1234 Main St.
Elkton , OR 97436
07/20/2019 9:00AM

Sample agent
agent

Agent Name

Agency Name
56
Recommendation
2
Safety hazard

1 - Roof

IN NI NP D
1.1 Coverings X X
1.2 Roof Drainage Systems X X
1.3 Flashings X X
1.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Ladder, Roof
Roof Drainage Systems: Gutter Material
Aluminum
Flashings: Material
Aluminum
Roof Type/Style
Gable, Hip, Combination

The roof style is a gable/hip combination. The pitch was a 3:12 which is suitable for the type of covering used.  

Coverings: Material
Asphalt

The second story roof is in need of repair/replacement. The 3 tab shingles are showing granule loss along with several other issues

Skylights, Chimneys & Other Roof Penetrations: Roof penetrations

The roof vents and vent stacks appear to be in decent condition with no water intrusion showing at this time. Because we have had no rain for a few months though, it should be noted that leaks may become apparent after some rain has fallen. 

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
1.1.1 - Coverings

Damaged (General)
Second story roof

Roof coverings showed moderate damage. Recommend a qualified roofing professional evaluate and repair. 

Credit
Comment
1.1.2 - Coverings

Shingles Missing

Observed areas that appeared to be missing sufficient coverings. Recommend qualified roofing contractor evaluate & repair. 

Credit
Comment
1.1.3 - Coverings

Underlayment Damage

The roof underlayment had areas of moderate damage visible at the time of the inspection. These areas should be repaired by a qualified roofing contractor to help prevent damage from roof leakage. The underlayment was inspected in representative areas only.

Credit
Comment
1.1.4 - Coverings

Roof sag
Second story roof

Roof sag was observed in the second story roof. I was unable to determine the cause of the sag. This was due to limited access to roof structure. 

Contractor Qualified Professional
Credit
Comment
1.2.1 - Roof Drainage Systems

Downspouts Drain Near House

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 6 feet from the foundation. 

Here is a helpful DIY link and video on draining water flow away from your house. 

Credit
Comment
1.2.2 - Roof Drainage Systems

Downspouts Missing
Back left corner of home

Home was missing downspouts in one or more areas. Recommend a qualified contractor install downspout extensions that drain at least 6 feet from the foundation. 

Credit
Comment
1.2.3 - Roof Drainage Systems

Gutter Damaged

Gutters have multiple failing joints and fasteners that are pulling out. Recommend a qualified contractor evaluate and repair

Credit
Comment
1.2.4 - Roof Drainage Systems

Gutter Improperly Sloped

Gutter are improperly sloped in areas, which could result in runoff drainage around the foundation and possible structural shifting. Recommend qualified roofing or gutters contractor repair.

Credit
Comment
1.2.5 - Roof Drainage Systems

Gutter Loose

The gutter(s) is loose and needs to be re-fastened to fascia and pitched properly.

Credit
Comment
1.3.1 - Flashings

Missing
1st Floor roof

The home is missing drip edge flashing on the lower roof. This has already begun to cause damage. Recommend having a licensed roofing contractor evaluate and remedy. The second story roof does have a drip edge installed

Credit
Comment
1.3.2 - Flashings

Incorrect flashing

On the back side of the lower roof, there is an incorrect flashing application. Recommend a further evaluation by a licensed roofer.  

Contractor Qualified Professional

2 - Inspection Details

In Attendance
Client's Agent, Licensed contractor
Occupancy
Occupied
Style
Multi-level
Temperature (approximate)
75 Fahrenheit (F)
Type of Building
Detached, Single Family
Weather Conditions
Clear, Dry
Drainage

Property could not be evaluated for proper drainage due to the dry season. Evidence suggests that the lot may have poor drainage behind the house. This cannot be confirmed but should be noted

3 - Exterior

IN NI NP D
3.1 Siding, Flashing & Trim X X
3.2 Exterior Doors X X
3.3 Walkways, Patios & Driveways X X
3.4 Decks, Balconies, Porches & Steps X
3.5 Eaves, Soffits & Fascia X X
3.6 Vegetation, Grading, Drainage & Retaining Walls X X
Inspection Method
Visual, Crawlspace Access, Attic Access
Siding, Flashing & Trim: Siding Style
Panels
Exterior Doors: Exterior Entry Door
Fiberglass

Door needs weatherstripping and the strike plate adjusted

Walkways, Patios & Driveways: Driveway Material
Concrete, Gravel
Decks, Balconies, Porches & Steps: Appurtenance
Front Porch
Siding, Flashing & Trim: Siding Material
Engineered Wood, Stucco

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
3.1.1 - Siding, Flashing & Trim

Evidence of Water Intrusion

Siding showed signs of water intrusion. This could lead to further siding deterioration and/or mold. Recommend a qualified siding contractor evaluate and repair. 

