Open area wells should have a guardrail to protect against Falls.
Glenford Blanc
PRO SPEX PROPERTY INSPECTION
SCOPE OF WORK
NOTICE: This inspection report is protected by copyright laws, any use or distribution by persons not party to the inspection contract for which this report is intended, is strictly prohibited. Refer to the inspection contract for terms of use.
A Pro Spex (here after referred to as Inspection Company) property Inspection is intended to be more than a report on the condition of the systems and components of the subject structure. It's an comprehensive documentation of, and an education in, the various systems and components. In addition to documenting conditions in specified systems and components, the information developed in the course of a Home Inspection is intended to help you in managing the home maintenance costs and preserving your home, by providing a basic understanding of how various systems work, and idea of age, documenting manufacturer and many other aspects.
Client understands that by accepting this property Inspection report, it is a limited and primarily visual, non-destructive, and non-technical examination (using normal operating controls where appropriate) of the applicable, safely accessible and readily accessible systems and components specified in the property Inspection Contract and Scope of Inspection and in the Inspection Report. Only the visible, safely accessible and readily accessible portions of the specified systems and components will be inspected. A building Inspection is intended to assist you in identifying these conditions. It is not a technical inspection, it is not a code compliance inspection.
Destructive testing and/or disassembly of materials of components, other than the removal of access covers intended to allow normal homeowner maintenance, is excluded. Barriers, carpet, walls, ceilings, tile, obstacles, personal goods or stored items are not removed or moved to gain access or to provide a clearer view.
Examination of certain systems and components and specific testing, evaluation, and remedial design work requires substantial additional time and the services of licensed contractors or individuals with necessarily narrow and highly specialized training. Such services may be provided by us as separate services but are not a part of this Inspection. These include but are not limited to the performance of engineering services, the inspection of swimming pools, spas, solar systems, irrigation, well and septic systems, or inspections for insects, pests, toxic substances and environmental hazards. If inspections or other services not included in the Home Inspection are desired, the Inspection Company, under a separate contract and for an additional fee, may provide some of these services or you may also seek any of these services independently.
This property Inspection is not a home warranty, guarantee, or insurance of any kind. By accepting the report, client understands that the report represents the conditions of the property at the time of the inspection and these conditions may change immediately following this inspection. It is not a substitute for a seller's disclosure statement or a pre-closing walk through. It does not replace insurance to protect against eventual deterioration of systems or components. Contact your real estate professional, insurance agent, or lender for information about this type of insurance.
This building inspection is not a code compliance inspection. While the inspector at his discretion may discuss issues that are related to the building code, the inspector does not have the authority to perform a code compliance inspection under the terms of this agreement. If client desires a technical code compliance inspection, for an additional fee, this can be provided separately and may involve the services of other professionals.
This building Inspection should not be seen as a termite or wood destroying organism (WDO) or wood destroying insect (WDI) inspections as required by some mortgage companies. When termite damage is visible at the time of inspection or when evidence of possible termite activity is noted, these areas are recorded for reference only, so that additional evaluation can be conducted during the WDO inspection by a licensed termite inspector. If prior repairs have been carried out, full confirmation and disclosure from the sellers is advised to ensure proper repair. Checking the historical data with the seller with regard to previous termite activity is always advised. Therefore, it's recommend that you have the property inspected by a licensed Termite Inspector prior to the close of escrow. Note: when requested thru this company, termite inspections are handled by a third party and arrangements are made as a courtesy only. Any agreements, warranties etc. related to the termite inspection, are the responsibility of that company.
This building Inspection does not include testing for mold or the measurement of indoor air quality. These services can be purchased separately. The presence of mold indicates abnormal moisture conditions. This inspection will attempt to identify the possible sources of moisture that may contribute to mold like conditions, but this is not a mold inspection. If you desire mold testing, contact our office for information about such services. In addition, you may want to consider the cleaning or sanitizing of air ducts and other concealed areas.
Note: Mold cannot exist without moisture. As a result any moisture whatsoever, no matter what its source, should be eliminated, or the potential for mold infestation will remain.
