10 Fairgrounds Drive
L0R 1C0
03/15/2018 11:00 am

23
Recommendation
2
Safety hazard

1 - Inspection Details

In Attendance
Client
Occupancy
Furnished, Occupied
Style
Multi-level
Type of Building
Detached
Weather Conditions
Clear

2 - Roof

IN NI NP O
2.1 Coverings X
2.2 Roof Drainage Systems X X
2.3 Flashings X X
2.4 Skylights, Chimneys & Other Roof Penetrations X X
Inspection Method
Ladder
Coverings: Material
Asphalt
Roof Drainage Systems: Gutter Material
Aluminum
Flashings: Material
Aluminum

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
2.2.1 - Roof Drainage Systems

Downspouts Drain Near House

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 4 to 6 feet from the foundation. 


Builder
CAD$
Credit
Comment
2.3.1 - Flashings

Missing or Loose/Separated

Flashings observed to be loose or separated, which can lead to water intrusion and/or mold. Recommend a qualified roofing contractor repair. 

Builder
CAD$
Credit
Comment
2.3.2 - Flashings

Missing Drip Edge (Warranty may be Voided)

Drip edge flashings were missing at time of inspection. Drip edge flashings provide protection against moisture intrusion and extending the life of the roof. Recommend a qualified roofing contractor evaluate and remedy. 


Important Infomation Regarding roof installation conditon


Click here Installation of drip edge flashing


Builder
CAD$
Credit
Comment
2.4.1 - Skylights, Chimneys & Other Roof Penetrations

Plumbling Stack Flashing Water Penetration

There are signs of possible water penetration at or near the plumbing stack flashing. If not properly installed, may be prone to leak and cause damage to the home. Have the flashing repaired or replaced.

Proper flashing around the plumbing stack is critical.

Builder

3 - Exterior

IN NI NP O
3.1 Siding, Flashing & Trim X X
3.2 Exterior Doors X
3.3 Walkways, Patios & Driveways X
3.4 Decks, Balconies, Porches & Steps X X
3.5 Eaves, Soffits & Fascia X
3.6 Vegetation, Grading, Drainage & Retaining Walls X
Inspection Method
Attic Access
Siding, Flashing & Trim: Siding Material
Brick, Concrete, Stucco
Exterior Doors: Exterior Entry Door
Glass, Steel
Walkways, Patios & Driveways: Driveway Material
Gravel

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
3.1.1 - Siding, Flashing & Trim

Flashing/Trim Improperly Installed

Flashing & trim pieces were improperly installed, which could result in moisture intrusion and damaging leaks. Recommend a qualified siding contractor evaluate and repair.

Builder
CAD$
Credit
Comment
3.4.1 - Decks, Balconies, Porches & Steps

Stairs - Missing

Slider door entrance section at the rear of the home without exterior stairs. Recommend qualified concrete/builder to evaluate & repair.

Builder

4 - Basement, Foundation, Crawlspace & Structure

IN NI NP O
4.1 Foundation X
4.2 Basements & Crawlspaces X
4.3 Floor Structure X X
4.4 Wall Structure X X
4.5 Ceiling Structure X
Inspection Method
Visual
Foundation: Material
Concrete
Floor Structure: Basement/Crawlspace Floor
Concrete
Floor Structure: Material
Wood Beams
Floor Structure: Sub-floor
OSB

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
4.3.1 - Floor Structure

Basement Staircase Framing Repair

Basement staircase landing framing stucture poor workmanship. This can cause damage to the structural integrity of the home. Recommend a qualified professional to repair or replace.



Structural Engineer
CAD$
Credit
Comment
4.3.2 - Floor Structure

Joists Need Repair

Improper joist spacing recommend blocking compression for all basement floor joist spans, to prevent joists from overturning or twisting. These joists have nothing to stop them from moving or even, in worst case, all rolling to the right, (or left) and collapsing completely. When it gets to that, the building can fail. Also one or more floor joists require bridging installation repair or replacement immediately where joists are damaged or improperly installed. This can cause damage to the structural integrity of the home. Recommend a qualified structural engineer evaluate and advise on how to correct.


