Viewing:

1234 Demonstration Report 1
Bonners Ferry, ID 83805
11/17/2021 8:00 am

41
Recommendation
19
Safety hazard

1 - Inspection Details

In Attendance
Client's Agent, Client
Occupancy
Occupied
Style
Log House, Log on Stick
Temperature (approximate)
36 Fahrenheit (F)
Type of Building
Detached, Single Family
Weather Conditions
Cloudy, Rain

2 - Roof

IN NI NP D
2.1 Coverings X
2.2 Roof Drainage Systems X X
2.3 Flashings X
2.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Binoculars, Ground, UAV
Roof Type/Style
Gable, Gable With Dormers
Coverings: Material
Metal
Roof Drainage Systems: Gutter Material
Seamless Aluminum
Flashings: Material
Metal
General Summary
Roof

Overall, the roof covering was found to be in good condition, but there were minor issues observed.

There are some places where screws are loose, or missing.

There are several places on the snow blocks that are damaged.

We recommend having the roof reviewed and repaired by a professional.

Coverings: Roof Overview
Roof General

These photos show an overview of the whole roof of the residence.

Skylights, Chimneys & Other Roof Penetrations: Roof Penetrations OK
Roof

Roof pipe penetrations were observed to be in good condition.

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
2.1.1 - Coverings

Loose and Missing Screws/Nails
Roof

LOOSE SCREWS/NAILS

Observed one or more under-driven nails/fasteners. Recommend a qualified roofing contractor evaluate and repair. 


MISSING SCREWS NAILS

There are small holes in the roof where screws are missing.

Roofing Professional
$
Credit
Comment
2.1.2 - Coverings

Snow Breaks - Damaged
Roof

There are several places where the snow blocks are damaged. Some even have screws missing and/or popped.

Recommend a qualified roofing professional evaluate and repair. 

Roofing Professional
$
Credit
Comment
2.2.1 - Roof Drainage Systems

Debris
North

Debris has accumulated in the gutters on the north side of the house. We recommend cleaning to facilitate water flow.

Gutter Contractor
$
Credit
Comment
2.2.2 - Roof Drainage Systems

Downspouts Drain Near House
North West, South East Gutter

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 3 feet from the foundation. 


Gutter Contractor
$
Credit
Comment
2.2.3 - Roof Drainage Systems

Gutter Damaged
Gutters On All Sides

The runoff gutters were damaged in several places. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor evaluate and repair. 

Gutter Contractor
$
Credit
Comment
2.2.4 - Roof Drainage Systems

Gutter Leakage

Gutters were observed to be leaking in one or more areas. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor evaluate and repair gutters to proper functionality. 

Roofing Professional
$
Credit
Comment
2.3.1 - Flashings

Roof Flashings
Roof

Roof flashing by the gable is detaching from the roof. Evaluation and repair recommended by a qualified professional.

Qualified Professional

3 - Exterior

IN NI NP D
3.1 Foundation X
3.2 Siding, Flashing & Trim X
3.3 Exterior Doors X
3.4 Walkways, Patios & Driveways X
3.5 Decks, Balconies, Porches & Steps X X
3.6 Eaves, Soffits & Fascia X
3.7 Vegetation, Grading, Drainage & Retaining Walls X X
3.8 Electrical / Telecom X
Inspection Method
Visual, Infrared
Foundation: Material
Concrete
Siding, Flashing & Trim: Siding Material
Wood, Log Siding
Siding, Flashing & Trim: Siding Style
Log
Exterior Doors: Exterior Entry Door
Wood
Walkways, Patios & Driveways: Driveway Material
Concrete, Gravel
Decks, Balconies, Porches & Steps: Appurtenance
Front Porch, Deck with Steps
Decks, Balconies, Porches & Steps: Material
Composite
Foundation: Foundation

The foundation is in overall good condition.

The protective wrapping is torn on east side of the house.

Siding, Flashing & Trim: Log Siding Overview

The log siding and chinking is overall in good condition. 

Southside, westside, eastside of the house shows signs of weathering. 

Resealing the wood recommended.

Siding, Flashing & Trim: Flashing, Trim Overview

Flashings are in overall good condition. Trim around some windows show signs of weathering. Resealing recommended.

 

Exterior Doors: Exterior doors

The exterior doors appear to be in good condition. The storm doors are installed on all exterior doors for extra protection.


Eaves, Soffits & Fascia: Soffits, Fascia Overview

The fascia boards are covered with flashing.
The soffits are in overall good condition.

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
3.2.1 - Siding, Flashing & Trim

Ground Clearance
Eastside

Inadequate clearance between siding and ground.   Recommend a minimum ground clearance between bottom of siding and ground of 4". Siding in contact with the ground or soil is a serious concern because that condition can provide direct access for wood destroying insects.

Siding Contractor
$
Credit
Comment
3.2.2 - Siding, Flashing & Trim

Weathered Siding

Southside, westside, eastside of the house siding shows signs of weathering. Recommended resealing wood siding.

Some siding is showing early signs of rot.