Credit
Comment
3.1.2 - Siding, Flashing & Trim

Flashing/Trim Improperly Installed

no Flashing is evident at time of inspection

Credit
Comment
3.1.3 - Siding, Flashing & Trim

Ground Clearance

Inadequate clearance between siding and ground.   Recommend a minimum ground clearance between bottom of siding and ground of 4". Siding in contact with the ground or soil is a serious concern because that condition can provide direct access for wood destroying insects.

Credit
Comment
3.1.4 - Siding, Flashing & Trim

Splitting

Siding trim is  splitting in one or more areas, which can lead to moisture intrusion and/or mold. Recommend monitoring for excessive splitting, in which case a qualified siding contractor should evaluate and repair/replace. Trim is inappropriate for application.

Credit
Comment
3.1.5 - Siding, Flashing & Trim

Trim defects

Trim is splitting in places(orange arrow). Interior trim is being used in an exterior application(red arrow). Plywood is being used as a trim and has signs of water damage (green). Horizontal trim is showing signs of bubbling which indicates water damage (blue). Butt joints of trim is separating and should be filled with caulking to prevent water intrusion(white)

Contractor Qualified Professional
Credit
Comment
3.1.6 - Siding, Flashing & Trim

Incorrect siding application

T&G siding should be installed vertically. 

Contractor Qualified Professional
Credit
Comment
3.1.7 - Siding, Flashing & Trim

Poor siding installation

The siding on the garage has been poorly installed and should be evaluated by a qualified contractor. 

Contractor Qualified Professional
Credit
Comment
3.2.1 - Exterior Doors

Weatherstripping Not Present
Front door, rear french doors

Doors are missing standard weatherstripping. This can result in significant energy loss and moisture intrusion. Recommend installation of standard weatherstripping.

Here is a DIY guide on weatherstripping

Credit
Comment
3.3.1 - Walkways, Patios & Driveways

Walkway Cracking - Minor

Minor cosmetic cracks observed. Recommend monitor and/or patch/seal.
Credit
Comment
3.5.1 - Eaves, Soffits & Fascia

Eaves - Damaged

One or more sections of the eaves are damaged. Recommend qualified roofer evaluate & repair.
Credit
Comment
3.5.2 - Eaves, Soffits & Fascia

Gap

There is opening, gap or hole in fascia / soffit which should be repaired. This can allow water intrusion and rodent infestation as well as deterioration of the surrounding material.

Credit
Comment
3.5.3 - Eaves, Soffits & Fascia

Wasps Nest

Wasp nests were visible under the soffits. Recommend a qualified exterminator evaluate and remove.

Credit
Comment
3.6.1 - Vegetation, Grading, Drainage & Retaining Walls

Negative Grading

Grading is sloping towards the home in some areas. This could lead to water intrusion and foundation issues. Recommend qualified landscaper or foundation contractor regrade so water flows away from home.

Here is a helpful article discussing negative grading. 

Credit
Comment
3.6.2 - Vegetation, Grading, Drainage & Retaining Walls

Tree Overhang

Trees observed overhanging the roof. This can cause damage to the roof and prevent proper drainage. Recommend a qualified tree service trim to allow for proper drainage. 

4 - Basement, Foundation, Crawlspace & Structure

IN NI NP D
4.1 Foundation X X
4.2 Basements & Crawlspaces X X
4.3 Floor Structure X X
4.4 Wall Structure X X
4.5 Ceiling Structure X X
Inspection Method
Crawlspace Access, Visual, Attic Access
Foundation: Material
Concrete
Floor Structure: Basement/Crawlspace Floor
Dirt
Floor Structure: Material
Wood Beams, Concrete
Floor Structure: Sub-floor
Plank
Foundation inspection

Recommend further evaluation by a qualified engineer to address some issues with the homes foundation

Ceiling Structure: Ceilings

No defects were evident in the ceilings at time of inspection. Note the upper floor roof Is missing a large portion of shingles and this will cause ceiling damage in wet weather

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
4.1.1 - Foundation

Foundation Cracks - Minor

Minor cracking was noted at the foundation. This is common as concrete ages and shrinkage surface cracks are normal. Recommend monitoring for more serious shifting/displacement. 

Here is an informational article on foundation cracks.