Floor Joist notching is insufficient, the maximum depth of a joist notch at the end of a joist can't exceed one-quarter of the joist depth. Maximum notch depth in the outer third of a joist is one-sixth of the joist depth. Recommend to limit the length of notches to one-third of the joist depth. No notching in the middle third of any joists.



Structural Engineer
CAD$
Credit
Comment
4.4.1 - Wall Structure

Evidence of Structural Damage

Evidence of structural damage was found in the wall structure. Recommend a structural engineer evaluate and advise on how to repair. 

Structural Engineer

5 - Heating

IN NI NP O
5.1 Equipment X
5.2 Normal Operating Controls X
5.3 Distribution Systems X
5.4 Vents, Flues & Chimneys X X
5.5 Presence of Installed Heat Source in Each Room X
Equipment: Brand
Keep Rite
Equipment: Energy Source
Gas
Equipment: Heat Type
Forced Air
Distribution Systems: Ductwork
Non-insulated

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
5.4.1 - Vents, Flues & Chimneys

Exhuasting Flue Improperly Installed

Furnace & Hot Water Tank exhaust flues are improperly installed. Recommend a qualified HVAC contractor evaluate and repair.



Builder

6 - Plumbing

IN NI NP O
6.1 Main Water Shut-off Device X
6.2 Drain, Waste, & Vent Systems X
6.3 Water Supply, Distribution Systems & Fixtures X
6.4 Hot Water Systems, Controls, Flues & Vents X X
6.5 Fuel Storage & Distribution Systems X
6.6 Sump Pump X X
Water Source
Public
Main Water Shut-off Device: Location
Basement
Drain, Waste, & Vent Systems: Material
ABS
Water Supply, Distribution Systems & Fixtures: Distribution Material
Copper, Pex
Water Supply, Distribution Systems & Fixtures: Water Supply Material
Copper, Pex
Hot Water Systems, Controls, Flues & Vents: Location
Basement
Hot Water Systems, Controls, Flues & Vents: Power Source/Type
Gas
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
Gas Meter
Sump Pump: Location
Basement

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
6.4.1 - Hot Water Systems, Controls, Flues & Vents

Improper Installation

Water heater is improperly installed. PEX piping shall not be installed within the first 18" of piping connecting to a water heater. Recommend qualified plumber evaluate and repair/relocate.


Builder
CAD$
Credit
Comment
6.6.1 - Sump Pump

Improper Installation

Sump pump has sub-standard installation. Recommend a qualified plumber evaluate and properly install.

Builder

7 - Electrical

IN NI NP O
7.1 Service Entrance Conductors X X
7.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X X
7.3 Branch Wiring Circuits, Breakers & Fuses X
7.4 Lighting Fixtures, Switches & Receptacles X X
7.5 Smoke Detectors X
7.6 Carbon Monoxide Detectors X
Service Entrance Conductors: Electrical Service Conductors
Below Ground
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Basement
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
Square D
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Branch Wiring Circuits, Breakers & Fuses: Branch Wire 15 and 20 AMP
Copper
Branch Wiring Circuits, Breakers & Fuses: Wiring Method
Romex

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
7.1.1 - Service Entrance Conductors

Water Intrusion

There is possible water intrusion and the meter / service entrance. Moisture can deteriorate the electrical equipment. Recommend that a licenced electrician repair / replace as needed.

Builder
CAD$
Credit
Comment
7.2.1 - Main & Subpanels, Service & Grounding, Main Overcurrent Device

Panel Damaged

Main Panel door lock mechanism broken - this is safety issue. Recommend repair or replacement of the main panel access door.

Builder
CAD$
Credit
Comment
7.4.1 - Lighting Fixtures, Switches & Receptacles

Improperly wired receptacles

One or more receptacles are not working and/or are ungrounded. To eliminate safety hazards, all receptacles in kitchen, bathrooms, garage & exterior should be wired correctly and grounded. Also recommend builder or licenced electrical contractor to repair or replace receptacles. Inspector noted that electrical panel has not been ESA approved and or Builder has not provided information on final electrical inspections. Recommend electrical systems have the necessary inspection completed.