Qualified Professional
$
Credit
Comment
3.2.3 - Siding, Flashing & Trim

Hole in the Siding
Southwest Side

There is a hole on the southwest side of the house. Moisture and animal entrance to the house. Repair recommended.

Qualified Professional
$
Credit
Comment
3.4.1 - Walkways, Patios & Driveways

Driveway Cracking - Minor
Driveway

Minor cracks observed, which may indicate movement in the soil. 

Recommended  concrete contractor patch/seal.

Concrete Contractor
$
Credit
Comment
3.4.2 - Walkways, Patios & Driveways

Walkway Cracking - Minor

The concrete on the left side of the porch has a crack/split. 

Moisture is draining to and collecting in this crack, when it rains.

This can cause moisture to penetrate underneath. If enough moisture collects and freezes, it can cause the concrete to swell and crack even more.

Recommend monitor and/or patch/seal.

Additionally, the gutter on the ground is leaking moisture. that moisture is draining under the porch.

Concrete Contractor
$
Credit
Comment
3.4.3 - Walkways, Patios & Driveways

Basement Concrete
Basement Concrete

Basement concrete has signs of minor cracking. 

The concrete has a noticeable hump. This hump could be caused by frost heave, or water.

Evaluation and repair by a qualified contractor recommended. 

Qualified Professional
$
Credit
Comment
3.5.1 - Decks, Balconies, Porches & Steps

Leaking Porch
North West Porch Overhang

The North West area of the porch overhang was observed to be leaking, when it rains.

The moisture is causing damage to the ceiling / overhang of the porch. We were unable to gauge the extent of the damage.

We recommend a roofing contractor inspect and remediate this issue.

Roofing Professional
$
Credit
Comment
3.5.2 - Decks, Balconies, Porches & Steps

Porch Posts Rotted Throughout
Front Porch

The front porch posts are rotted out. 

Repair recommended.

Qualified Professional
$
Credit
Comment
3.5.3 - Decks, Balconies, Porches & Steps

Porch Floor Boards
Front Porch

The boards on the covered porch are made from 1st generation Trex material that is unsafe to use. 

Replacement strongly recommended. 

Deck Contractor
$
Credit
Comment
3.5.4 - Decks, Balconies, Porches & Steps

Porch Steps
North West Porch Steps

The steps on the front porch have warped Trex boards, some boards are detaching from steps. 

Repair recommended.


Qualified Professional
$
Credit
Comment
3.5.5 - Decks, Balconies, Porches & Steps

Porch Lattice
Front Porch

The front porch lattice is broken in some spots, and is detaching from the porch framing. 

Repair recommended.

Qualified Professional
$
Credit
Comment
3.5.6 - Decks, Balconies, Porches & Steps

Entire Deck is a Safety Hazard and Needs Replaced
South Deck

The entire deck needs to be replaced. It is a major safety hazard.

1: The South West Post that is supposed to be holding up the entire corner of the deck, is missing. It appears to be built as a possible cantilever. However, it is insufficient.

2: The railing and support posts are rotted out so badly, that you can break them into pieces with your hand.

3: The railing is not connected properly at the corners. If someone leans against the railing, it can easily break away due to rot, and/or being disconnected.

4: The flooring on the deck is made with 1st generation Trex. This material is unsafe, and should be replaced throughout with a different material. The current deck floor boards are not properly fastened. There are many loose and unfastened boards. A person could easily fall through the deck floor.

Deck Contractor
$
Credit
Comment
3.6.1 - Eaves, Soffits & Fascia

Front Porch Soffits
Front Porch

The front porch soffits board is loose and creating gap between the boards. Possibility for moisture and insect intrusion. 

Repair recommended.

Qualified Professional
$
Credit
Comment
3.7.1 - Vegetation, Grading, Drainage & Retaining Walls

Water Erosion, Mud Slide
Southwest Side

WEST SIDE

Water and earth erosion was discovered under the deck ramp close to the house foundation. It creates a mud slide that can enter the house which can also create mold problems.

We observed numerous old sandbags that appeared to be used in an attempt to hold back mud and/or water, due to erosion.

Mud has penetrated the sandbag area, and has settled onto the porch concrete floor.

Additionally, the deck entrance ramp has structural failures underneath. There is a single brick holding it up. (see photo)

It is recommended to remediate the erosion issues.

EAST SIDE

Erosion was also discovered on the east side of the house. The earth is slowly moving up against the house. 

This needs to be remediated.

Qualified Professional
$
Credit
Comment
3.8.1 - Electrical / Telecom

Outside Outlet is Not Working
Southside Deck

One outside outlet is not working. Repair recommended.

Qualified Professional
$
Credit
Comment
3.8.2 - Electrical / Telecom

Telecom - Exposed Wire
North East Exterior Wall

We observed a wire bundle protruding from the telco box.

The sheathing on the wire bundle was split open and exposing the wires.

It appears that there is ROMEX styles electrical wiring that is being used as a ground.

The white wire was dangling.

The black wire ran to the grounding rod. However, the black wire was not attached to the grounding rod. The wire was shoved into the dirt.

