1234 Main St.
Billings Mt 59105
12/10/2018 9:00AM

Sample agent
agent

Agent Name

Agency Name
12
Maintenance/informational
4
Deficiencies
3
Safety hazard/immediate concerns

1 - General

Present
Client
Client present at end
Yes
Age Source
Municipal records or property listing
Number of residential units inspected.
1
Weather
Dry (no rain)
Temperature
Cold
Type of property
Single family
Inspection Fee
400
Occupied?
Yes, Furniture or stored items were present

Any Home that is fully/partially furnished or has stored items will slightly limit the scope of inspection including, but not limited to; not being able to see all visible holes in walls, moisture staining, testing of receptacles.

2 - Grounds

R NP NI IN
2.1 Soils / Drainage / Landscaping X
2.2 Driveway X
2.3 Sidewalks / Patios X
2.4 Stairs X
Soils / Drainage / Landscaping: Site Profile
Minor slope
Soils / Drainage / Landscaping: Site sloping addequate

 Site drainage appears to be in overall satisfactory condition. 

Driveway: Material
Poured in place concrete
Sidewalks / Patios: Condition
Required repairs or replacement
Sidewalks / Patios: Material
Poured in place concrete
Stairs : Condition
Appeared serviceable
Stairs : Exterior stair material
Concrete
Driveway: Condition
Serviceable
Limitations

Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only. 

  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
2.2.1 - Driveway

Driveways - Minor

Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway, but no trip hazards were found. The client may wish to have repairs made for cosmetic reasons.

House front Driveway Contractor
Credit
Comment
2.3.1 - Sidewalks / Patios

Reversed drainage on sidewalk/patio.

Sidewalk or patio appear to have negative drainage towards recommend replacement or repair to  avoid further damage to sidewalk or foundation. 

Gardening shovel tool shape Concrete Contractor

3 - Exterior & Foundation

R NP NI IN
3.1 Exterior Walls / Trim X
3.2 Foundation X X
Exterior Walls / Trim: Inspection method
Viewed from ground
Exterior Walls / Trim: Wall cover condition
Appeared serviceable
Exterior Walls / Trim: Wall structure
Wood frame, Not fully visible
Foundation: Condition
Appeared serviceable
Foundation: Material
Poured in place concrete
Foundation: Type
Finished basement, Concrete garage slab
Foundation: Footing material
Poured in place concrete
Exterior Walls / Trim: Wall Cover
Fiberboard
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
3.1.1 - Exterior Walls / Trim

Caulking

Caulk was missing / deteriorated / substandard in some areas. For example, around windows / around doors / at siding butt joints / at siding-trim junctions / at wall penetrations. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
CAULK
Contractor Qualified Professional
Credit
Comment
3.2.1 - Foundation

Cracks - Moderate

Moderate cracks (1/8 inch - 3/4 inch) and/or leaning were found in the foundation. This may be a structural concern or an indication that settlement is ongoing. The client should consider hiring qualified contractors and/or engineers as necessary for further evaluation. Such contractors may include:

  • Foundation repair contractors who may prescribe repairs, and will give cost estimates for such repairs
  • Masonry contractors who repair and/or replace brick veneer
  • Geotechnical engineers who attempt to determine if settlement is ongoing, and the cause of the settlement
  • Structural engineers who determine if repairs are necessary, and prescribe those repairs

At a minimum, recommend sealing cracks to prevent water infiltration. Numerous products exist to seal such cracks including hydraulic cement, resilient caulks and epoxy sealants.

Foundation Foundation Contractor
Credit
Comment
3.2.2 - Foundation

Garage floor Settling

Garage floor appears to be settling.  Interior garage settling is generally cosmetic and gradual.  If cars are parked in garage during winter,  high levels of snow melt off from vehicles can cause quicker settling. Recommend monitoring in the future for rapid settling. 

Gardening shovel tool shape Concrete Contractor

4 - Roof

R NP NI IN
4.1 General X
4.2 Shingles / Shakes X X
4.3 Gutters / Downspouts / Extensions X
General: Condition
Appeared serviceable
General: Roof surface material
Asphalt or fiberglass composition shingles
General: Roof type
Gable
Shingles / Shakes: Layers
One
Gutters / Downspouts / Extensions: Condition
Limited evaluation due to little or no rainfall during and prior to the inspection, Appeared serviceable
General: Limitations

The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free. 