Credit
Comment
4.1.2 - Foundation

Improper Construction Practices

Improper or sub-standard construction practices were noted at the foundation wall or slabs/piers. Recommend a structural engineer evaluate and advise on how to bring the construction up to standards. Issues include lack of a pressure treated sill at the wall structure, spans too long for unsupported beams and sagging beams

Credit
Comment
4.2.1 - Basements & Crawlspaces

Beam sag

Contractor Qualified Professional
Credit
Comment
4.3.1 - Floor Structure

Joists Need Repair

One or more floor joists were damaged or improperly installed. This can cause damage to the structural integrity of the home. Recommend a qualified structural engineer evaluate and advise on how to correct.
Credit
Comment
4.3.2 - Floor Structure

Post & Pier

Post support under the home is insufficient. Recommend additional support be added by a professional

Contractor Qualified Professional
Credit
Comment
4.4.1 - Wall Structure

Incorrect assembly

Wall should be constructed with 2 sill plates. The plate in contact with the concrete should be a PT board. This prevents bug and moisture damage

Contractor Qualified Professional

5 - Heating

IN NI NP D
5.1 Equipment X X
5.2 Normal Operating Controls X
5.3 Distribution Systems X X
5.4 Presence of Installed Heat Source in Each Room X
Equipment: Brand
Bryant
Equipment: Energy Source
Electric
Equipment: Heat Type
Heat Pump
AFUE Rating
13

AFUE (Annual fuel utilization efficiency) is a metric used to measure furnace efficiency in converting fuel to energy. A higher AFUE rating means greater energy efficiency. 90% or higher meets the Department of Energy's Energy Star program standard.

Distribution Systems: Ductwork
Insulated

Ducting was insulated

Presence of Installed Heat Source in Each Room: Ducting

Each room had a register for the heating system but has no other installed heat sources

Heating system limitations

The heat pump should be cleaned and serviced by a hvac professional to extend the life of the unit. 

Normal Operating Controls not inspected.

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
5.1.1 - Equipment

Filter Missing

The furnace filter was missing. Recommend replacement.

Here is a DIY video on changing furnace filters. 

Credit
Comment
5.1.2 - Equipment

Needs Servicing/Cleaning

Furnace should be cleaned and serviced annually. Recommend a qualified HVAC contractor clean, service and certify furnace.

Here is a resource on the importance of furnace maintenance.

Credit
Comment
5.3.1 - Distribution Systems

Duct Damaged

Air supply duct was damaged. Recommend a qualified HVAC contractor repair.

6 - Cooling

IN NI NP D
6.1 Cooling Equipment X
6.2 Normal Operating Controls X
6.3 Distribution System X X
6.4 Presence of Installed Cooling Source in Each Room X
Cooling system

The system operated correctly although a seviceing is recommended 

Cooling Equipment: Brand
Bryant
Cooling Equipment: Energy Source/Type
Electric
Cooling Equipment: Location
Garage
Distribution System: Configuration
Central
Cooling Equipment: SEER Rating
0 SEER

Modern standards call for at least 13 SEER rating for new install. 

Read more on energy efficient air conditioning at Energy.gov.

Normal Operating Controls: Cooling controls

The cooling system was tested and appears to work correctly. Recommend a service and cleaning by an hvac professional

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65 Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies

7 - Plumbing

IN NI NP D
7.1 Main Water Shut-off Device X
7.2 Drain, Waste, & Vent Systems X X
7.3 Water Supply, Distribution Systems & Fixtures X
7.4 Hot Water Systems, Controls, Flues & Vents X X
7.5 Fuel Storage & Distribution Systems X
7.6 Sump Pump X
Water Source
Public
Drain, Waste, & Vent Systems: Drain Size
1 1/2"
Drain, Waste, & Vent Systems: Material
PVC
Water Supply, Distribution Systems & Fixtures: Distribution Material
Pex
Water Supply, Distribution Systems & Fixtures: Water Supply Material
Pex
Hot Water Systems, Controls, Flues & Vents: Capacity
50 gallons
Hot Water Systems, Controls, Flues & Vents: Location
Garage enclosure
Hot Water Systems, Controls, Flues & Vents: Power Source/Type
Electric
Drain, Waste, & Vent Systems: Undersink damage
Filters
Kitchen Sink
Sediment Filter

Under the kitchen sink is a sediment filter. This was the only filter observed during the inspection

Plumbing

The plumbing appears to have been updated. Some defects were noted with draining

Hot Water Systems, Controls, Flues & Vents: Manufacturer
Whirlpool

I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. 

Here is a nice maintenance guide from Lowe's to help. 