Qualified Professional

4 - Basement

IN NI NP D
4.1 Windows X
4.2 Lighting Fixtures, Switches & Receptacles X
4.3 Heating Equipment X
4.4 Smoke Detectors X
4.5 Carbon Monoxide Detector X
Heating Equipment: Energy Source
Propane
Heating Equipment: Heat Type
Propane Stove
Heating Equipment: Basement Stove
Basement

Propane stove was in working condition at the time of the inspection.

Basement Overview
Basement

The basement is in overall good condition.

Ceiling: Drywall ceiling is in overall good condition. No water leaks or stains were detected at the time of the inspection.
Floor: Tile floor is in overall good condition. No cracks or missing grout was detected at the time of the inspection.
Walls: Walls (tongue and groove, and drywall) in basement are in overall good condition.
Windows: All windows in basement area were in working condition at the time of the inspection. One window has damage.
Doors: Doors in basement are are overall in good condition.
Electric Outlets: All electric outlets were in working condition at the time of the inspection.
Light Fixtures: Some ceiling light fixtures/fans were in working condition at the time of the inspection. Light fixtures by basement stairs were not working.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
4.1.1 - Windows

Basement Window Damage
Basement

One window in the basement has broken glass, and damaged screen. 

Repair recommended.

Window Repair and Installation Contractor
$
Credit
Comment
4.2.1 - Lighting Fixtures, Switches & Receptacles

Light Fixture is Not Working
Basement

Some light fixtures in the basement are not working. There is insufficient light at the basement stairs area. 

Repair recommended.

Electrical Contractor
$
Credit
Comment
4.3.1 - Heating Equipment

Stove Propane Supply Pipe
Basement

Propane supply pipe is detached from the wall. 

Repair recommended by a qualify professional.

Qualified Professional
$
Credit
Comment
4.4.1 - Smoke Detectors

Smoke Detectors are Missing

Smoke detector is missing.
Smoke alarms provide life-saving warnings to allow people to get out of the house before they are trapped by fire or smoke.

Electrical Contractor

5 - Living Room

IN NI NP D
5.1 Windows X
5.2 Heating Equipment X
5.3 Smoke Detectors X
5.4 Carbon Monoxide Detector X
5.5 Other X
Heating Equipment: Energy Source
Propane
Heating Equipment: Heat Type
Propane Stove
Living Room Conditon
Living Room

Living room is in overall good condition.

Ceiling: Tongue and groove ceiling is in overall good condition. No water leaks or stains were detected at the time of the inspection.
Floor: Wood floor is in overall good condition.
Walls: Walls in living room are in overall good condition.
Windows: All windows in living room were in working condition at the time of the inspection.
Doors: Door in living room is overall in good condition. No leaks, broken glass, no weather stripping damage.
Electric Outlets: All electric outlets were in working condition at the time of the inspection.
Light Fixtures: Ceiling fan, wall light fixtures were in working condition at the time of the inspection.


Heating Equipment: Propane Stove Not Inspected
Living Room

Propane stove was not inspected due to being turned off.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
5.1.1 - Windows

Hallway Window
Hallway

Window sill has signs of minor water damage/stains.

Qualified Professional
$
Credit
Comment
5.3.1 - Smoke Detectors

Smoke Detectors are Missing
Living Room

Smoke detector is missing.
Smoke alarms provide life-saving warnings to allow people to get out of the house before they are trapped by fire or smoke.

Electrical Contractor
$
Credit
Comment
5.4.1 - Carbon Monoxide Detector

Carbon Monoxide Detector is Missing
Living Room

Carbon monoxide detector is missing.
Because CO is an odorless, tasteless, and colorless gas, its presence indoors can be detected only through the use of CO detectors. These detectors warn people about the potential for CO poisoning in the same way that smoke detectors warn about the potential for acute fire-related smoke exposure.

Qualified Professional

6 - Kitchen

IN NI NP D
6.1 Dishwasher X
6.2 Refrigerator X
6.3 Range/Oven/Cooktop X
6.4 Garbage Disposal X
6.5 Miscellaneous Kitchen X
6.6 Windows X
6.7 GFCI & AFCI X
6.8 Smoke Detectors X
6.9 Carbon Monoxide Detector X
Dishwasher: Brand
Maytag
Refrigerator: Brand
Kenmore
Range/Oven/Cooktop: Range/Oven Energy Source
Gas
Range/Oven/Cooktop: Range/Oven Brand
Samsung
Range/Oven/Cooktop: Exhaust Hood Type
None
Range/Oven/Cooktop: Stove
Kitchen

All burners were in working condition at the time of the inspection.

Dishwasher: Dishwasher OK
Kitchen

Dishwasher was in working condition at the time of the inspection.

Refrigerator: Refrigerator OK
Kitchen

Refrigerator was in working condition at the time of the inspection.

Kitchen Overview
Kitchen

Kitchen is in overall good condition.

Ceiling: Tongue and groove ceiling was in overall good condition. There were no signs of water damage at the time of the inspection.

Floor: Wood floor in the kitchen was in overall good condition, and there were no signs of damage at the time of the inspection.