The Inspection Company is not a party to any contracts or other agreements relating to the transfer to the subject property between parties. Therefore, this Inspection Company cannot offer recommendations pertaining to the use of the information contained in the Inspection Report with regard to such contracts or agreements. All decisions pertaining to consulting with any representatives or other parties including, but not limited to, real estate agents, insurers, title companies, surveyors, mortgage lenders, and attorneys with regard to the use or to the timeliness of use of the information contained in the Inspection Report are solely your responsibility.
A Home Inspection is a "snapshot in time." A system or component performing normally during the inspection, does not assure that it will continue to do so. By accepting the services of this company, client understands that any system or component can fail catastrophically and without any warning or indication of impending failure. While the inspector may provide estimates, based on historical data, the inspector cannot predict any future Negative Conditions including but not limited to plumbing leaks, systems failures, or the remaining service life of any applicable system or component. The Inspection Company is not responsible for and will not repair any component which fails subsequent to this inspection or which is identified or described in this Inspection Report.
All repairs, corrective measures, or new work undertaken on any system or component should be performed only by qualified parties, licensed where applicable. It is recommended that only new or appropriate materials should be used. All work should be performed in a workmanlike manner and in accordance with all appropriate and applicable industry standards and governmental codes and regulations. Subsequent to completion and where appropriate and applicable, it is recommended that all such work be documented by work orders, invoices, or receipts from the individuals or companies which performed the work as well as by copies of all signed off building permits and lien releases from contractors and their employees, other workers, and material suppliers.
It is recommended that a copy of the appropriate portion or portions of the inspection report be provided to all qualified individuals retained to further evaluate and/or perform modifications or corrective measures to address Adverse Conditions documented in the Inspection Report. When work requiring a permit is performed without obtaining the proper permit and inspections, that work may be considered nonconforming and illegal by governmental building code, ordinance, and regulation agencies that are charged with the promulgation and enforcement of such codes, ordinances, and regulations. Nonconforming work may jeopardize the safety of persons occupying or entering the property. It may also adversely affect specific insurance coverage and the saleability of the property and may result in added costs in the form of additional fees and/or property taxes or other penalties.
The written observations and recommendations contained in this Inspection Report are based on the knowledge and experience of the inspector. You may receive different information from other inspectors, trades persons, insurance adjusters, private or public personnel, contractors, building and system warranty services personnel, or other parties whose interests are different from the Inspection Company's interests. If you receive information which differs from that expressed in this written Inspection Report, it is recommended that such information also be obtained in writing on the appropriate company or agency letterhead, bearing all applicable licensing numbers, and signed by the individual providing the information.
When other parties state that a component or an Adverse Condition designated Corrective Action is safe and/or adequate at the present time, without the need for any modifications or corrective measures, it is recommended that those parties be asked to put such statements in writing accompanied by a signed letter stating that no action is necessary and that the component or Adverse Condition identified in the Inspection Report is safe and adequate according to all industry standards and governmental regulations.
The following conditions and limitations apply to the use of ladders throughout this inspection: A ladder will be used only to aid in inspecting roof surfaces and reaching attic access openings. A ladder will be used only, when, in the judgment of the inspector, it is safe to do so. Under no circumstances will the use of ladder be considered when roof surfaces are not safely accessible and readily accessible with a ladder eighteen(18) feet or shorter in length and when attic access openings are not safely accessible and readily accessible with a ladder sixteen(16) feet or shorter in length.
This inspection is performed and this Inspection Report is prepared solely on behalf of and for the exclusive use of the person or organization named in this report and no third parties have any right to this inspection and Inspection Report. Its sole purpose is to provide you with both an education and a better understanding of some of the conditions which may exist at the subject property in order to assist you in planning for both immediate and regular maintenance of the specified systems and components. Therefore, it is recommended that the contents of this inspection and Inspection Report be kept strictly confidential and not be discussed with or shown to others, including but not limited to appraisers, insurance agents and adjusters, home warranty companies, and lenders, without careful consideration, whose interests are different from those of the Inspection Company and its Clients.
The Inspection Company will return (for a separate fee) to any property which the Company has previously inspected for the purpose of re-inspection to verify that any Adverse Conditions documented in the course of the original inspection have been modified or corrected, to inspect items that were inaccessible at time of inspection, or that remedial measures have been performed. Said re-inspection will be performed subject to the following:
The re-inspection will only address items identified in the original report as deficient or inaccessible.