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
7.2.1 - Drain, Waste, & Vent Systems

Improper Connection

An improper connection was observed at a drain, waste or vent pipe. Recommend a qualified plumber evaluate and repair.
Credit
Comment
7.2.2 - Drain, Waste, & Vent Systems

Toilet draining
1st Floor Bathroom

The toilet in the main bathroom is incorrectly sloped preventing good draining. Recommend having a plumber evaluate and rectify

Contractor Qualified Professional
Credit
Comment
7.4.1 - Hot Water Systems, Controls, Flues & Vents

No Drip Pan

No drip pan was present. Recommend installation by a qualified plumber.
Credit
Comment
7.4.2 - Hot Water Systems, Controls, Flues & Vents

No Expansion Tank

No expansion tank was present. Expansion tanks allow for the thermal expansion of water in the pipes. These are required in certain areas for new installs. Recommend a qualified plumber evaluate and install.

8 - Electrical

IN NI NP D
8.1 Service Entrance Conductors X X
8.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X X
8.3 Branch Wiring Circuits, Breakers & Fuses X X
8.4 Lighting Fixtures, Switches & Receptacles X X
8.5 GFCI & AFCI X X
8.6 Smoke Detectors X X
8.7 Carbon Monoxide Detectors X
Service Entrance Conductors: Electrical Service Conductors
Overhead
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Right
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Capacity
200 AMP
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
General Electric
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Sub Panel Location
None

No sub panel

Branch Wiring Circuits, Breakers & Fuses: Branch Wire 15 and 20 AMP
Copper
Branch Wiring Circuits, Breakers & Fuses: Wiring Method
Surface Mounted Distribution, Not Visible
Wiring

It appears the home has had  semi updated wiring installed. This did not replace all old wire but rather added to it

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
8.2.1 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Inadequate Ground

The ground at service entrance appears inadequate and should be checked by a licensed electrician.

Credit
Comment
8.2.2 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Knockouts Missing

"Knockouts" are missing on the electric panel. This poses a safety hazard and it is recommended that the opening in the panel caused by the missing knockout(s) be properly sealed by a licensed electrician.

Credit
Comment
8.2.3 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Missing Labels on Panel

At the time of inspection, panel was missing labeling. Recommend a qualified electrician or person identify and map out locations. 

Credit
Comment
8.2.4 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

No Ground Wire

Missing ground wire. Recommend qualified electrician evaluate and install. 

Credit
Comment
8.3.1 - Branch Wiring Circuits, Breakers & Fuses

Aluminum Branch Circuits

Aluminum wire appears to be installed on branch electrical circuits in the subject premises. These single strand, branch circuit aluminum wires were used widely in houses during the mid 1960s and 1970s. According to the U.S. Consumer Product Safety Commission, problems due to expansion can cause overheating at connections between the wire and devices (switches and outlets) or at splices, which has resulted in fires. For further information on aluminum wiring contact the U.S. Consumer Product Safety Commission via the Internet at http://www.cpsc.gov/ . It is recommended that the electrical system be evaluated by a licensed electrician.

Credit
Comment
8.3.2 - Branch Wiring Circuits, Breakers & Fuses

Improper Wiring

Wiring should be ran to a junction box. Recommend evaluation by a licensed electrician

Credit
Comment
8.5.1 - GFCI & AFCI

No GFCI Protection Installed

No GFCI protection present in all locations. Recommend licensed electrician upgrade by installing ground fault receptacles in all locations.

Here is a link to read about how GFCI receptacles keep you safe. 

Credit
Comment
8.5.2 - GFCI & AFCI

Gfci failed
1st Floor Bathroom, Northwest wall under service panel

GFCI failed when tested. Recommend replacement 

Contractor Qualified Professional
Credit
Comment
8.6.1 - Smoke Detectors

Low Battery

Smoke detector failed to respond when tested. Recommend battery be replaced.

9 - Fireplace

IN NI NP D
9.1 Vents, Flues & Chimneys X
9.2 Lintels X
9.3 Damper Doors X
9.4 Cleanout Doors & Frames X
Type
N/A

I. The inspector shall inspect:

readily accessible and visible portions of the fireplaces and chimneys;

lintels above the fireplace openings;

damper doors by opening and closing them, if readily accessible and manually operable; and

cleanout doors and frames.

II. The inspector shall describe:

the type of fireplace.