Walls: Walls are in overall good condition.

Cabinets: All cabinets were in working condition, and no damage was detected at the time of the inspection.

Light Fixtures: All light fixtures were in working condition at the time of the inspection.

Plumbing: Plumbing is properly installed with p-trap, and individual shut off valves are installed under the sinks. There was no leak detected at the time of the inspection.



Garbage Disposal: Garbage Disposal OK
Kitchen

Kitchen garbage disposal was in good working condition at the time of the inspection.

Range/Oven/Cooktop: Oven Not Inspected
Kitchen

Oven was not inspected due to cookware stored in the oven.

Miscellaneous Kitchen: Kitchen Water Heater Not Inspected
Under Main Kitchen Sink

Water heater under the sink was turned off so it could not be inspected.

10.1 The inspector shall inspect: F. installed ovens, ranges, surface cooking appliances, microwave ovens, dishwashing machines, and food waste grinders by using normal operating controls to activate the primary function. 10.2 The inspector is NOT required to inspect: G. installed and free-standing kitchen and laundry appliances not listed in Section 10.1.F. H. appliance thermostats including their calibration, adequacy of heating elements, self cleaning oven cycles, indicator lights, door seals, timers, clocks, timed features, and other specialized features of the appliance. I. operate, or con rm the operation of every control and feature of an inspected appliance.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
6.6.1 - Windows

Kitchen Window
Kitchen

Kitchen window by refrigerator does not close properly. This results in not be able to latch the window in that corner, and heat leak.
Also, window seal has signs of minor water damage/stains.

Qualified Professional
$
Credit
Comment
6.7.1 - GFCI & AFCI

GFCI is Missing
Kitchen Island

GFCI is not installed at the island kitchen sink. GFCI needs to be installed within 6 feet from water source.

Qualified Professional
$
Credit
Comment
6.8.1 - Smoke Detectors

Smoke Detectors are Missing
Kitchen

Smoke detector is missing.
Smoke alarms provide life-saving warnings to allow people to get out of the house before they are trapped by fire or smoke.

Electrical Contractor
$
Credit
Comment
6.9.1 - Carbon Monoxide Detector

Carbon Monoxide Detector is Missing
Kitchen

Carbon monoxide detector is missing.
Because CO is an odorless, tasteless, and colorless gas, its presence indoors can be detected only through the use of CO detectors. These detectors warn people about the potential for CO poisoning in the same way that smoke detectors warn about the potential for acute fire-related smoke exposure.

Qualified Professional

7 - Master Bedroom

IN NI NP D
7.1 General X
7.2 Smoke Detectors X
7.3 Carbon Monoxide Detectors X
General: Master Bedroom Overview
Master Bedroom

Master bedroom is in overall good condition.

Ceiling: Tongue and groove ceiling is in overall good condition.
Floor: Wood floor is in overall good condition.
Walls: Walls in master bedroom are in overall good condition.
Windows: All windows in master bedroom were in working condition at the time of the inspection.
Doors: Door in master bedroom is overall in good condition.
Electric Outlets: All electric outlets were in working condition at the time of the inspection.
Light Fixtures: Ceiling light fixture was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
7.2.1 - Smoke Detectors

Smoke Detectors are Missing
Master Bedroom

Smoke detector is missing.
Smoke alarms provide life-saving warnings to allow people to get out of the house before they are trapped by fire or smoke.

Electrical Contractor
$
Credit
Comment
7.3.1 - Carbon Monoxide Detectors

Carbon Monoxide Detector is Missing
Master Bedroom

Carbon monoxide detector is missing.
Because CO is an odorless, tasteless, and colorless gas, its presence indoors can be detected only through the use of CO detectors. These detectors warn people about the potential for CO poisoning in the same way that smoke detectors warn about the potential for acute fire-related smoke exposure.

Qualified Professional

8 - Main Level Bedroom 2

IN NI NP D
8.1 General X
8.2 Smoke Detectors X
8.3 Carbon Monoxide Detectors X
General: Main Level Bedroom 2
Main Level

Th bedroom is in overall good condition.

Ceiling: Tongue and groove ceiling is in overall good condition.
Floor: The wood floor is in overall good condition.
Walls: The walls in main floor bedroom are in overall good condition.
Windows: All windows in main floor bedroom were in working condition at the time of the inspection.
Doors: The door in main floor bedroom is overall in good condition. The door has minor scratches.
Electric Outlets: All electric outlets were in working condition at the time of the inspection.
Light Fixtures: The ceiling light fixture was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
8.2.1 - Smoke Detectors

Smoke Detectors are Missing
Main Floor Bedroom

The smoke detector is missing.
Smoke alarms provide life-saving warnings to allow people to get out of the house before they are trapped by fire or smoke.

Electrical Contractor
$
Credit
Comment
8.3.1 - Carbon Monoxide Detectors

Carbon Monoxide Detector is Missing
Bedroom 2

The carbon monoxide detector is missing.
Because CO is an odorless, tasteless, and colorless gas, its presence indoors can be detected only through the use of CO detectors. These detectors warn people about the potential for CO poisoning in the same way that smoke detectors warn about the potential for acute fire-related smoke exposure.