The re-inspection will focus on attempting to determine whether or not the action taken meets the actions agreed to as provided for in a written contract or agreement.
The re-inspection will not address issues of adequacy of method chosen to repair or replace deficient system or component.
Client must provide a detailed description of the proposed work write, sufficient to assist the inspector in determining if the agreement has been fully satisfied. Client understands that if the work once completed, conceals any element of the agreed repair/replacement, the
Inspector can only report observations of the completed product and can make no judgment on the completeness of the work as it involves elements that are no longer visible (e.g. roof underlayment, plumbing repairs in finished ceilings etc.) If client desires a more detailed
Inspection of repair or replacement of any system or component, client has the option under separate fee agreement to retain the inspectors services to perform interim inspections as the work progresses.
The re-inspection is not a code compliance inspection. While we may at our discretion point out issues that may be inconsistent with the local building code, Pro Spex Inspectors are not authorized to report code compliance issues. Client has the option to contract for code compliance inspection under separate agreement, or contact the local authority for having jurisdiction, or retain the services of licensed professionals familiar with local code applicable to the situation at hand.
Like the home inspection, the re-inspection is limited to what can be seen without dismantling or removing components. All conditions of a full home inspection apply to a re-inspection.
For the reason stated above, it is recommended that all repairs, corrective measures, or new work undertaken on any system or component be performed only by qualified parties and that only new, appropriate or specified materials be used. Further, that all work be performed in a workmanlike manner and in accordance with all appropriate applicable industry standards and governmental codes, ordinances and regulations. Client is strongly advised the verify the competence of persons contracted to complete or correct any repairs undertaken in response to the comments of the home inspection.
Items that are present but no inspected. While the inspection company make every effort to inspect all aspects of the home. Site and environmental conditions may dictate that certain systems or components cannot be safely inspected (e.g. roof too high above ground or snow on roof). When such conditions exist, the inspector will note in the report why a system or component was not inspected. Note: the inspection report at that point is complete. If client desires said system or component to be inspected, separate arrangements will have to be made with the inspection company or other professional.
Comment Key or Definitions
This Report lists the systems and components inspected by this company. Items not found in this report are considered beyond the scope of this inspection, and should not be considered inspected at this time.
Please read the entire report for all items .
Notice: This report contains technical information that may not be readily understandable to the lay person. Therefore, a verbal consultation with the inspector is a mandatory part of this inspection report. If you choose not to consult with the inspector, this inspection company cannot be held liable for your understanding or misunderstanding of this report's contents. If you were not present during this inspection please call the office to arrange for your verbal consultation.
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Summary items that are marked as either Major (in the inspectors opinion, item may be costly, is in need of immediate attention or is a safety issue) or Minor (item is not determined to the be costly, is not in need of immediate attention or is not a safety issue). Be advised that opinions can vary. Note: This company classifies all electrical issues as major due to possible safety implications regardless of cost or ease of repair.
Note: The pictures and comments within this report, represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a SUITABLY LICENSED AND QUALIFIED CONTRACTOR. It is not the inspectors responsibility to determine the cause of the issues described herein or what corrective action should take place. When multiple instances of the same issue are observed, this report may not contain photos of all instances.
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Appears Serviceable (AS): The inspector did not observe conditions that would lead us to believe problems existed with this system or component. The item is capable of being used. Some serviceable items may, however, show wear and tear. Other conditions if applicable, will be noted in the body of the report.
Maintenance Recommended (MR): The inspector did not observe conditions that would lead us to believe problems existed with this system or component. The item is capable of being used. However the system or component does not appear to have been maintained according to the manufacturers recommendations. Lack of maintenance can reduce life expectancy and or performance. or , may adversely affect other systems and components.
Not Inspected (NI): The inspector did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP): This item, component or unit is not present in this home or building.
Repair or Replace (RR): The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement. Significantly deficient systems or components will be identified as: Not functional / unsafe / worn / near end of lifespan. When in the inspector's opinion, an item is "significantly deficient", the reason will be within the body of the report. NOTE: Opinions can vary, it is the customers responsibility to seek a 2nd opinion from a qualified contractor. The decision to Repair or Replace, lies solely with the party for whom this report is prepared.