III. The inspector shall report as in need of correction:

evidence of joint separation, damage or deterioration of the hearth, hearth extension or chambers;

manually operated dampers that did not open and close;

the lack of a smoke detector in the same room as the fireplace;

the lack of a carbon-monoxide detector in the same room as the fireplace; and

cleanouts not made of metal, pre-cast cement, or other non-combustible material.

IV. The inspector is not required to:

inspect the flue or vent system.

inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels.

determine the need for a chimney sweep.

operate gas fireplace inserts.

light pilot flames.

determine the appropriateness of any installation.

inspect automatic fuel-fed devices.

inspect combustion and/or make-up air devices.

inspect heat-distribution assists, whether gravity-controlled or fan-assisted.

ignite or extinguish fires.

determine the adequacy of drafts or draft characteristics.

move fireplace inserts, stoves or firebox contents.

perform a smoke test.

dismantle or remove any component.

perform a National Fire Protection Association (NFPA)-style inspection.

perform a Phase I fireplace and chimney inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies

10 - Attic, Insulation & Ventilation

IN NI NP D
10.1 Attic Insulation X X
10.2 Vapor Retarders (Crawlspace or Basement) X X
10.3 Ventilation X X
10.4 Exhaust Systems X X
Dryer Power Source
220 Electric
Dryer Vent
None Found
Flooring Insulation
None

No insulation found in the floor

Attic Insulation: R-value
0
Ventilation: Ventilation Type
Passive
Exhaust Systems: Exhaust Fans
Fan Only
General overview

No insulation in the floors and little in the attic. Recommend adding insulation to the attic and having a qualified contractor evaluate the floor

Attic Insulation: Insulation Type
Blown, Batt
Attic Insulation: R value

R value cannot be determined at this time due to lack of access to all areas in attic. The insulation that was observed is lacking and should be added to. 

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
10.1.1 - Attic Insulation

Improper Installation

Attic insulation was improperly installed. Recommend a qualified insulation contractor evaluate and correct. 

Credit
Comment
10.1.2 - Attic Insulation

Insufficient Insulation

Insulation depth was inadequate. Recommend a qualified attic insulation contractor install additional insulation.

Credit
Comment
10.2.1 - Vapor Retarders (Crawlspace or Basement)

Improper Installation

Vapor barrier is improperly installed. This can result in unwanted moisture. Recommend insulation contractor evaluate.
Credit
Comment
10.2.2 - Vapor Retarders (Crawlspace or Basement)

Vapor Barrier Damaged

Vapor barrier is damaged in one or more areas. Recommend insulation contractor repair or replace.
Credit
Comment
10.4.1 - Exhaust Systems

Bathroom Vents Into Attic

Bathroom fan vents into the attic, which can cause moisture and mold. Recommend a qualified attic contractor property install exhaust fan to terminate to the exterior.
Credit
Comment
10.4.2 - Exhaust Systems

Ducts loose

Ductwork in the attic is loose or disconnected. Recommend repair.

11 - Doors, Windows & Interior

IN NI NP D
11.1 Doors X X
11.2 Windows X
11.3 Floors X X
11.4 Walls X
11.5 Ceilings X
11.6 Steps, Stairways & Railings X X
11.7 Countertops & Cabinets X X
Windows: Window Manufacturer
JELD-WEN
Windows: Window Type
Sliders

Windows look to be in good condition

Floors: Floor Coverings
Carpet
Walls: Wall Material
Gypsum Board
Ceilings: Ceiling Material
Gypsum Board
Countertops & Cabinets: Cabinetry
Wood
Countertops & Cabinets: Countertop Material
Laminate
General overview

Doors and windows were in good shape minus some missing weather stripping. The vinyl windows did not appear to have failed seals but the aluminum windows in the back of the house should be monitored for leaks during the wet season

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
11.1.1 - Doors

Door Latch Alignment

Door latch and/or strike plate is out of alignment. Recommend a handyman repair.

Credit
Comment
11.1.2 - Doors

Poor Weather-stripping

At the time of the inspection, weather-stripping at interior doors was generally damaged or deteriorated. The Inspector recommends replacement/installation of effective weather-stripping components as necessary by a qualified contractor.

Credit
Comment
11.3.1 - Floors

Moderate Wear

Floors in the home exhibited moderate surface wear along major paths of travel. Recommend a qualified flooring contractor evaluate for possible re-finish. 

Credit
Comment
11.6.1 - Steps, Stairways & Railings

Handrail

The handrail is not installed correctly. 

Contractor Qualified Professional
Credit
Comment
11.7.1 - Countertops & Cabinets

Cabinets Damaged

Cabinets had visible water damage at time of inspection. Recommend a qualified cabinets contractor evaluate and repair.