Qualified Professional

9 - Loft

IN NI NP D
9.1 General X
9.2 Loft Stairs X
9.3 Carbon Monoxide Detectors X
General: Loft
Loft

Master bedroom is in overall good condition.

Ceiling: Tongue and groove ceiling is in overall good condition. No water leaks or stains were detected at the time of the inspection.
Floor: Carpet floor is in overall good condition.
Walls: Walls in loft are in overall good condition.
Windows: All windows in loft were in working condition at the time of the inspection.
Electric Outlets: All electric outlets were in working condition at the time of the inspection.
Light Fixtures: Ceiling light fixture was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
9.2.1 - Loft Stairs

Loft Stairs
Loft

The stairs coming to loft area should have non slip material. Installation recommended. 

Qualified Professional
$
Credit
Comment
9.3.1 - Carbon Monoxide Detectors

Carbon Monoxide Detector is Missing
Loft

Carbon monoxide detector is missing.
Because CO is an odorless, tasteless, and colorless gas, its presence indoors can be detected only through the use of CO detectors. These detectors warn people about the potential for CO poisoning in the same way that smoke detectors warn about the potential for acute fire-related smoke exposure.

Qualified Professional

10 - Basement Storage Room 1

IN NI NP D
10.1 General X
10.2 Walls X
10.3 Ceilings X
Walls: Wall Material
Drywall
Ceilings: Ceiling Material
Drywall
General: Basement Storage Overview
Basement Storage Room

Basement storage room is in overall good condition.

Floor: Tile floor is in overall good condition. No cracks or missing grout was detected at the time of the inspection.
Doors: Door in basement storage room is overall in good condition.
Light Fixtures: Ceiling light fixture was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
10.2.1 - Walls

Wall Damage
Basement Bedroom 1

There is a minor wall damage noted. 

Qualified Professional
$
Credit
Comment
10.3.1 - Ceilings

Drywall Patchwork
Basement Bedroom 1

There is a drywall patchwork done. Ask homeowner for the reason.



Qualified Professional

11 - Basement Storage Room 2

IN NI NP D
11.1 General X
General: Basement Storage Room 2
Basement Storage Room 2

Basement storage room is in overall good condition.

Ceiling: Drywall ceiling is in overall good condition.
Floor: Tile floor is in overall good condition. No cracks or missing grout was detected at the time of the inspection.
Walls: Walls in the basement storage room is in overall good condition.
Doors: Door in basement storage room is overall in good condition.
Light Fixtures: Ceiling light fixture was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency

12 - Master Bathroom

IN NI NP D
12.1 Toilet X
12.2 GFCI & AFCI X
Master Bathroom Overview
Master Bathroom

The master bathroom is in overall in good condition.

Ceiling: Tongue and groove ceiling was in overall good condition. There were no signs of water damage at the time of the inspection.

Floor: Wood floor in the master bathroom was in overall good condition, and there were no signs of damage at the time of the inspection.

Walls: Walls are in overall good condition.

Cabinets: All cabinets were in working condition, and no damage was detected at the time of the inspection.

Light Fixtures: All light fixtures were in working condition at the time of the inspection.

Plumbing: Plumbing is properly installed with p-trap, and individual shut off valves are installed under the sinks. There was no leak detected at the time of the inspection.

Jet Bathtub: Jet bathtub was in working condition at the time of the inspection.

Toilet: Toilet is in overall good condition. No leaks were detected at the time of the inspection. Water supply to the toilet did not shut off.

Shower: Shower was in working condition at the time of the inspection.


GFCI & AFCI: GFCI in Master Bathroom
Master Bathroom

GFCI in master bathroom is properly installed and was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
12.1.1 - Toilet

Water Supply to the Toilet
Master Bedroom

The water supply was continually running and did not turn off. Repair recommended by a qualify professional.  

Plumbing Contractor

13 - Main Level Bathroom

IN NI NP D
13.1 General X
13.2 Lighting Fixtures, Switches & Receptacles X
13.3 GFCI & AFCI X
General: Main Level Bathroom
Main Level Bathroom

Main Level Bathroom is in overall in good condition.

Ceiling: Tongue and groove ceiling was in overall good condition. There were no signs of water damage at the time of the inspection.

Floor: Wood floor in the main level bathroom was in overall good condition, and there were no signs of damage at the time of the inspection.

Walls: The walls were in overall good condition.

Cabinets: All cabinets were in working condition, and no damage was detected at the time of the inspection.

Light Fixtures: All light fixtures were in working condition at the time of the inspection.

Plumbing: Plumbing is properly installed with P-trap, and individual shut off valves are installed under the sinks. There was no leak detected at the time of the inspection.

Toilet: Toilet was in working condition a the time of the inspection. No leaks were detected at the time of the inspection.

Shower: Shower was in working condition at the time of the inspection.

GFCI & AFCI: GFCI in Main Level Bathroom
Main Level Bathroom

GFCI in main level bathroom is properly installed and was in working condition at the time of the inspection.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
13.2.1 - Lighting Fixtures, Switches & Receptacles

Light Fixture is Not Working
Main Level Bathroom

Part of over the sink light fixture in this bathroom is not working. Recommended repair by a qualify professional.