Limited Inspection (LI): Could not perform a full inspection due to site conditions (weather, physical limitations, accessibility etc.) Inspector will state why inspection was limited. When conditions have changed, a re-inspection is recommended prior to expiration of clients contingency(additional fees apply).
Further Investigation Needed (FI): Not enough visible evidence to define a system or component as serviceable, or in need or repairs. Continued monitoring may be necessary before a conclusion can be reached, and a more in depth review is recommended.
Client advised to take these issues into consideration before the end of the contingency period. IT IS FURTHER RECOMMENDED THAT CLIENT CONDUCT A RE-INSPECTION BY OUR OFFICE WHEN CORRECTIONS ARE MADE. Note: If this inspection is covered by our service guarantee, failure to follow our recommendations could void the terms of the guarantee. If client was not present during the inspection, it is strongly recommended that client conduct a phone consultation with the inspector before their contingency expires.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
2.1 | WALL CLADDING FLASHING AND TRIM | X | ||||||
2.2 | DOORS (Exterior) | X | ||||||
2.3 | STOOPS, STEPS, AREAWAYS, AND APPLICABLE RAILINGS | X | ||||||
2.4 | DECKS, BALCONIES, PORCHES, PATIOS, PATIO COVERS AND APPLICABLE RAILINGS | X | ||||||
2.5 | VEGETATION, GRADING, DRAINAGE, (With respect to their effect on the condition of the building) | X | ||||||
2.6 | EAVES, SOFFITS AND FASCIAS | X | X | |||||
2.7 | DRIVEWAYS, WALKWAYS AND RETAINING WALLS | X | ||||||
2.8 | WINDOWS (EXTERIOR CONDITION) | X |
The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
Open area wells should have a guardrail to protect against Falls.
The boards on the underside of the deck are rotting. Likely because they are not made of pressure treated wood.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
3.1 | ROOF COVERINGS | X | ||||||
3.2 | FLASHINGS | X | ||||||
3.3 | SKYLIGHTS, AND ROOF PENETRATIONS | X | ||||||
3.4 | ROOF DRAINAGE SYSTEMS | X | X | |||||
3.5 | ROOF VENTS (RIDGE, GABLE, SOFFITS) | X | ||||||
3.6 | ROOF SHEATHING | X |
The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. The fasteners used to install roof shingles, in most instances are not visible and therefore are not inspected.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
Minor damage to the shingles on the rear slope to the right of the chimney.
Seal exposed nails to prevent nail corrosion and leaks.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
4.1 | ROOF COVERINGS | X | ||||||
4.2 | FLASHINGS | X | ||||||
4.3 | SKYLIGHTS, AND ROOF PENETRATIONS | X | ||||||
4.4 | ROOF DRAINAGE SYSTEMS | X | ||||||
4.5 | ROOF VENTS (RIDGE, GABLE, SOFFITS) | X | ||||||
4.6 | ROOF SHEATHING | X |
The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. The fasteners used to install roof shingles, in most instances are not visible and therefore are not inspected.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
The roof over the pool house was poorly installed. It is separating at the seam, and buckling. Water is getting below the membrane and will cause significant damage if not replaced.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
5.1 | GARAGE/CARPORT CEILINGS | X | ||||||
5.2 | GARAGE/CARPORT WALLS (INCLUDING FIREWALL SEPARATION) | X | ||||||
5.3 | GARAGE/CARPORT FLOOR | X | ||||||
5.4 | GARAGE OVERHEAD/ROLL UP DOOR (S) | X | ||||||
5.5 | OCCUPANT DOOR FROM GARAGE TO INSIDE HOME | X | ||||||
5.6 | GARAGE DOOR OPERATORS | X | ||||||
5.7 | GARAGE DOOR MOTION SENSOR | X | ||||||
5.8 | GARAGE ROOF (DETACHED STRUCTURES) | X | ||||||
5.9 | GARAGE DOOR TO EXTERIOR | X |
The home inspector shall observe: Walls, ceiling, and floor slab; access door to interior, roll up door and door operator. The home inspector shall: Operate the garage door operator only if it is functioning. Identify the door type and operator manufacturer. Report signs of abnormal operation, failure of the motion sensors if installed. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; is not required to manually lift doors, or operate any remote control devices or keypads.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
Garage ceiling cover with boards. Must be fire resistant.
