Loading
Document Name
Sort Generated Document By
Header Text
Total Credit Requested
$ 0.00
Preview
Create
Viewing:
19
Maintenance item
3
Recommendation
4
Safety hazard

1 - Inspection Details

In Attendance
Client, Client's Agent
Occupancy
Furnished, Occupied
Style
Multi-level
Temperature (approximate)
34 Celsius (C)
Type of Building
Detached, Single Family
Weather Conditions
Humid

2 - Roof

IN NI NP D
2.1 Coverings X
2.2 Roof Drainage Systems X X
2.3 Flashings X
2.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Ground, Ladder, Roof, Drone
Roof Type/Style
Hip, Combination
Coverings: Material
Asphalt
Roof Drainage Systems: Gutter Material
Aluminum
Flashings: Material
Aluminum

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
2.2.1 - Roof Drainage Systems

Debris

Debris has accumulated in the gutters. Recommend cleaning to facilitate water flow.

Here is a DIY resource for cleaning your gutters. 

Credit
Comment
2.2.2 - Roof Drainage Systems

Downspouts Drain Near House

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 6 feet from the foundation. 

Here is a helpful DIY link and video on draining water flow away from your house. 

Credit
Comment
2.2.3 - Roof Drainage Systems

Downspouts Missing

Home was missing downspouts in one or more areas. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor install downspout extensions that drain at least 6 feet from the foundation. 

Credit
Comment
2.2.4 - Roof Drainage Systems

Gutter Loose

The gutter(s) is loose and needs to be re-fastened to fascia and pitched properly.

3 - Exterior

IN NI NP D
3.1 Siding, Flashing & Trim X
3.2 Exterior Doors X
3.3 Walkways, Patios & Driveways X X
3.4 Decks, Balconies, Porches & Steps X X
3.5 Eaves, Soffits & Fascia X
3.6 Vegetation, Grading, Drainage & Retaining Walls X X
Inspection Method
Attic Access, Visual
Siding, Flashing & Trim: Siding Material
Aluminum, Brick, Concrete, Masonry
Exterior Doors: Exterior Entry Door
Glass, Steel
Walkways, Patios & Driveways: Driveway Material
Asphalt
Decks, Balconies, Porches & Steps: Appurtenance
Deck, Deck with Steps
Decks, Balconies, Porches & Steps: Material
Wood

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
3.3.1 - Walkways, Patios & Driveways

Driveway Cracking - Minor

Minor cosmetic cracks observed, which may indicate movement in the soil. Recommend monitor and/or have concrete contractor patch/seal.

Credit
Comment
3.3.2 - Walkways, Patios & Driveways

Walkway Cracking - Minor

Minor cosmetic cracks observed. Recommend monitor and/or patch/seal.
Credit
Comment
3.4.1 - Decks, Balconies, Porches & Steps

Deck - Rotted Boards

One or more deck boards are showing signs of rot. Recommend a qualified deck contractor replace.
Credit
Comment
3.4.2 - Decks, Balconies, Porches & Steps

Railing Unsafe

There is an unsafe opening in the railing and also not properly fastened. The spacing on the rail should not exceed 4" and railing need to be secure. An opening greater than 4" is a serious safety hazard especially for children as their head or other body part can become trapped.

4 - Basement, Foundation, Crawlspace & Structure

IN NI NP D
4.1 Foundation X X
4.2 Basements & Crawlspaces/Cold Room X X
4.3 Floor Structure X
4.4 Wall Structure X
4.5 Ceiling Structure X
Inspection Method
Attic Access, Crawlspace Access, Visual, Cold Room
Foundation: Material
Concrete
Floor Structure: Basement/Crawlspace Floor
Concrete
Floor Structure: Material
Wood Beams
Floor Structure: Sub-floor
OSB

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
4.1.1 - Foundation

Foundation Cracks - Minor

Minor cracking was noted at the foundation. This is common as concrete ages and shrinkage surface cracks are normal. Recommend monitoring for more serious shifting/displacement. 

Here is an informational article on foundation cracks.

Credit
Comment
4.2.1 - Basements & Crawlspaces/Cold Room

Door Condition

Recommend cold room door to be replaced with a proper exterior rated door and weather stripping.

Credit
Comment
4.2.2 - Basements & Crawlspaces/Cold Room

Improper Ventilation

Spray foam found blocking ventilation in cold room. Recommend repair/replacement with a proper exhausting/venting method.