DIY

14 - Basement Bathroom

IN NI NP D
14.1 General X
14.2 GFCI & AFCI X
14.3 Shower X
General: Basement Bathroom
Basement

Basement bathroom is in overall in good condition.

Ceiling: Ceiling was in overall good condition. There were no signs of water damage at the time of the inspection.

Floor: Tile floor in the basement bathroom was in overall good condition. There were no signs of cracks, and missing grout at the time of the inspection.

Vanity: Vanity was in working condition, and no damage was detected at the time of the inspection.

Light Fixtures: All light fixtures were in working condition at the time of the inspection.

Plumbing: Plumbing is properly installed with P-trap, and individual shut off valves are installed under the sink. There was no leak detected at the time of the inspection.

Bathtub/Shower: Bathtub was in working condition at the time of the inspection. It is missing shower head.

Toilet: Toilet is in overall good condition. No leaks were detected at the time of the inspection.


  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
14.3.1 - Shower

Showerhead is Missing
Basement Bathroom

There is missing showerhead in this bathroom.

Handyman/DIY

15 - Laundry/Utility Room

IN NI NP D
15.1 Room Condition X
15.2 Main Water Shut-off Device, Septic Clean Out X
15.3 Hot Water Heater X
15.4 Heating Equipment X
15.5 Fuel Storage & Distribution Systems X
15.6 Electrical / Plumbing X
15.7 Washer / Dryer X
Water Source
Local Co-op
Dryer Power Source
220 Electric
Dryer Vent
Metal
Main Water Shut-off Device, Septic Clean Out: Location
Basement
Hot Water Heater: Power Source/Type
Electric
Hot Water Heater: Capacity
65 gallons
Hot Water Heater: Location
Basement
Heating Equipment: Brand
Goodman
Heating Equipment: Energy Source
Gas
Heating Equipment: Heat Type
Forced Air
Fuel Storage & Distribution Systems: Main Gas Shut-off Location
At Tank
Booster System Pump
Laundry/Utility Room

CMBE-1-44 Booster System Pump was installed in laundry/utility room. 

It was in working condition at the time of the inspection.

Booster system pump is designed for domestic and commercial water supply, pressure boosting. It keeps a constant pressure in the pipe system. A pressure sensor monitoring discharge pressure will signal to the speed controller to change the motor speed to adapt the performance to the new situation.



Water Softener
Laundry/Utility Room

Impression Plus Series Water Softeners was installed in laundry/utility room. No leaks were detected at the time of the inspection.

https://www.water-right.com/wp-content/uploads/2019/11/SS-IMP-SOFT.pdf


Room Condition: Laundry/Utility Room
Basement

This room is overall in good condition. There were no leaks on ceiling, walls, and floor detected at the time of the inspection.

Main Water Shut-off Device, Septic Clean Out: Main Water Shut Off Valve
Basement

Main water shut off valve was located in the basement in utility/laundry room.

Main Water Shut-off Device, Septic Clean Out: Septic Clean Out Location
Southside

Septic clean out pipe is on the southside of the house. 

Hot Water Heater: Manufacturer
Ruud

I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. 

Here is a nice maintenance guide from Lowe's to help. 

Heating Equipment: Furnace
Laundry/Utility Room

Furnace was inspected via thermostat. It was in working condition at the time of the inspection. 

Heating Equipment: Thermostat Location
Front Room

Furnace thermostat is located near loft stairs.

Fuel Storage & Distribution Systems: Gas Shut Off Valve
Gas Tank

Main gas shut off valve is located on the tank. The gas tank is located south/west from the house.

Electrical / Plumbing: Electrical Overview
Laundry/Utility Room

Electrical system is in overall good condition. The main circuit panel is located in laundry/utility room.
Main panel is Square D system with Romex wiring. Main panel wiring appears to be in correctly wired.    

Electrical / Plumbing: Plumbing Overview

Plumbing appears to be in overall good condition. The were no leaks detected at the time of the inspection. Plumbing under the sinks has P-traps and individual shut off valve installed. Toilets have individual shut off valves installed also.
Water pressure is 30 PSI. 

NOTE:30-80 PSI is considered acceptable.


Washer / Dryer: Washer / Dryer
Laundry/Utility Room

Samsung washer and dryer appear to be in working condition. 

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
15.3.1 - Hot Water Heater

No Drip Pan
Laundry/Utility Room

No drip pan was present. Recommend installation by a qualified plumber.

Drip pan helps prevent damage to finished surfaces due to water heater leaks. It is installed under the water heater.

Plumbing Contractor
$
Credit
Comment
15.7.1 - Washer / Dryer

Dryer Vent is Dirty
Eastside

Lint in the dryer vent can cause fire. Cleaning recommended.