Electrical Contractor

8 - Attic, Insulation & Ventilation

IN NI NP O
8.1 Attic Insulation X
8.2 Ventilation X
8.3 Exhaust Systems X
Dryer Power Source
220 Electric
Dryer Vent
Metal (Flex)
Attic Insulation: Insulation Type
Blown
Ventilation: Ventilation Type
Ridge Vents
Exhaust Systems: Exhaust Fans
Fan Only

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations

9 - Doors, Windows & Interior

IN NI NP O
9.1 Doors X X
9.2 Windows X X
9.3 Floors X
9.4 Walls X X
9.5 Ceilings X
9.6 Steps, Stairways & Railings X X
9.7 Countertops & Cabinets X X
Windows: Window Type
Casement, Sliders
Floors: Floor Coverings
Carpet, Hardwood, Tile
Walls: Wall Material
Drywall
Ceilings: Ceiling Material
Gypsum Board
Countertops & Cabinets: Cabinetry
Laminate
Countertops & Cabinets: Countertop Material
Granite, Marble, Quartz

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
9.2.1 - Windows

Damaged

One or more windows appears to have general damage, but are operational. Recommend a window professional clean, lubricate & adjust as necessary.

Builder
CAD$
Credit
Comment
9.2.2 - Windows

Improper Window Framing Installation

One or more interior window framings appear to be cracking/splitting also not properly sealed due to substandard installation. Recommend qualified professional to repair or replace.

Builder
CAD$
Credit
Comment
9.2.3 - Windows

Missing Screen

One or more windows missing screen. Recommend replacement.

Builder
CAD$
Credit
Comment
9.2.4 - Windows

Basement Slider Window

Basement slider window's need repair with a proper window flashing/drip edge or exterior type sealant. Recommend window well and proper drainage installation by a qualified professional or builder. Also for all current installed window wells, recommend repair or replace at the foundation walls. Suggest scope of work to be complete before landscape grading.

Builder
CAD$
Credit
Comment
9.4.1 - Walls

Major Wall & Corner Cracks

Cracking visible at the corners of doors and windows. Indicate soil movement, which is a structural concern and should be evaluated by a structural engineer.

Builder
CAD$
Credit
Comment
9.4.2 - Walls

Minor Wall & Corner Cracks

Minor cracks at the corners of doors and windows in walls. Appeared to be the result of settling. Some settling is not unusual in a home of this age and these cracks are not a structural concern.

Builder
CAD$
Credit
Comment
9.4.3 - Walls

Nail Pops

Protruding nail heads visible at the time of the inspection appeared to be the result of settlement. Nails should be repaired or replaced, drywall re-fastened and the drywall finished to match the existing wall surfaces. All work should be performed by a qualified drywall or painting contractor.

Builder
CAD$
Credit
Comment
9.7.1 - Countertops & Cabinets

Cabinets Damaged

Cabinets had visible damage at time of inspection. Recommend a qualified cabinets contractor evaluate and repair. 

Builder
CAD$
Credit
Comment
9.7.2 - Countertops & Cabinets

Poor/Missing Caulk

Bathroom countertop was missing sufficient caulk/sealant at the wall. This can lead to water damage. Recommend adding sealant at sides and corners where counters touch walls.


Builder

10 - Garage

IN NI NP O
10.1 Floor X
10.2 Walls & Firewalls X
10.3 Garage Door X X
10.4 Garage Door Opener X
10.5 Occupant Door (From garage to inside of home) X
Garage Door: Material
Insulated
Garage Door: Type
Automatic
Garage Limitaions

Inspector not able to complete full garage inspection due to storage and sersonal belongings.

Floor not inspected.

Walls & Firewalls not inspected.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • O = Observations
CAD$
Credit
Comment
10.3.1 - Garage Door

Panel Damage

Garage door panel is damaged and may need repair/replacement. Recommend a qualified garage door contractor evaluate. 

Builder