General: Method
Traversed
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
4.2.1 - Shingles / Shakes

Composition - Exposed fastener heads

Nail heads were exposed at one or more shingles. More than just a few exposed nail heads may indicate a substandard roof installation. Recommend applying an approved sealant over exposed nail heads now and as necessary in the future to prevent leaks.
Contractor Qualified Professional
Credit
Comment
4.3.1 - Gutters / Downspouts / Extensions

Debris in drainage systems

Debris has accumulated in one or more gutters or downspouts. Gutters can overflow and cause water to come in contact with the building exterior, or water can accumulate around the foundation. Recommend cleaning gutters and downspouts now and as necessary in the future.

Wrench DIY

5 - Attic & Roof Structure

R NP NI IN
5.1 Access X
5.2 Roof Structure X
5.3 Insulation X
5.4 Ventilation X
Roof Structure: Ceiling structure
Trusses
Roof Structure: Condition
Appeared serviceable
Roof Structure: Roof structure type
Trusses
Insulation: Insulation condition
Appeared serviceable
Insulation: Type
Fiberglass loose fill
Insulation: Vermiculite
None visible
Ventilation: Condition
Appeared serviceable
Ventilation: Types
Enclosed soffit vents, Ridge vent(s)
Access: Method
Viewed from Hatch
Insulation: Rating
R-30

Ratings are based on estimate depths of insulation Present. Insulation depths can greatly vary in different areas of the attic. No guarantee of present R-value.

  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
5.3.1 - Insulation

Compacted or Uneven

The ceiling insulation in one or more areas of the attic was compacted or uneven / missing / substandard. Heating and cooling costs may be higher due to reduced energy efficiency. To increase energy efficiency, recommend that a qualified person repair, replace or install insulation as necessary and per standard building practices (typically R-38).

House construction Insulation Contractor
Credit
Comment
5.3.2 - Insulation

Substandard (< R-38)

The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. To increase energy efficiency, recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.

 

House construction Insulation Contractor

6 - Garage or Carport

R NP NI IN
6.1 General X
6.2 Attached Garage-House Door X
6.3 Vehicle Door X
6.4 Automatic Opener X
6.5 Floor X
6.6 Interior/Walls/Ceilings X
General: Type
Attached
Attached Garage-House Door: Condition
Appeared serviceable
Attached Garage-House Door: Type
Wood, Solid core
Vehicle Door: Condition
Appeared serviceable
Vehicle Door: Type
Sectional
Vehicle Door: # of Doors
2
Automatic Opener: Condition
Appeared serviceable, Not determined (not plugged in or no power
Floor: Condition
Appeared serviceable
Interior/Walls/Ceilings: Condition
Serviceable
Interior/Walls/Ceilings: Ventilation
None visible
Automatic Opener: Unplugged, no power
One or more automatic door openers were not plugged in or had no power. The inspector was unable to fully evaluate the automatic opener(s).
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected

7 - Kitchen

R NP NI IN
7.1 Counters X
7.2 Cabinets X
7.3 Floors X
7.4 Sinks X
7.5 Under-Sink Food Disposal X
7.6 Dishwasher X
7.7 Range/Cooktop/Oven X
7.8 Ventilation X
7.9 Refrigerator X
7.10 Microwave X
Limitations
Counters: Material
Solid surface
Cabinets: Condition
Appeared serviceable
Floors: Type or covering
Vinyl linoleum or marmoleum
Floors: Condition
Appeared serviceable
Sinks: Condition
Appeared serviceable
Under-Sink Food Disposal: Condition
Appeared Serviceable
Range/Cooktop/Oven: Fuel Type
Electric
Ventilation: Type
None visible
Microwave: Condition
Not a permanent fixture
Counters: Condition
Appeared serviceable
Dishwasher: Condition
Appeared serviceable
Refrigerator: Condition
Appeared serviceable
Range/Cooktop/Oven: Condition
Appeared serviceable
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
7.8.1 - Ventilation

No hood or fan

No exhaust hood, ceiling or wall-mounted exhaust fan or downdraft exhaust system was found for the cook top or range. This can be a nuisance for odor and grease accumulation. Where a gas-fired range or cook top is installed, carbon monoxide and excessive levels of moisture can accumulate in living spaces. If desired recommend that a qualified contractor install a venting system per standard building practices.
 