Handyman/DIY

16 - Electrical

IN NI NP D
16.1 Service Entrance Conductors X
16.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X
16.3 Branch Wiring Circuits, Breakers & Fuses X
Service Entrance Conductors: Electrical Service Conductors
Below Ground, Copper, 220 Volts
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Main Panel Location
Basement
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Capacity
200 AMP
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Manufacturer
Square D
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Panel Type
Circuit Breaker
Main & Subpanels, Service & Grounding, Main Overcurrent Device: Sub Panel Location
Garage, Barn
Branch Wiring Circuits, Breakers & Fuses: Branch Wire 15 and 20 AMP
Copper
Branch Wiring Circuits, Breakers & Fuses: Wiring Method
Romex
Service Entrance Conductors: Electrical Location
North East Yard

Service Entrance and Meter

General Findings - Electrical

The interior electrical was in generally good condition.

NOTE: See the section "Barn", for electrical information related to the Shop

NOTE: See the section "Garage", for electrical information related to the Garage

Main & Subpanels, Service & Grounding, Main Overcurrent Device: Electrical Panes Overview
Basement Laundry / Utility Room

The primary distribution panel is in good condition.

The wiring is high quality workmanship.

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency

17 - Garage / Shop

IN NI NP D
17.1 Foundation X
17.2 Exterior X
17.3 Doors X
17.4 Windows X
17.5 Ceiling X
17.6 Walls X
17.7 Garage Door X
17.8 Electrical / Plumbing X
Foundation: Material
Slab on Grade
Garage Door: Material
Vinyl
Garage Door: Type
Up-and-Over
Garage / Shop Overview

The shop is in overall good condition.

No serious issues were observed.

Foundation: Foundation
Garage

The foundation is in overall good condition.

Exterior: Exterior Overview
Garage

The exterior walls were in overall good condition at the time of the inspection.

Doors: Doors Overview
Garage

The doors in the garage are in overall good condition.
One door has rust on the bottom of the door.

Windows: Windows Overview
Garage

The windows in the garage were overall in good condition.
One window could not be inspected.

Ceiling: Ceiling Overview
Garage

The ceiling in the garage is in overall good condition. No stains or leaks were observed at the time of the inspection.

Walls: Walls Overview
Garage

The walls in the garage are overall in good condition.

Garage Door: Garage Door Overview
Garage

The garage door, and garage door sensor were in working condition at the time at the inspection. The garage doors were operated using the garage door openers.

Electrical / Plumbing: Electrical Overview
Garage

Electrical sub-panel could not be inspected in details, it has stuff in front of it .
Light fixtures were in working condition at the time of the inspection.
One receptacle does not work.

Electrical / Plumbing: Plumbing Overview
Garage

Bathroom in the garage is in overall good condition.
Toilet: Toilet was in working condition, there were no leaks detected at the time of the inspection.
Utility sink: Sink was in good condition, no leaks were detected at the time of the inspection.
Dog Shower: Shower was in good condition at the time of the inspection.
Water Heater: Water heater was in working condition at the time of the inspection.
Washer & Dryer: Washer and dryer were in working condition at the time of the inspection.

Windows: Window Obstruction
Garage

One window in the garage could not be inspected due to stuff blocking the pathway.

Electrical / Plumbing: Sub-Panel
Garage

Sub-panel could not be detailed inspected due to stuff in front of it.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
17.1.1 - Foundation

Outside Concrete Slab
Garage

Outside concrete slab has minor cracks in it.

Qualified Professional
$
Credit
Comment
17.2.1 - Exterior

Dent in the Siding
Garage

There was minor dent detected at the right sight of the garage door. 

Qualified Professional
$
Credit
Comment
17.3.1 - Doors

Rust on the bottom of the Door
Garage

There was rust observed at the bottom of the side garage door. No other signs of water intrusion were observed at the time of the inspection. 

Qualified Professional
$
Credit
Comment
17.6.1 - Walls

Minor Cracks Present
Garage

Minor cracks were detected on the wall above door.

Qualified Professional
$
Credit
Comment
17.8.1 - Electrical / Plumbing

One Outlet is Not Working
Garage

One outlet on the exterior of the garage is not working.

Qualified Professional

18 - Garage / Shop Roof

IN NI NP D
18.1 Coverings X
18.2 Roof Drainage Systems X X X
18.3 Flashings X
18.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Binoculars, Ground, UAV
Roof Type/Style
Gable
Coverings: Material
Metal
Roof Drainage Systems: Gutter Material
not present
Flashings: Flashings Overview
Garage

The flashings are installed and in overall good condition.

Flashings: Material
Metal
General Summary
Garage

Overall, the roof covering was found to be in good condition, but there were issues observed.

There is damage in some areas.

There are no gutters. This can cause erosion.

We recommend having the roof reviewed and repaired by a professional.

Skylights, Chimneys & Other Roof Penetrations: Roof Ventilation Pipe Penetration
Garage

Roof pipe penetrations were observed to be in good condition.

Coverings: Roof Overview
Garage

These photos show an overview of the whole roof of the garage.

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
18.1.1 - Coverings

Damaged (General)
North Corner


There is notable damage on the north corner of the roof.

Recommend a qualified roofing professional evaluate and repair. 

