCI) type receptacles had an open ground. Open ground GFCI receptacles will trip, but they won't provide a grounded electric supply for appliances that need them. This is a potential shock hazard. Recommend that a qualified electrician repair per standard building practices. For example, by upgrading to grounded, 3-conductor wiring. In older dwellings constructed when GFCI protection was not required, and in areas where GFCI protection is not required, replacing 3-slot GFCI receptacles with 2-slot receptacles may be an acceptable repair.

Electric Electrical Contractor

5 - Plumbing

IN NI NP D
5.1 Main Water Shut-off Device X
5.2 Drain, Waste, & Vent Systems X
5.3 Water Supply, Distribution Systems & Fixtures X X
5.4 Hot Water Systems, Controls, Flues & Vents X
5.5 Fuel Storage & Distribution Systems X
5.6 Sediment Trap X
Water Source
Public
Main Water Shut-off Device: Location
Front Exterior
Drain, Waste, & Vent Systems: Drain Size
Unknown
Drain, Waste, & Vent Systems: Material
ABS
Water Supply, Distribution Systems & Fixtures: Distribution Material
Unknown
Water Supply, Distribution Systems & Fixtures: Water Supply Material
Copper
Hot Water Systems, Controls, Flues & Vents: Location
Exterior Closet
Hot Water Systems, Controls, Flues & Vents: Power Source/Type
Gas
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
Gas Meter
Hot Water Systems, Controls, Flues & Vents: Manufacturer
Bradford & White

I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. 

Here is a nice maintenance guide from Lowe's to help. 

Sediment Trap:

No sediment trap was installed in the gas supply line at the . Sediment traps prevent damage to gas-fired appliances by trapping oil, scale, water condensation and/or debris. Recommend that a qualified contractor install a sediment trap per standard building practices.

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
5.3.1 - Water Supply, Distribution Systems & Fixtures

Water valve leaking
Garage

One or more leaks were found in water supply valve for the washing machine's cold water. A qualified plumber should repair as necessary.

Pipes Plumbing Contractor

6 - Garage

IN NI NP D
6.1 Ceiling X
6.2 Floor X
6.3 Walls & Firewalls X
6.4 Garage Door X
6.5 Garage Door Opener X
6.6 Exposed Gas appliances X
6.7 Occupant Door (From garage to inside of home) X
Garage Door: Material
Metal
Garage Door: Type
Sectional

The inspector does not determine the adequacy of firewall ratings. Requirements for ventilation in garages vary between municipalities.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies

7 - Basement, Foundation, Crawlspace & Structure

IN NI NP D
7.1 Foundation X
7.2 Basements & Crawlspaces X
7.3 Floor Structure X
7.4 Wall Structure X
7.5 Ceiling Structure X
Inspection Method
Attic Access
Foundation: Material
Slab on Grade

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies

8 - Heating

IN NI NP D
8.1 Equipment X
8.2 Normal Operating Controls X
8.3 Distribution Systems X X
8.4 Presence of Installed Heat Source in Each Room X
Equipment: Brand
Goodman
Equipment: Energy Source
Gas
Equipment: Heat Type
Forced Air
Distribution Systems: Ductwork
Insulated

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
8.3.1 - Distribution Systems

Insulation damaged and/or deteriorated

One or more heating or cooling ducts in an unconditioned space (e.g. crawl space, attic or basement) were not insulated, or the insulation was damaged or deteriorated.  This can result in reduced energy efficiency, moisture inside heating ducts, and/or "sweating" on cooling ducts. Recommend that a qualified person repair per standard building practices. For example, by wrapping ducts in insulation with an R-value of R-8.

Contractor Qualified Professional

9 - Cooling

IN NI NP D
9.1 Cooling Equipment X X
9.2 Normal Operating Controls X
9.3 Distribution System X
9.4 Presence of Installed Cooling Source in Each Room X
Cooling Equipment: Brand
Goodman
Cooling Equipment: Energy Source/Type
Electric
Cooling Equipment: Location
Exterior

The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms)

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65 Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
9.1.1 - Cooling Equipment

Air Flow Restricted

Permanent structures were too close to the heat pump or air conditioning condensing unit. There should be at least 12 inches of clearance on all sides and at least 4-6 feet above. Inadequate clearances around and above can result in reduced efficiency, increased energy costs and/or damage to equipment. Recommend making repairs or modifications as necessary to maintain these clearances, by a qualified contractor if necessary.

Credit
Comment
9.1.2 - Cooling Equipment

Dryer vent near condenser

House vents should not be near the AC compressor or condenser.  Clothes dryer lint can quickly plug coils.  Combustion products can damage the coils.