In order to open or close 2 of the doors, the control must be depressed continuously.
The left garage door is missing the motion sensors. Motion sensors are important for child safety and should be installed as soon as possible.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
6.1 | CEILINGS | X | ||||||
6.2 | WALLS | X | ||||||
6.3 | FLOORS | X | ||||||
6.4 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | X | ||||||
6.5 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS | X | ||||||
6.6 | DOORS (REPRESENTATIVE NUMBER) | X | ||||||
6.7 | WINDOWS (Excluding Storm Windows) | X |
The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
Signs of prior repairs visible in the kitchen ceiling below the master bathroom. We did not detect the presence of moisture which suggests this is not a recent occurrence. Recommend you contact the owner for more information.
Signs of water stains are present on ceiling in the sunroom and family room. We did not detect the presence of moisture which suggests this is not a recent occurrence. The underlying cause is moisture or dampness related a possible roof leak and or a leak around the chimney flashing.
What stain at the base of the door on the interior floor.
Water stain visible on interior window trim to the upper right of the stone fireplace. Reason unknown.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
7.1 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | X | ||||||
7.2 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS | X | ||||||
7.3 | PLUMBING FIXTURES | X | ||||||
7.4 | HOT WATER SYSTEMS, CONTROLS, FLUES AND VENTS | X | ||||||
7.5 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) | X | ||||||
7.6 | SUMP PUMP | X | ||||||
7.7 | EXTERIOR HOSE BIBS | X | ||||||
7.8 | Ejector Pump (Whole house pumps only) | X | ||||||
7.9 | Fire Sprinkler System | X | ||||||
7.10 | OTHER | X |
The gas was off. Owner gave permission to turn on. Water heater pilot light out. When gas is restored to the water heater, recommend a followup inspection by this company (additional fees apply).
The subject property has a private well and septic system. These systems should be inspected by suitably licensed professionals. Unlike public systems, we do not inspect the plumbing system at full load in order to avoid running the well dry and damaging the pump. All comments made do not refer to these systems.
The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.
The water distribution system was inspected by running the water at all locations at the same time for approximately 15 minutes. This included all bathrooms, kitchen. while repeatedly flushing the toilets.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
Common causes of this are: Clogged Water filters, Blocked main water valves, Galvanized pipe corrosion, Semi-closed main valve, under sized main line among others. Consult a licensed plumber to further investigate the issue and correct as needed.
The shower head leaks where it connects to the stem.
Know what had the shower head reason unknown.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
8.1 | CRAWLSPACE | X | ||||||
8.2 | WALLS (Structural) | X | ||||||
8.3 | COLUMNS OR PIERS | X | ||||||
8.4 | FLOORS (Structural) | X | ||||||
8.5 | CEILINGS (structural) | X | ||||||
8.6 | ROOF STRUCTURE AND ATTIC | X |
The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
9.1 | SERVICE ENTRANCE CONDUCTORS | |||||||
9.2 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | X | X | |||||
9.3 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | X | ||||||
9.4 | CONNECTED DEVICES AND FIXTURES (Readily Accessible permanently installed devices, fixtures, switches, outlets etc.) | X | ||||||
9.5 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE | X | ||||||
9.6 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) | X | ||||||
9.7 | LOCATION OF MAIN AND DISTRIBUTION PANELS | X | ||||||
9.8 | SMOKE DETECTORS | X | ||||||
9.9 | CARBON MONOXIDE DETECTORS (Excludes Plugins) | X | ||||||
9.10 | OTHER ELECTRICAL ITEMS |
The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.
Note: The pictures and comments below represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
I recommend a licensed electrician inspect further to determine if these breakers are compatible and correct as needed.
Neutral (white) wires and ground (bare copper) wires cannot share the same lug (screw) in a panel unless they are on the same circuit. Doing so could create a shock hazard.
Several light fixtures are not working. Check light bulb before calling electrician.
All wet locations which include laundry rooms and bathrooms should have outlets protected by a GFCI.