5 - Heating

IN NI NP D
5.1 Equipment X X
5.2 Normal Operating Controls X
5.3 Distribution Systems X X
5.4 Presence of Installed Heat Source in Each Room X
Equipment: Brand
Keeprite
Equipment: Energy Source
Gas
Equipment: Heat Type
Forced Air
Distribution Systems: Ductwork
Insulated

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
5.1.1 - Equipment

Annual Servicing/Cleaning

Furnace should be cleaned and serviced annually. Recommend a qualified HVAC contractor clean, service and certify furnace.

Here is a resource on the importance of furnace maintenance.

Credit
Comment
5.3.1 - Distribution Systems

Ducts Not Sealed

Air supply ducts were not properly sealed. Recommend a qualified HVAC contractor seal supply and return ducts for maximum efficiency.

6 - Cooling

IN NI NP D
6.1 Cooling Equipment X X
6.2 Normal Operating Controls X
6.3 Distribution System X
6.4 Presence of Installed Cooling Source in Each Room X
Cooling Equipment: Brand
Keeprite
Cooling Equipment: Energy Source/Type
Central Air Conditioner
Cooling Equipment: Location
Exterior South
Distribution System: Configuration
Central

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65 Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
6.1.1 - Cooling Equipment

Vegetation/Storage Too Close

Vegetation/Storage was too close to the compressor, which can limit heat dissipation and limit effectiveness. Recommend cutting back vegetation or removal of storage items to avoid overheating compressor.

7 - Plumbing

IN NI NP D
7.1 Main Water Shut-off Device X
7.2 Drain, Waste, & Vent Systems X X
7.3 Water Supply, Distribution Systems & Fixtures X X
7.4 Hot Water Systems, Controls, Flues & Vents X
7.5 Fuel Storage & Distribution Systems X
7.6 Sump Pump X
Filters
None
Water Source
Public
Main Water Shut-off Device: Location
Basement
Drain, Waste, & Vent Systems: Drain Size
1 1/2"
Drain, Waste, & Vent Systems: Material
ABS
Water Supply, Distribution Systems & Fixtures: Distribution Material
Copper, Pex
Water Supply, Distribution Systems & Fixtures: Water Supply Material
Copper, Pex
Hot Water Systems, Controls, Flues & Vents: Location
Basement
Hot Water Systems, Controls, Flues & Vents: Power Source/Type
Tankless
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
Gas Meter
Hot Water Systems, Controls, Flues & Vents: Manufacturer
Rheem

I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. 

Here is a nice maintenance guide from Lowe's to help. 

Sump Pump not present.

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
7.2.1 - Drain, Waste, & Vent Systems

Improper Connection

Severely corroded connection was observed at a drain, waste or vent pipe. Recommend a qualified plumber evaluate and repair.

Credit
Comment
7.3.1 - Water Supply, Distribution Systems & Fixtures

Improper Installation

Bathroom distribution pipes were installed in a sub-standard way (Missing shut-off valves). Recommend a qualified plumber evaluate and properly fit and install pipes.

Credit
Comment
7.3.2 - Water Supply, Distribution Systems & Fixtures

Toilet Leaking

Toilet is loose and/or leaking at the base. Recommend a qualified plumber evaluate and repair to prevent further water damage. 

8 - Electrical

IN NI NP D
8.1 Service Entrance Conductors X
8.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X
8.3 Branch Wiring Circuits, Breakers & Fuses X X
8.4 Lighting Fixtures, Switches & Receptacles X
8.5 GFCI & AFCI X X
8.6 Smoke Detectors X X
8.7 Carbon Monoxide Detectors X X
Service Entrance Conductors: Electrical Service Conductors
Below Ground
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Basement
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Capacity
200 AMP
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
ITE
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Branch Wiring Circuits, Breakers & Fuses: Branch Wire 15 and 20 AMP
Copper
Branch Wiring Circuits, Breakers & Fuses: Wiring Method
Romex

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
8.3.1 - Branch Wiring Circuits, Breakers & Fuses

Improper Wiring

Pool pump branch wire unsafe. Inspector found Non-rated (extension cord) buried underground running to pool pump. Also current outdoor receptacle is not GFCI which is required , stated at pool pump data plate. Recommend a Licenced Electrician to repair and replace immeadialty.