Roofing Professional
$
Credit
Comment
18.2.1 - Roof Drainage Systems

Downspouts Drain Near House
Garage

One or more downspouts drain too close to the home's foundation. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement. Recommend a qualified contractor adjust downspout extensions to drain at least 3 feet from the foundation. 

Roofing Professional
$
Credit
Comment
18.2.2 - Roof Drainage Systems

Gutters are Missing
Garage

There are no gutters present on the westside of the structure.  Gutters are recommended because they collect rain water from the roof and direct it away form the building.

Handyman

19 - Barn

IN NI NP D
19.1 Foundation X
19.2 Exterior X
19.3 Doors X
19.4 Windows X
19.5 Ceiling X
19.6 Garage Door X
19.7 Electrical / Plumbing X
19.8 Loft X
Foundation: Material
Slab on Grade, Dirt
Garage Door: Type
Up-and-Over
Barn Overview
Barn

The barn appeared to be in overall good condition. 

No stains or leaks were observed at the time of the inspection. 

The windows and doors were in working condition at the time of the inspection.

Foundation: Concrete Foundation
Barn

The concrete foundation in the barn is in overall good condition.

Exterior: Electrical Overview
Barn

Exterior walls were in overall good condition at the time of the inspection.

There is a small hole that was observed in the siding.

Doors: Doors Overview
Barn

Doors in the barn are in overall good condition.

Windows: Windows Overview
Barn

The windows in the barn area, and upstairs unfinished apartment are in overall good working condition.

Ceiling: Ceiling Overview
Barn

The ceiling in the barn is in overall good condition. No stains or leaks were present at the time of the inspection.

Garage Door: Garage Door Overview
Barn

The garage door, and garage door sensor were in working condition at the time at the inspection. 

The garage door was tested using the garage door opener. 

Electrical / Plumbing: Electrical Overview
Barn

Electrical sub-panel is in overall good condition.
Light fixtures were in working condition at the time of the inspection.
One receptacle does not have a cover.

Loft: Loft Overview
Barn

The loft is unfinished. The framing and electrical wiring are exposed.
Windows: Windows were in working condition at the time of the inspection.
Electrical: All wires are exposed in the electrical boxes.
Insulation: Insulation was not present.
Floor: Sub-floor was installed.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
19.2.1 - Exterior

Hole in the Metal Siding
Barn

There is one notable hole it the siding. 

Qualified Professional
$
Credit
Comment
19.7.1 - Electrical / Plumbing

Frost Free Spigot
Barn

The frost free spigot has no water pressure.


Qualified Professional
$
Credit
Comment
19.7.2 - Electrical / Plumbing

Cover Plates Missing
Barn

One receptacle is missing a cover plate. This causes short and shock risk. Recommend installation of a plate.

Handyman/DIY

20 - Barn Roof

IN NI NP D
20.1 Coverings X
20.2 Roof Drainage Systems X X
20.3 Flashings X
20.4 Skylights, Chimneys & Other Roof Penetrations X
Inspection Method
Binoculars, Ground, UAV
Roof Type/Style
Gable
Coverings: Material
Metal
Roof Drainage Systems: Gutter Material
not present
Flashings: Material
Metal
Flashings: Flashings Overview
Barn

The flashings are installed and in overall good condition.

Coverings: Roof Overview
Barn

The barn roof is in overall good condition. 

These photos show an overview of the whole roof of the barn.

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency
$
Credit
Comment
20.1.1 - Coverings

Debris
North West

There is debris that is accumulating on the snow break.

Debris should be removed every season, in order to keep the roof healthy. 

DIY
$
Credit
Comment
20.2.1 - Roof Drainage Systems

Gutters Missing
Barn

There are no gutters present on the structure.  Gutters are recommended because they collect rain water from the roof and direct it away form the building.

Gutter Contractor

21 - Thermal Imaging

IN NI NP D
21.1 Interior & Exterior X
21.2 Roof X
Thermal General Comments

We inspected the roof, interior, and exterior of the home using FLIR Thermal Imaging cameras.

Our general observations detected no safety issues or serious energy loss anomalies.

The outside temperature was roughly 36 degrees. The ambient temperature inside of the home was 65 degrees.

All photos can be viewed in the attached Thermal Imaging reports.

Interior & Exterior: Interior and Exterior OK

The attached photo report "Thermal Imaging Inspection Interior and Exterior.pdf" contains thermal images of the interior and exterior of the home.

The photos contain high temperature, median temperature and cold temperature readings. 

The camera that was used, is a Flir Thermal camera.

There were no serious energy loss anomalies observed, regarding energy leaks from the interior to the exterior.

Additionally, no issues were observed related to safety.

Roof: Thermal Roof Report OK

The attached PDF Thermal Roof Inspection contains images with a temperature variations.

The camera used is a Flir thermal camera. This camera does not output thermographic temperature specific data. However, the temperature range will capture any anomalies that would be related to energy leaks.

We found no anomalies that would indicate noticeable energy loss.  

  • IN = Inspected
  • NI = Not Inspected
  • NP = Not Present
  • D = Deficiency