For more on smoke alarms see CPSC Safety Alert
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
10.1 | DISHWASHER | X | ||||||
10.2 | RANGES and COOKTOPS | X | ||||||
10.3 | WALL OVENS | X | ||||||
10.4 | KITCHEN EXHAUST/RANGE HOOD | X | ||||||
10.5 | BUILT IN MICROWAVE | X | ||||||
10.6 | FOOD WASTE DISPOSER | X | ||||||
10.7 | TRASH COMPACTOR | X | ||||||
10.8 | Refrigerator (Limited Inspection) | X | ||||||
10.9 | Other Appliances (Limited Inspection) | X |
Refrigerator inspections are limited in scope to the outward physical appearance. This unit appears to operate normally however interior temperatures are not measured and its ability to keep items frozen for extended periods is not known. We do not test ice makers. For more information, we recommend consulting an appliance contractor.
The washer dryer appears to be operational. A short limited test did not reveal any concerns. (This check is performed as a courtesy only, and is only performed if the unit is empty) For a detailed inspection, consult a qualified appliance contractor.
NOTE: INSPECTION OF APPLIANCES ARE LIMITED IN SCOPE, ALL FEATURES ARE NOT INSPECTED, AS A RESULT SOME FEATURES MAY NOT FUNCTION. FOR A MORE EXTENSIVE INSPECTION, ADDITIONAL FEES APPLY AND MAY REQUIRE AN APPLIANCE CONTRACTOR.
The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle only; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances (e.g. Washer/Dryers); or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable. Inspection of refrigerators is limited to reporting its physical appearance only (refrigeration temperatures are not measured).
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
The interior is heavily corroded and the unit is jammed.
The freezer is not freezing and is making an unusual noise, reason unknown. Repairs to refrigerators of this type are often costly.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
11.1 | HEATING EQUIPMENT (Excluding Portable Systems) | X | ||||||
11.2 | HVAC SYSTEM OPERATING CONTROLS | X | ||||||
11.3 | AUTOMATIC SAFETY CONTROLS | X | ||||||
11.4 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | X | ||||||
11.5 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM | X | ||||||
11.6 | HEATING SYSTEM CHIMNEYS, FLUES AND VENTS | X | ||||||
11.7 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) | |||||||
11.8 | GAS/LP FIRELOGS AND FIREPLACES | |||||||
11.9 | COOLING AND AIR HANDLER EQUIPMENT (Excludes Window Units) | X | ||||||
11.10 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM | X | ||||||
11.11 | OTHER |
The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
12.1 | HEATING EQUIPMENT (Excluding Portable Systems) | X | ||||||
12.2 | HVAC SYSTEM OPERATING CONTROLS | X | ||||||
12.3 | AUTOMATIC SAFETY CONTROLS | X | ||||||
12.4 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | X | ||||||
12.5 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM | X | ||||||
12.6 | HEATING SYSTEM CHIMNEYS, FLUES AND VENTS | X | ||||||
12.7 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) | |||||||
12.8 | GAS/LP FIRELOGS AND FIREPLACES | |||||||
12.9 | COOLING AND AIR HANDLER EQUIPMENT (Excludes Window Units) | X | ||||||
12.10 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM | X | ||||||
12.11 | OTHER |
The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
13.1 | INSULATION IN ATTIC | X | ||||||
13.2 | INSULATION UNDER FLOOR SYSTEM | X | ||||||
13.3 | VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) | X | ||||||
13.4 | VENTILATION OF FOUNDATION and CRAWLSPACES AREAS | X | ||||||
13.5 | VENTING SYSTEMS (Kitchens, baths and laundry) | X | ||||||
13.6 | VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC) | X | ||||||
13.7 | OTHER | X |
The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.
Note: The pictures and comments represent a sampling of the issue found and are intended to help explain the area of concern. Other areas of similar concern could be present and are often found upon closer examination by a qualified contractor. We Strongly Recommend the entire summary be discussed with a qualified contractor. It is not the inspectors responsibility to determine the cause of the issues described herein.
AS | RR | MR | FI | NI | NP | NV | ||
---|---|---|---|---|---|---|---|---|
14.1 | Closed Property Condition | X |
Radon Test: It is the responsibility of the property owner and the purchaser(if applicable) or their respective agents, to ensure that closed home conditions are maintained 12 hours before and throughout the testing period. Failure to keep the home closed (except for normal entry and exit) will void the test and a retest will have to be performed (for an additional fee)
AS | RR | MR | FI | NI | NP | NV |
---|
This section contains additional (archived) information that may be useful at a later date.