Credit
Comment
8.5.1 - GFCI & AFCI

No GFCI Protection Installed

No GFCI protection present in all locations. Recommend licensed electrician upgrade by installing ground fault receptacles in all locations.

Here is a link to read about how GFCI receptacles keep you safe. 

Credit
Comment
8.6.1 - Smoke Detectors

Inappropriate Location

Smoke detector effectiveness may be compromised due to location. Recommend relocating according to manufacturers instructions.
Credit
Comment
8.7.1 - Carbon Monoxide Detectors

Inappropriate Location

Carbon monoxide detector effectiveness may be compromised due to location. Recommend relocating according to manufacturers instructions.

9 - Fireplace

IN NI NP D
9.1 Vents, Flues & Chimneys X
9.2 Lintels X
9.3 Damper Doors X
9.4 Cleanout Doors & Frames X
Type
Gas
Gas Supply Shut Off
Gas supply was turned off, so operation of gas fireplaces could not be verified. Recommend having gas supply turned on and operation of fireplaces confirmed.

I. The inspector shall inspect:

readily accessible and visible portions of the fireplaces and chimneys;

lintels above the fireplace openings;

damper doors by opening and closing them, if readily accessible and manually operable; and

cleanout doors and frames.

II. The inspector shall describe:

the type of fireplace.

III. The inspector shall report as in need of correction:

evidence of joint separation, damage or deterioration of the hearth, hearth extension or chambers;

manually operated dampers that did not open and close;

the lack of a smoke detector in the same room as the fireplace;

the lack of a carbon-monoxide detector in the same room as the fireplace; and

cleanouts not made of metal, pre-cast cement, or other non-combustible material.

IV. The inspector is not required to:

inspect the flue or vent system.

inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels.

determine the need for a chimney sweep.

operate gas fireplace inserts.

light pilot flames.

determine the appropriateness of any installation.

inspect automatic fuel-fed devices.

inspect combustion and/or make-up air devices.

inspect heat-distribution assists, whether gravity-controlled or fan-assisted.

ignite or extinguish fires.

determine the adequacy of drafts or draft characteristics.

move fireplace inserts, stoves or firebox contents.

perform a smoke test.

dismantle or remove any component.

perform a National Fire Protection Association (NFPA)-style inspection.

perform a Phase I fireplace and chimney inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies

10 - Attic, Insulation & Ventilation

IN NI NP D
10.1 Attic Insulation X X
10.2 Vapor Retarders (Crawlspace or Basement) X
10.3 Ventilation X
10.4 Exhaust Systems X X
Dryer Power Source
220 Electric
Dryer Vent
Metal (Flex)
Flooring Insulation
None
Attic Insulation: Insulation Type
Batt, Blown
Attic Insulation: R-value
48
Ventilation: Ventilation Type
Passive, Soffit Vents
Exhaust Systems: Exhaust Fans
Fan Only

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
10.1.1 - Attic Insulation

Improper Installation

Attic insulation was improperly installed. Recommend a qualified insulation contractor evaluate and correct. 

Credit
Comment
10.4.1 - Exhaust Systems

Bathroom Vents Into Attic

Bathroom fan vents into the interiors of home, which can cause moisture and mold. Recommend a qualified attic contractor property install exhaust fan to terminate to the exterior.

Credit
Comment
10.4.2 - Exhaust Systems

Kitchen Vents Into Attic

Kitchen fan vents into the attic, which can cause moisture and mold. Recommend a qualified attic contractor property install exhaust fan to terminate to the exterior.

11 - Doors, Windows & Interior

IN NI NP D
11.1 Doors X
11.2 Windows X X
11.3 Floors X
11.4 Walls X
11.5 Ceilings X
11.6 Steps, Stairways & Railings X
Windows: Window Manufacturer
Unknown
Windows: Window Type
Casement, Single Pane, Sliders, Thermal
Floors: Floor Coverings
Hardwood, Laminate, Tile
Walls: Wall Material
Drywall
Ceilings: Ceiling Material
Gypsum Board

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiencies
Credit
Comment
11.2.1 - Windows

Water Damage

One or more windows appears to have general damage, but are operational. Recommend a window professional clean, lubricate & flashings as necessary.

Credit
Comment
11.2.2 - Windows

Failed Seal

Observed condensation between the window panes, which indicates a failed seal. Recommend qualified window contractor evaluate & replace.