Wrenches Handyman

8 - Basement

R NP NI IN
8.1 General X
8.2 Stairs X
8.3 Handrails X X
General: Limitations
Structural components such as joists and beams, and other components such as piping, wiring and/or ducting that are obscured by under-floor insulation are also excluded from this inspection. Note that the inspector does not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning or spacing. 

The inspector does not guarantee or warrant that water will not accumulate in the basement in the future. Access to the basement during all seasons and during prolonged periods of all types of weather conditions (e.g. heavy rain, melting snow) would be needed to do so. The inspector does not determine the adequacy of basement floor or stairwell drains, or determine if such drains are clear or clogged.

Note that all basement areas should be checked periodically for water intrusion, plumbing leaks and pest activity. 
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
8.2.1 - Stairs

Overhead clearance too low

The ceiling height over stairs at one or more locations was too low and poses a safety hazard, especially for tall people. Ceilings over stairs should be at least 6 feet 8 inches high. At a minimum, be aware of this hazard, especially when guests who are not familiar with the stairs are present. Recommend that a qualified contractor repair per standard building practices.
Contractor Qualified Professional
Credit
Comment
8.3.1 - Handrails

No returns

One or more handrails had no returns installed, where ends of handrails turn and connect to adjacent walls so objects or clothing will not catch on the open ends. This is a safety hazard. For increased safety, recommend that a qualified person install returns per standard building practices.

Contractor Qualified Professional
Credit
Comment
8.3.2 - Handrails

Not continuous or full length

Handrails at one or more flights of stairs were not continuous or did not extend the full length of the stairs. This is a potential fall hazard. Handrails should be continuous for the entire length of the stairs. For Increased safety, recommend that a qualified contractor replace or repair handrails per standard building practices.

Contractor Qualified Professional

9 - Electric

R NP NI IN
9.1 Service X
9.2 Panels X
9.3 Wiring X X
9.4 Receptacles X
9.5 Switches X
9.6 Lighting X
9.7 Exterior X
9.8 Smoke and CO alarms X
Service: Type
Underground
Service: Number of conductors
3
Service: Voltage
120-240
Service: Protection
Breakers
Service: System ground
Not determined
Service: Service entrance conductor material
Stranded Aluminum
Service: Main disconnect rating
150
Panels: Main service panel condition
Appeared serviceable
Panels: Sub-panel(s) condition
Not determined
Panels: Location of MAIN panel #A
Garage
Panels: Location of main disconnect
Breaker at top of main service panel
Wiring: Condition
Serviceable
Wiring: Branch circuit wiring type
Aluminum solid-strand, Copper
Wiring: Solid strand aluminum wiring present
Yes
Service: Condition
West
Appeared serviceable
Service: Amperage
150
Wiring: GFCI present
Yes
Smoke and CO alarms: CO alarms installed
Overview
Yes
Smoke and CO alarms: Smoke alarms installed
Yes, Recommend additional
Limitations

The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection, and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items are present some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110 volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for and placement of smoke and carbon monoxide alarms is not determined as part of this inspection. Upon taking occupancy, proper operating and placement of smoke and carbon monoxide alarms should be verified and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed because the overall capacity may be diminished by lesser-rated components in the system. Any repairs recommended should be made by a licensed electrician. 

  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
9.3.1 - Wiring

AL solid-strand wiring found

One or more branch circuits with solid-strand aluminum wires were found. Problems due to expansion and contraction with this type of wiring can cause overheating at connections between the wire and devices such as switches and receptacles, or at splices. This is a potential fire hazard. The Consumer Products Safety Commission recommends either discontinuing use of circuits with aluminum wiring, removing the wiring, or that an electrician determine if copper wire can be pig-tailed onto the ends of the aluminum wire. A qualified electrician should evaluate the full electrical system and repair as necessary. For more information, visit:

ALWIRE1

ALWIRE2

Electric Electrical Contractor
Credit
Comment
9.3.2 - Wiring

Exposed in attic <6' from hatch, door

Non-metallic sheathed wiring in the attic was routed on surfaces within 6 feet of one or more access hatches or doors, and was subject to damage. Wiring can be damaged when hatches are lifted and set aside, when stored items are moved into or out of the attic, etc. This is a potential shock and/or fire hazard. For increased safety, recommend that a qualified electrician repair per standard building practices.

Electric Electrical Contractor

10 - Plumbing / Fuel Systems

R NP NI IN
10.1 General X
10.2 Service / Main Line X
10.3 Supply Lines X
10.4 Drain and Waste Lines X
10.5 Venting X
10.6 Fuel Systems X
Service / Main Line: Condition
Appeared serviceable
Service / Main Line: Type
Public
Service / Main Line: Water Pressure PSI
70
Supply Lines: Condition
Appeared serviceable
Supply Lines: Type
Copper
Drain and Waste Lines: Drain pipe condition
Appeared serviceable
Drain and Waste Lines: Waste pipe condition
Appeared serviceable
Drain and Waste Lines: Drain pipe material
PVC
Drain and Waste Lines: Waste pipe material
PVC
Venting: Condition
Appeared serviceable
Venting: Vent pipe material
PVC
Fuel Systems: Condition
Appeared serviceable
Fuel Systems: Visible fuel storage systems
None visible
Service / Main Line: Main shut-off location
Basement utility room
Basement, In utility room
Fuel Systems: Location of main fuel shut-off
Back yard
At gas meter, At building exterior
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected

11 - Water Heater

R NP NI IN
11.1 General X
11.2 Tank Casing X
11.3 Bonding X
11.4 TPR Valve X
11.5 Water Shut off X
11.6 TPR Drain Line X
11.7 Burners X
11.8 Flues X
General: Energy source
Natural gas
General: Capacity
50
General: Location
Utility room, Basement
General: TPR valve
Yes
Burners: Condition
Appeared serviceable
Flues: Condition
Appeared Serviceable
General: Condition
Utility Room
Appeared serviceable
General: Type
Tank
General: Estimated Age
2009-09-12T06:00:00.000Z
General: Water Temp
125.4
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
11.1.1 - General

Water temp over 120 degrees

If the water temperature is set too high it can cause scalding burns to users. If a high setting is desired, care should always be taken to blend in enough cold water for safety. Areas that are used by children should have blending valves installed to ensure they do not accidentally set the temperature too high. Alternatively, when adjusting the water temperature, ensure it is kept below a safe level.

12 - Fireplaces, Stoves, Chimneys and Flues

R NP NI IN
12.1 General X
12.2 Fireplace X
12.3 Chimney & Flues X
Chimney & Flues: Condition
Appeared serviceable
Chimney & Flues: Gas-fired flue type
B-vent
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected

13 - Heating, Ventilation and Air Condition (HVAC)

R NP NI IN
13.1 General X
13.2 Heating X
13.3 Forced Air X
13.4 Filters X
13.5 Ducts & Registers X
13.6 Burners (furnace or boiler) X
13.7 Combustion Air X
13.8 Flues X
13.9 Heat Pump; AC X
13.10 Normal Controls X
13.11 Ventilation X
Heating: Distribution Type
Ducts and registers
Heating: Heating Type
Forced air, Furnace
Heating: Primary heating last service date
Unknown
Forced Air: Condition
Appeared serviceable
Forced Air: Fuel Type
Natural gas
Forced Air: Location
Utility room, Laundry room
Forced Air: Serial number

1311452899

Forced Air: Estimated age

0-5years

Filters: Condition
Recommend replacing upon taking occupancy, Appeared serviceable
Filters: Filter location
At base of air handler
Ducts & Registers: Condition
Appeared serviceable
Burners (furnace or boiler): Condition
Appeared serviceable
Combustion Air: Type
No dedicated source visible uses room air
Flues: Condition
Appeared serviceable
Heat Pump; AC: Cooling fuel type
Electric
Heat Pump; AC: Location
Building exterior, west
Heat Pump; AC: Type
Through wall
Normal Controls: Condition
Appeared serviceable
Heating: Date of Manufacture
05/12/2018
Forced Air: Model number

GMH950904CXAG

Heat Pump; AC: Date of Manufacture
01/12/2017
Heat Pump; AC: Condition
Appeared serviceable
Heat Pump; AC: Temperature Difference

Temperature differences were between 14-20 which is optimal for service efficiency. 

  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected

14 - Bathroom, Laundry and sinks

R NP NI IN
14.1 Counters X
14.2 Cabinets X
14.3 Floors X
14.4 Sinks X
14.5 Toilets X
14.6 Bathtubs X
14.7 Showers X
14.8 Ventilation X
14.9 Laundry X
Counters: Condition
Appeared serviceable
Cabinets: Condition
Appeared serviceable
Floors: Condition
Appeared serviceable
Floors: Type or covering
Laminate
Sinks: Condition
Appeared serviceable
Toilets: Condition
Appeared serviceable
Bathtubs: Condition
Appeared serviceable
Showers: Condition
Appeared serviceable
Ventilation: Condition
Appeared serviceable
Ventilation: Bathroom and laundry ventilation type
Spot exhaust fans
Laundry: 240 present
Yes
Laundry: Gas supply for laundry equipment present
Yes, Capped/not in use
Location #A
Full bath, Master bath
Location #B
Full bath, first floor
Location #C
3/4 bath, basement
  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected

15 - Interior, Doors and Windows

R NP NI IN
15.1 Exterior Doors X
15.2 Interior Doors X
15.3 Windows & Skylights X
15.4 Walls, Ceilings and Fixtures X
15.5 Floors X
15.6 Stairs/Handrails/Gaurdrails X
Exterior Doors: Condition
Appeared serviceable
Interior Doors: Condition
Appeared serviceable
Windows & Skylights: Condition
Appeared serviceable
Windows & Skylights: Window Type
Vinyl, Sliding
Walls, Ceilings and Fixtures: Ceiling type or covering
Drywall
Walls, Ceilings and Fixtures: Condition
Appeared serviceable
Walls, Ceilings and Fixtures: Wall type or covering
Drywall
Floors: Condition
Appeared serviceable
Floors: Concrete slab condition
Not visible
Floors: Type or covering
Carpet, Laminate
Stairs/Handrails/Gaurdrails: Condition
Appeared serviceable
Limitation

The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as nail-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Determining the cause and/or source of odors is not within the scope of this inspection.

Exterior Doors: Exterior door material
Metal, Sliding glass
Windows & Skylights: New windows

Windows appear to be almost new. Most likely less than one year old. Recommend asking sellers for any possible warranty transfer information.

  • R = Recommendations
  • NP = Not Present
  • NI = Not Inspected
  • IN = Inspected
Credit
Comment
15.1.1 - Exterior Doors

Doors
Garage

One or more exterior doors were difficult to open or close / were difficult to latch / were sticking. Recommend that a qualified person repair as necessary.
 
Contractor Qualified Professional
Credit
Comment
15.2.1 - Interior Doors

Wouldn't latch
Basement utility room

One or more interior doors wouldn't latch or were difficult to latch. Recommend that a qualified person repair as necessary. For example, by adjusting latch plates or locksets.
Contractor Qualified Professional
Credit
Comment
15.5.1 - Floors

Squeaky

Squeaking or creaking noises occur when walking on one or more sections of flooring. This is usually caused by substandard construction practices where the sub-floor decking is not adequately fastened to the framing below. For example, not enough glue was used and/or nails were used rather than screws. In most cases, this is only an annoyance rather than a structural problem. Various solutions such asSqueeeeek No More and Counter Snap fastenersexist to correct this. Repairs to eliminate the squeaks or creaks may be more or less difficult depending on the floor covering and the access to the underside of the sub-floor. Recommend that a qualified contractor evaluate and repair as necessary. For more information, visit:
SQUEAK
Contractor Qualified Professional