Contractor Qualified Professional

10 - Fireplace

IN NI NP D
10.1 Vents, Flues & Chimneys X X
10.2 Lintels X
10.3 Damper Doors X X
10.4 Cleanout Doors & Frames X X
Type
Wood, Gas

The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.

I. The inspector shall inspect:

readily accessible and visible portions of the fireplaces and chimneys;

lintels above the fireplace openings;

damper doors by opening and closing them, if readily accessible and manually operable; and

cleanout doors and frames.

II. The inspector shall describe:

the type of fireplace.

III. The inspector shall report as in need of correction:

evidence of joint separation, damage or deterioration of the hearth, hearth extension or chambers;

manually operated dampers that did not open and close;

the lack of a smoke detector in the same room as the fireplace;

the lack of a carbon-monoxide detector in the same room as the fireplace; and

cleanouts not made of metal, pre-cast cement, or other non-combustible material.

IV. The inspector is not required to:

inspect the flue or vent system.

inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels.

determine the need for a chimney sweep.

operate gas fireplace inserts.

light pilot flames.

determine the appropriateness of any installation.

inspect automatic fuel-fed devices.

inspect combustion and/or make-up air devices.

inspect heat-distribution assists, whether gravity-controlled or fan-assisted.

ignite or extinguish fires.

determine the adequacy of drafts or draft characteristics.

move fireplace inserts, stoves or firebox contents.

perform a smoke test.

dismantle or remove any component.

perform a National Fire Protection Association (NFPA)-style inspection.

perform a Phase I fireplace and chimney inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
10.1.1 - Vents, Flues & Chimneys

No Sparkscreen or Raincap

No spark screen or rain cap was installed at one or more chimney flue terminations. Spark screens reduce the chance of embers exiting the flue and causing fires. They also prevent wildlife (e.g. birds, rodents, raccoons) from entering flues. Rain caps prevent water from entering flues, mixing with combustion deposits and creating caustic chemicals which can corrode flues. They also prevent damage to masonry from freeze-thaw cycles and prevent metal components (e.g. dampers, metal firebox liners) from rusting. Recommend that a qualified person install rain caps with spark screens per standard building practices where missing.

Contractor Qualified Professional
Credit
Comment
10.1.2 - Vents, Flues & Chimneys

Exterior caulking

Gaps were found between the brick chimney and the building exterior. Recommend that a qualified person repair as necessary to prevent water, insect and/or vermin intrusion. For example, by installing or renewing caulk. Note that an approved material other than caulk should be used for gaps wider than 1/4 inch.

Contractor Qualified Professional
Credit
Comment
10.3.1 - Damper Doors

Damper Inoperable

Damper was corrodid and inoperable. Recommend a qualified fireplace contractor repair.

Credit
Comment
10.4.1 - Cleanout Doors & Frames

Ash clean out doors

One or more ash clean-out doors were missing and/or corroded. Recommend that a qualified person repair or replace as necessary.

Contractor Qualified Professional

11 - Attic, Insulation & Ventilation

IN NI NP D
11.1 Attic Insulation X X
11.2 Vapor Retarders (Crawlspace or Basement) X
11.3 Ventilation X
11.4 Exhaust Systems X
Dryer Power Source
Gas
Dryer Vent
None installed

 The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
11.1.1 - Attic Insulation

Compacted and/or uneven

The ceiling insulation in one or more areas of the attic was uneven and very compacted. Heating and cooling costs may be higher due to reduced energy efficiency. Recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).

Contractor Qualified Professional

12 - Doors, Windows & Interior

IN NI NP D
12.1 Doors X
12.2 Windows X
12.3 Floors X
12.4 Walls X
12.5 Ceilings X
12.6 Steps, Stairways & Railings X X
12.7 Countertops & Cabinets X
12.8 Smoke alarms X

The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
12.6.1 - Steps, Stairways & Railings

Baluster Spaces Too Wide

The baluster space is not up to modern safety standards. The space between balusters should not allow passage of a 4 3/8-inch sphere for child safety. Recommend a qualified handyman or original installer repair and bring up to code. 

13 - Built-in Appliances

IN NI NP D
13.1 Dishwasher X
13.2 Refrigerator X
13.3 Range/Oven/Cooktop X
13.4 Garbage Disposal X
13.5 Built-in Microwave X
Range/Oven/Cooktop: Exhaust Hood Type
Vented
Range/Oven/Cooktop: Range/Oven Energy Source
Gas
  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies